Professional Documents
Culture Documents
Photovoltaic Generation Penetration Limits in Radial Distribution Systems
Photovoltaic Generation Penetration Limits in Radial Distribution Systems
Photovoltaic Generation Penetration Limits in Radial Distribution Systems
system. However, PVDG dispatch techniques need to be clearly in customers’ revenue, since the generation installed at the end
defined, so that they may be applied when Smart Grid becomes of the line would have higher power limitations than those con-
fully operational. Planning studies must take high PVDG pene- nected nearer to the substation [5]. Voltage may also be reduced
tration levels into consideration, so that impacts on the distribu- by controlling the reactive power. The PVDG power factor may
tion network may be analyzed and control techniques defined. be controlled by the power electronic devices of the converter,
The present paper outlines a theoretical framework regarding regulating voltage while active power is being supplied. How-
PVDG penetration limits in radial distribution systems, fo- ever, in certain situations, losses in the network may be high [5].
cusing on voltage rises and conductor ampacity. It presents On the other hand, with greater DG penetration, PVDG
and discusses studies proving that conductor ampacity and systems may prove to be an interesting voltage regulation
voltage rises are limiting factors that manifest themselves tool, acting in cooperation with other more usual means (e.g.,
under different conditions. Simulations were carried out on a voltage regulators, shunt capacitors, and transformer on-load
generic two-bus distribution system model and the maximum tap changers). A large portion of PVDG generation may ac-
amount of PVDG that may be accommodated considering each tively participate in voltage control by adjusting active and
of the criteria was determined. Depending on the load and the reactive power production [12]. The existence of a communi-
power factor (PF), the substation voltage was adjusted in order cations system interconnecting customers and utility may help
to analyze the impact on the amount of PVDG. Lastly, some to control voltage in worst-case scenarios [15].
concluding remarks are made regarding situations in which There are several ways to increase PVDG penetration in dis-
certain criteria are more restrictive. tribution systems from a voltage rise perspective [5]. For ex-
ample, one way of accommodating more DG is to reduce the
II. DISTRIBUTED GENERATION PENETRATION series impedance of the line. To do this, it is necessary to re-
CONSTRAINT FACTORS inforce the feeder, either by increasing the number of conduc-
A consensus is yet to be reached regarding DG penetration tors per phase or by substituting the conductors with others of
limits in distribution systems. Various limits are found in the greater cross-sections. This solution reduces voltage drops and
bibliography, ranging from 5% to up to 100% of the load [7], losses, but the associated cost is quite prohibitive. Besides, this
[8]. The reverse flow of power from load bus bars to the substa- increases short circuit currents, affecting protection devices and
tion provokes an impact on the feeder voltage profile, increasing the interruption capacity of circuit breakers accordingly [8].
bus voltages [5]–[15]. This is usually pointed out as a major con- The modification of steady-state voltage limits also affects
cern regarding DG penetration. However, another important as- DG penetration limits in distribution systems. The concern re-
pect must be considered in determining the PVDG penetration lated to voltage rises is aggravated when generation is located
in a distribution feeder: the actual line and transformer current near the end of the line, since the impedance seen from the DG
carrying capacity [5], [6]. IEEE Std. 1547-2003 “IEEE Standard to the substation is greater. The amount of PVDG that may be
for Interconnecting Distributed Resources with Electric Power installed in a feeder is not an absolute number, since it depends
Systems” establishes criteria and requirements for some relevant on the location of sources along the line sections [5].
