com
xEffect
RCDs for machines and
equipment with electrical drives
Enhanced reliability in drive applications
Optimized interaction of
Eaton drives and RCDs
Eaton takes up this problem and offers a It is clearly recommended and in many To learn how harmonized RCDs and Eaton
complete solution from one hand. The cases already mandatory to use RCDs drive solutions can provide increased ener-
interaction between Eaton drives and type F and Bfq for such applications. gy efficiency with maximum
RCDs is harmonized. Unwanted trips They give the possibility to offer a safe and productivity and machine uptime, down-
because of system caused earth leakage reliable operation of the machine with a load the Whitepaper here
currents will be avoided and a safe power high system uptime. www.eaton.eu/en/cp/rcd
disconnection in case of dangerous fault
currents is guaranteed.
Benefits:
• Reliable protection for machines with
1 phase frequency converters
Definition
The type F RCD is defined according to affecting their standard functionality, have voltage independent and can be used for
IEC/EN 62423. It provides safe and reliable a time delayed tripping and distinguish fault and additional protection. As a result,
protection against sinusoidal residual themselves from other devices thanks to the recommendations for installations
currents and pulsating DC fault currents their high resistance to power surges: this including variable frequency drives have
(like type A devices). It is also capable ensures minimal false tripping and a high been modified.
of handling residual currents with mixed degree of safety.
frequencies of up to 1 kHz (10, 50, 1000 Eaton also offers a digital version of the
Hz) in accordance with the IEC 62423 They are available as RCCBs (2-pole or type F RCBO, which displays fault currents
standard. 4-pole up to 100 A) as well as RCBOs at the device in real time.
(1N up to 40 A). With three versions for
Type F RCDs can accept smooth DC different protection levels (30 mA, 100 mA
residual currents of up to 10 mA without and 300 mA), the type F functionality is
Field of Application
Type F residual current devices are de- The detection of mixed frequencies and The time delayed tripping and the high
signes specifically for use in applications the higher load rating with DC residual cur- current withstands capability support in ad-
with single phase frequency converters rents up to 10 mA enables the RCD type F dition avoiding nuisance tripping. Overall,
such as pumps, welding units, vibrators or to provide excellent protection for humans the RCD type F enables machine builders
hammer drills. In this type of application, and the system in all applications which and plant manufacturers to develop
residual currents with mixed frequencies contain appliances and motors with single equipment that is extremely reliable while
can arise which residual current devices phase frequency converters. ensuring high safety levels for the operator
type AC and A are unable to cope with. and maintenance staff.
Benefits:
• Reliable protection for machines with
3 phase frequency converters
Definition
The RCCB type B detects (acc. to IEC The special adapted tripping curve The RCCB type B+ is sensitive to all resid-
62423) beside AC and pulsating DC (non-sensitive against system caused ual currents and is additionally equipped
residual currents also smooth DC residual earth leakage currents at high with a tripping curve that limits the trip-
currents. With the extended sensitivity frequencies) of the RCCB type Bfq ping current to max. 420 mA for frequen-
of the RCCB type B, electrical installers complies to the specifications of the cies up to 20 kHz.
and machinery builders can increase the RCCB type B and avoid in addition This complies additionally to the
safety considerably in power distribution unwanted tripping in industrial specifications for superior fire protection
and machineries. applications which contain frequency according to the German standard VDE
converter controls. 066-440 (formerly VVDEV 0664-110).
Field of Application
Smooth DC residual currents can occur They are also equipped with a time de- RCCBs type B+ are perfectly suitable for
in industrial, commercial and residential layed tripping and a high current withstand installers and machinery builders to in-
applications which contain photovoltaic capability to offer high reliability for the crease safety in fire risk applications such
systems, frequency converters or electron- system. as petrol stations, agriculture, paint shops,
ic consumers. In this kind of applications depots, warehouses and many more.
only RCCBs type B, Bfq or B+ can gua- RCCBs type Bfq with their special adapted
rantee a safe protection for persons and tripping curve are the perfect choice for in-
equipment. dustrial applications with 3 phase frequen-
cy converters.
• Appliances and motors with • Appliances and motors with 1 phase frequency converters with PFC (Power Factor Compensation) or
1 phase frequency converters • 1 phase frequency converters supplied between phase/phase or
(supply: phase/neutral)
• 3 phase frequency converters
• DC systems (photovoltaic systems, UPS units…)
• Washing machines, dishwashers • PV systems Industrial applications which Fire risk applications such as:
• Heat pumps • Battery banks contain high-power frequency
converter controls such as:
• Motor applications • UPS units • Petrol stations
• Ventilation, cooling and • EV charging • Agriculture
5
air conditioning systems • 3 phase motor applications
• Medical devices • Paint shops
• Welding equipment • Speed regulated machine tools
• etc. • Warehouses
• etc. • Biogas plants, etc.
