Beam Design
Beam Design
Beam Design
A
TB-1 TB-1 TB-1
Beam
Beam Size Reinforcement Stirrups
Mkd.
B(mm) D(mm) Top Bottom
TB-1 300 600 4-T16 4-T16 2L-10T@150c/c
TB-2 400 600 4-T20 3-T20 2L-10T@200c/c
TB-3 250 400 3-T16 3-T16 2L-10T@150C/C
1B4
1B4 1B4 1
1 B
1 B 1 4
1 B 3 1B4
B
B 3 3
2 1
1 1 B
1B3 B 1B3
B 2
2 1 2
1 B
B 1B3 1B3 3
4
1B3 1B3
Y X
Z
Load 2055
Beam
Mkd. Beam Size Reinforcement Stirrups
2B3 2B3
2B5 2
2
B 2 2 2 B
2 B B B 2
4 2 4 2
B
2B3 2B3 2
Y X
Z
Load 2055
Beam
Beam Size Reinforcement Stirrups
Mkd.
B(mm) D(mm) Top Bottom
2B1 300 600 4-T25 4-T20 2L-10T@150 c/c
2B2 400 600 4-T25 4-T25 2L-10T@150 c/c
2B3 300 450 3-T16 3-T16 2L-10T@150 c/c
2B4 400 600 3-T20 4-T25 2L-10T@200 c/c
2B5 250 400 3-T12 3-T16 2L-10T@200 c/c
R R RB4
B B
3 3
R R
B R B
2 B 2
RB3 R RB3
B 2
2
Y X
Z
Load 2055
Beam
Mkd. Beam Size Reinforcement Stirrups
YX
Z
Load 2055
SB1
Stair roof beam Layout
Beam
Beam Size Reinforcement Stirrups
Mkd.
B(mm) D(mm) Top Bottom
SB1 300 600 3-T16 3-T16 2L-10T@175 C/C
SB2 250 400 2-T12 2-T16 2L-10T@200 C/C
Design Of interior Beam : (As T Beam)
Loading Data:
Parameters:
Concrete characteristic strength,fc' = 25 N/mm2 = 3625.95 psi
Beam Size:
Width =bw= 300 mm = 11.8 in
Depth = D = 600 mm = 23.6 in
Clear cover = 35 mm = 1.4 in
Column Size:
Width= 450 mm = 17.7 in
Depth= 450 mm = 17.7 in
Calculation:
bf = 1006 mm = 39.62 in
Where, β1 = 0.85
M u ≤ φ Mn
Where, φ = 0.9
Mn = As x fy x(d- a/2)
Minimum Reinforcement:
Shear Design:
Where, φ= 0.75
Vn = Vc + Vs
Vu = 20.16 kips
>Vu,Sectional dimension is ok
Shear Reinforcement:
φVs ≥ Vu - φVc
Where, Vs = Av x fy x d/s
s= NA in
Loading Data:
Parameters:
Concrete characteristic strength,fc' = 25 N/mm2 = 3625.95 psi
Beam Size:
Width =bw= 400 mm = 15.7 in
Depth = D = 600 mm = 23.6 in
Clear cover = 35 mm = 1.4 in
Column Size:
Width= 450 mm = 17.7 in
Depth= 450 mm = 17.7 in
Calculation:
bf = 1106 mm = 43.55 in
Where, β1 = 0.85
M u ≤ φ Mn
Where, φ = 0.9
Mn = As x fy x(d- a/2)
Minimum Reinforcement:
Shear Design:
Where, φ= 0.75
Vn = Vc + Vs
Vu = 29.64 kips
>Vu,Sectional dimension is ok
Shear Reinforcement:
φVs ≥ Vu - φVc
Where, Vs = Av x fy x d/s
s= NA in
Loading Data:
Parameters:
Concrete characteristic strength,fc' = 25 N/mm2 = 3625.95 psi
Beam Size:
Width =bw= 300 mm = 11.8 in
Depth = D = 600 mm = 23.6 in
Clear cover = 35 mm = 1.4 in
Column Size:
Width= 450 mm = 17.7 in
Depth= 450 mm = 17.7 in
Calculation:
bf = 1006 mm = 39.62 in
Where, β1 = 0.85
M u ≤ φ Mn
Where, φ = 0.9
Mn = As x fy x(d- a/2)
Minimum Reinforcement:
Shear Design:
Where, φ= 0.75
Vn = Vc + Vs
Vu = 39.12 kips
>Vu,Sectional dimension is ok
Shear Reinforcement:
φVs ≥ Vu - φVc
Where, Vs = Av x fy x d/s
s= 14.738 in