aspects, such as the DG shall not cause the voltage to go outside
steady-state limits. However, this standard does not define the B. PVDG Penetration Limits From a Conductor
maximum DG capacity that may be interconnected to a single Ampacity Perspective
point of common coupling or connected to a given feeder [9]. Power injected by the DG must not surpass the current con-
It is considered that two basic steady-state operation criteria duction capacity of lines and transformers. Feeders supplying
must always be met, regardless of whether generation is cen- consumer units should not have their cross-sections reduced,
tralized or distributed: 1) voltage must remain within certain as prescribed by technical norms that consider the coincidence
limits, typically between 0.95 and 1.05 pu; and 2) lines and factor, to avoid restrictions to the DG power injection capacity
transformers must not be submitted to overloads. When these [5]. Generally, the dimensioning of low-voltage lines uses a co-
criteria are met, it is possible to determine the amount of PVDG incidence factor, since the load individual maximum demands
that may be injected into a distribution system. do not occur at the same time. However, the coincidence factor
for PVDG generation is much greater, since an entire distribu-
A. PVDG Penetration Limits From a Voltage Rise Perspective
tion feeder may be exposed to the same irradiance, therefore
PVDG penetration must consider admissible voltage limits, enabling all PVDG systems to reach maximum output power
which depends, among other factors, on line impedance [7]. Due simultaneously. This may limit PVDG penetration, and some
to voltage regulators (e.g., transformer on-load tap changer), authors state that the installed peak capacity must be lower than
the voltage at the substation is kept constant; thus, the oppo- the coincident load [6].
site flow of power from the load bus bars towards the substa-
tion provokes the voltage to rise along the feeder. The limit to
III. PVDG PENETRATION LIMITS
the PVDG power injection is identified when the upper voltage
limit is attained. The voltage rise in the low voltage circuits (i.e., Simulations were carried out to determine the maximum
secondary of transformers) can also be significant, and should amount of PVDG that may be installed in a distribution system,
be included in the analyses [11], [15]. considering both voltage rise and line capacity criteria. Several
One way of limiting voltage rises is by reducing the power configurations were analyzed, with regard to substation voltage
injected by PVDG when voltage reaches the upper limit. How- and different load conditions. The simulations were performed
ever, this option would require measures to compensate losses in Matlab® with the power flow program MatPower [16].
SHAYANI AND DE OLIVEIRA: PHOTOVOLTAIC GENERATION PENETRATION LIMITS IN RADIAL DISTRIBUTION SYSTEMS 1627
A generic 13.8-kV, triphase, symmetric, balanced radial Fig. 2. Voltage at the load bus and line current as a function of P at rated
load.
line is considered, comprised of an aluminum conductor with
cross section 4/0 AWG ( , ,
). The substation that supplies energy to
this line is modeled as an infinite bus. The line is 2.85 km locally, and the surplus is injected into the grid. The PVDG gen-
long; this length was defined in order to allow a 5% voltage eration is increased until the upper voltage limit is reached (i.e.,
drop under rated conditions. The active power at the load bus ) at the load bus (Fig. 2).
corresponds to that which is consumed by the load , In the base case, without PVDG, the load consumes
produced by the PVDG , and supplied through the line and . By increasing the
. amount of PVDG until it supplies all the active power of the
In order to simplify load flow calculations, the entire load is load (i.e., ), the voltage at the load bus rises to
concentrated at the end of the line and step-down transformers . In this situation, the voltage at the load bus
are not represented (Fig. 1). Besides, the following assumptions is lower than that at the substation , since the
have been made: 1) line is modeled only by its series impedance. reactive power of the load continues to be supplied through
Shunt capacitances may be neglected, since the line is short; 2) the line. As only reactive power flows through the line, the
the line may be loaded up to its rated capacity; 3) the substation substation is supplying the equivalent to a load with a null
voltage is taken as reference and is kept constant, since there power factor (not considering the active losses in the line). It
normally exist voltage regulators, such as on-load tap changer; thus becomes clear that the amount of PVDG may be greater
4) no capacitor banks nor any other voltage control devices than the maximum value of the load, for no limit was reached
are used throughout the line; 5) PV generation is modeled as yet.
a constant power injection [10], [15]; 6) the load is modeled By further increasing the amount of PVDG, it may be ob-
as constant power; 7) PV systems operate with a unity power served that the upper limit of the voltage at the load bus (i.e.,
factor, i.e., they generate only active power, in order to repre- ) is reached for (i.e.,
sent the typical situation of products readily available on the and ) flowing from the
market; and 8) the steady-state lower and upper voltage limits load bus towards the substation. In this situation, the amount
are and , respectively. of PVDG corresponds to 160% of the load active power, but
the current at the line represents only 64.6% of its rated ca-
pacity. The amount of PVDG was limited by the voltage rise,
since the line would be capable of conducting more power to-
A. Rated Load wards the substation. However, the load could be damaged with
steady-state voltage above the limit.