• VDE 0664-400
F B Bfq B+
Correct installation
Possible residual current waveforms of applications with
frequency converters and suitable RCDs
300 mA 300 mA Suitable
Suitable
RCD
RCCB Circuit
Circuit Load Current
Load Current Residual
ResidualCurrent
Current
F B/Bfq/B+ Type
Type
B F /L /L /F1
~
L1
30 mA 30 mA 30 mA 30 mA 30 mA 30 mA N /M M
/F2 t t
PE –
1
F F B/Bfq/B+ F F B/Bfq/B+
B+ /F2
kHz
/L /L /L
~
Bfq L
M
PFC
2 N
/F1 – /F2 t t
PE
6
for applications with 1 phase frequency
converters. But there are also 1 phase t
300 mA FC designs which require RCD type B
protection. /L /F1
A/F ~ /L
L1
RCDs type F are not suitable for appli- L2 M
3 N+ /M –
ances that can generate smooth DC /F2 t
PE t
30 mA 30 mA residual currents, e.g. 1 phase FC with
PFC or 1 phase FC supplied between /F2
A/F B/Bfq/B+
phase/phase.
t
They are not suitable for installations in
networks with frequencies that deviate
from the rated frequency 50/60 Hz (not /L /L /F1
~
at the outgoing terminal of a frequency L1
L2 M
converter). 4 L3
/M – t
N+ /F2
PE
Electrical loads that can generate smooth
DC residual currents in the event of a fault /F2
B/Bfq/B+
F B/Bfq/B+ F F B/Bfq/B+
Possible residual current waveforms and suitable RCDs
Suitable
SuitableRCD
RCCB- Type
– Type Circuit Circuit LoadLoad
Current
Current Residual Current
Residual Current
/L /L /F1
B F A AC
L
1
N /F
t t
PE
/L /L /F1
B+ L
2
N /F t t
PE
a a
/L /L /F1
kHz
L
Bfq 3
N /F t t
PE
L
4
N /F
t t
PE
/L /F1
/L /L /L /F1
L
5 N
/F t t
PE
a a
/L /F1
/L
L
6 N
/F t t
PE
/L /L /F1 /F2
~
L1
7 M
N /M – t
/F2 t t
PE
/L /L /F1
L
8
N – /F t t
PE
/L
L1 /L /F1
L2
9 L3
N /F t t
PE
/L /L /F1
L1
10 L2
N /F
PE t t
/L /L /L /L
~
L
PFC
M
11 N
/F1 – /F2 t t t
PE
/L /F2
~ /L /F1
L1
L2 M
12
N+ /M – t
/F2 t t
PE
/L /L /F1
L1
L2
13 L3
N /F t
PE
/L /L /F1 /F2
~
L1
14 L2 M
L3
/M – t t
N+ /F2
PE
The table shows the possible residual cur- al currents, e.g. 1 phase FC with PFC or Electrical loads that can generate smooth
rent waveforms and the suitable RCDs. 1 phase FC supplied between phase/ DC residual currents in the event of a
phase (see Table, Possible residual current fault must be assigned to their own circuit
In general, RCDs type F are designed
waveforms and suitable RCDs, circuits with a universal current-sensitive residual
for applications with 1 phase frequency
8 to 13). current protective device (type B, type Bfq
converters. But there are also 1 phase
or type B+).
FC (frequency converters) designs which They are not suitable for installations in
require RCD type B protection. networks with frequencies that deviate For more details see Eaton Whitepaper
from the rated frequency 50/60 Hz (not „RCDs&Drives“.
RCDs type F are not suitable for applica-
at the outgoing terminal of a frequency
tions that can generate smooth DC residu-
converter).
7 EATON CORPORATION BR019004EN
Eaton hat sich das Ziel gesetzt, durch den Einsatz seiner Energiema-
nagement-Technologien und -Dienstleistungen für mehr Lebensqualität
zu sorgen und die Umwelt zu schützen. Die nachhaltigen Lösungen
helfen den Kunden, elektrische, hydraulische und mechanische Energie
sicherer, effizienter und zuverlässiger zu nutzen. Eaton erzielte im Jahr
2019 einen Umsatz von 21,4 Milliarden Dollar und verkauft Produkte in
mehr als 175 Ländern. Weltweit arbeiten rund 95.000 Mitarbeitende bei
Eaton.