Initially, the rated load configuration is considered, dimen-
sioned so as to use the entire conductor capacity. Since a single B. Effects of Changing the Substation Voltage
4/0 AWG aluminum conductor feeder supports 314 A in steady-
state operation, the maximum power conducted is 7.5 MVA. Since previous simulations demonstrated that the first limit
This value is adopted as the power base for per unit (pu) calcu- reached is at the load bus, one way of increasing the
lations. Considering a 0.92 lagging power factor, the reference amount of PVDG is to reduce the voltage at the substation (i.e.,
for the Brazilian electric power system, the load is modeled with reference bus). However, the voltage at the substation must en-
and . sure the load is always supplied within the adequate voltage
With the voltage at the substation fixed at , limits. In this regard, six base cases were developed, each corre-
the voltage at the load bus is , considering rated sponding to a different voltage value at the substation, ranging
load and null PVDG production. The amount of PVDG is then from 1.050 pu to 1.000 pu. Then, based on each base case (i.e.,
incremented in the load bus. Since the PV system injects only without PVDG), simulations were carried out increasing the
active power, the active component of the load is thus supplied power injected by PVDG until the upper voltage limit is reached
1628 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 26, NO. 3, AUGUST 2011
TABLE I TABLE II
PVDG MAXIMUM AMOUNT CONSIDERING THE UPPER PVDG MAXIMUM AMOUNT CONSIDERING BOTH THE UPPER VOLTAGE
VOLTAGE LIMIT CRITERION (VALUES IN pu) LIMIT AND THE CONDUCTOR AMPACITY CRITERIA (VALUES IN pu)
TABLE III
PVDG MAXIMUM AMOUNT AS A FUNCTION OF THE LOAD CONDITION
CONSIDERING THE UPPER VOLTAGE LIMIT CRITERION (VALUES IN pu)
Fig. 3. Voltage at the load bus and line current as a function of P at rated
by the load . In fact, when is twice
load.
, the apparent power flowing through the line is the
same as in the base case (with null PVDG), and thus, there is
at the load bus (Table I). Although Table I includes line cur- no line overload. However, voltage rises more slowly when
rents, this criterion was not considered in the analysis. Shaded the active and reactive power flow in opposite directions, since
cells in Table I indicate the limiting criterion, where the interac- the voltage rise caused by the active component of the current
tive process of increasing PVDG production is stopped flowing towards the substation is partially offset by the voltage
. drop caused by the reactive component flowing towards the
The simulations showed that with , up to 1.81 load.
pu of PVDG may be installed at the feeder. This represents an
increase of 22% in PVDG over the amount in the previous case, C. Effects of the Load Condition
with only a 0.010 pu reduction in the voltage at the substation. In the following simulations, the substation voltage was set
For lower values of , greater amounts of PVDG could be to , since it allows larger amounts of PVDG
injected, without surpassing the upper limit of the voltage at than . This value provides a better regulation,
the load bus. However, for values lower than 1.038 pu, the allowing the voltage to drop during heavy load (0.95 pu), and to
current in the line surpasses its rated value, characterizing an rise during high PVDG generation periods (1.05 pu). This sym-
overload at conductors. metric regulation provides a better assessment of the behavior
Fig. 3 presents the variation in the modules of voltage and of the voltage and current as a function of the amount of PVDG.
of line current as a function of , for . It Maintaining the reference bus voltage at and
may be noted that, considering only the voltage limit, the current considering , ten new cases were set up, in order to
reaches 221% of the conductor ampacity. Restricted by both assess how the amount of load affects the voltage at the load
criteria (i.e., voltage rise and conductor ampacity), a of bus and, consequently, influences the PVDG penetration limit.
is obtained, as opposed to . With Simulations were carried out for load conditions varying from
this result, a second set of simulations was carried out, based on 100% to 10% of the rated value, covering light, medium, and
the same base cases. The amount of PVDG was increased until heavy load conditions (Table III). Shaded cells in Table III in-
either the upper voltage or the line current limit was reached dicate the limiting criterion, where the interactive process of in-
(Table II). Shaded cells in Table II indicate which criterion was creasing PVDG production is stopped .
first reached in each case. Negative values indicate that As the load is reduced in the situation with no PVDG gener-
power flows from the load bus towards the substation. ation, lower currents flow through the line, with lower voltage
For substation voltages ranging between 1.030 pu and 1.000 drops, which bring the voltage at the load bus closer to its upper
pu, it may be noted that the amount of active power injected limit. For example, at rated load, the voltage is ,
in the system is approximately equal to the amount consumed and at 10% of the rated load, the voltage is .
SHAYANI AND DE OLIVEIRA: PHOTOVOLTAIC GENERATION PENETRATION LIMITS IN RADIAL DISTRIBUTION SYSTEMS 1629
TABLE IV TABLE VI
PVDG MAXIMUM AMOUNT AS A FUNCTION OF THE LOAD PVDG MAXIMUM AMOUNT AS A FUNCTION OF THE LOAD POWER
CONDITION CONSIDERING BOTH THE UPPER VOLTAGE LIMIT FACTOR CONSIDERING BOTH THE UPPER VOLTAGE LIMIT AND
AND THE CONDUCTOR AMPACITY CRITERIA (VALUES IN pu) CONDUCTOR AMPACITY CRITERIA (VALUES IN pu)
B. Voltage Rise
The simulations showed that the upper voltage limit was re-
strictive only for substation voltage (Table II).
With (Tables IV and VI), the conductor ampacity
limit proved to be more restrictive than the voltage rise limit at
the load bus, regardless of the load condition or its power factor.
Consider as an example the situation of rated load and unity PF.
When , maximum current flows from the substation to-
wards the load bus, provoking a voltage drop in the line. When
PV generation is at its maximum , the cur-
rent is also at a maximum, but flows from the load bus towards
the substation. In this case, the voltage drop was
, and the voltage rise was .
TABLE VIII
P VALUES: COMPARISON BETWEEN 1) SIMULATIONS Assuming the same current amplitude, same line parameters,
AND 2) EQUATION (1) (VALUES IN PU) and same voltage at substation , the voltage drop for null
PVDG and the voltage rise for maximum PVDG have approx-
imately the same value (i.e., the voltage drop is slightly higher
than the voltage rise):
(2)
(3)
From the simulations, the voltage drop and voltage rise were
determined for several different conditions (Table IX). Results
confirm that and are approximately equal,
where power of the load, in pu. with the voltage drop slightly higher than the voltage rise. The
A comparison between the values obtained with simu- values are not exactly the same because the load was modeled
lations and those calculated by (1) indicates that the error is less as constant power, and thus, the current varied with the voltage
than 3% for the main cases (Table VIII). This error is caused at the load bus. From Table VIII, one can see that the voltage
by different load models adopted in simulations (i.e., constant rise is for rated load and . In order
power) and in (1) (i.e., constant current). PF values less than 0.5 not to reach the voltage criteria, it is necessary that the voltage
are not shown because the corresponding active power is too at the substation be . For all other conditions,
small to affect the system. it can be noted that all voltage rises are lower than the voltage
With the help of this mathematical formula, one can deter- drops, indicating that could be even greater than 1.000 pu
mine the amount of PVDG that can be installed in a radial dis- [i.e., as would be calculated by (3)].
SHAYANI AND DE OLIVEIRA: PHOTOVOLTAIC GENERATION PENETRATION LIMITS IN RADIAL DISTRIBUTION SYSTEMS 1631