GT3000 LARGE Stand Alone Braking Unit Manual
GT3000 LARGE Stand Alone Braking Unit Manual
answerdrives.com
GT3000-LARGE
Code: IMGT30015EN/IT
Revision: 0.1
Date: Dec-07
Answer Drives S.r.l. thanks you for choosing a product of the GT3000 family and for any useful advice aimed at the improvement of this manual.
SUMMARY
Summary i
Preface iii
Safety standard iv
1: Introduction 1
2: Identification code 3
3: Technical data 3
8 Connections 12
9 Dimensions 13
BUA1 GT3000-LARGE
ii IMGT30015EN/IT
PREFACE
This manual provides detailed information and safety standards on the installation, startup, use and maintenance of the autonomous braking
unit.
This manual has been drawn for specialized operators involved in the installation, assembly, commissioning and maintenance operations,
and uses three different kinds of safety labels along with their identifying symbols to indicate information that requires special attention:
CAUTION ! Indicates a wrong action that could lead to hazardous situations for the operators. Moreover, it warns
the personnel of possible hazards that may occur during maintenance operations.
Hazardous voltage Signals the presence of high voltages with following hazard of death or electric
shock for the operators.
Indicates situations that may jeopardize the safety of persons and/or damage the equipment.
Shows a procedure that should be followed or avoided in order to carry out correct installation, repair or
WARNING replacement operations without damaging the inverter.
IMGT30015EN/IT iii
BUA1 GT3000-LARGE
SAFETY STANDARDS
This section contains information related to safety necessary and useful for the personnel working with the unit. The information is general and
concerns the risks both for the operators and the maintenance related to the operation and the maintenance of the braking unit. The
inobservance of these standards may jeopardize the safety of persons with hazard of death or damage to the inverter, the motor or the
operating machine.
Before operating with the unit, read the safety instructions both of the braking unit and of the inverter.
All electrical maintenance and installation procedures on the unit must be performed by qualified
technicians.
All standard electric safety procedures must be observed:
CAUTION! - Never touch anything within the unit until having verified that it is neither thermally hot nor live.
- Always wear insulated or rubber safety shoes and wear safety glasses.
- Never work alone.
- Never connect any grounded meters or oscilloscopes.
- Never remove safety shields.
- Always pay utmost care when handling components or taking measurements inside the panel.
• DANGER!
- The braking unit and all other devices connected MUST BE PROPERLY GROUNDED.
- Do not remove the resistor connected between the terminal 5 of M1 and ground (see cap.2.3)
- The voltages on the unit output terminals are hazardous both when the inverter is enabled, and when it is not working.
- If the unit is installed in the panel, do not let it work with electric cabinet doors open.
• DANGER! RISK OF FIRE, SERIOUS DAMAGE!
- Do not apply power to the inverter and/or to the unit, if any moisture, dust or caustic/corrosive chemicals agents may have
entered the cabinet or internal components.
• DANGER! RISK OF FIRE, SERIOUS DAMAGE OR INJURIES!
-The braking unit is an open type device and must be installed strictly as instructed in this MANUAL and in full compliance with
existing standards and regulations.
- Never store any flammable material in, on, or close to the unit.
• DANGER! RISK OF DEATH OR ELECTRICAL SHOCK!
The following safety steps must be strictly adhered to before servicing the unit:
- Perform power supply lock/disconnection procedure and open the main knife switch of the
cabinet.
DANGER - Make sure that all power supplies coming into the unit (main supply and auxiliary supplies)
are disconnected before servicing the unit.
- Before servicing the unit, wait at least ten (10) minutes after having disconnected power
supply. Before accessing the terminals make sure that the capacitors of the DC bus of
GT3000 are unloaded: Use a multimeter rated for 1000Vdc or higher to verify that the DC
voltage is lower than 40V. Refer to the safety shield borne by all inverters and braking units.
- The braking switch output terminals present hazardous dc voltages (higher than 500V)
- Do not modify the insulation distances or remove insulating materials and coverings.
- If insulation tests on the motor or on the cables must be performed, disconnect the cables
from the inverter and braking units first. High-potential tests must not be performed on
GT3000 components.
- Protect the inverter against bad weather and adverse environmental conditions (temperature,
humidity, vibrations, collisions, etc). Should the unit be temporarily stored outdoors, special
precautions must be taken (See GT3000 Manual).
The braking unit contains components sensitive to electrostatic charges; such components may be
CAUTION damaged, if improperly handled. During maintenance or replacement operations of the electronic
boards, the following steps must be adhered to:
Use a maintenance kit for electrostatic charges. Proper Electrostatic Discharge (ESD) precautions
must be taken:
Wear properly grounded static straps.
Handle the boards by handling them by their edges.
Boards must not get in contact with highly insulating materials, such as plastic sheets, insulating
surfaces, parts of synthetic fabrics.
Boards must be placed only on conductive surfaces.
Boards must be packaged in conductive sheets before shipping.
iv IMGT30015EN/IT
1 INTRODUCTION
Electric motors have the capability of regenerating mechanical power from the shaft to electric power available at motor terminals. In such
mode of operation the electric motor applies a braking torque to the driven machine. The inverter can transfer power from motor terminals to
the D.C. bus.
Depending how the power is removed from the D.C. bus, two different types of braking may be obtained:
- Recovery braking. It means that the braking power is sent back to the supply network, it requires another inverter1 (instead of the
diode rectifier) to transfer power from the D.C. bus to the supply network
- Dynamic braking. It means that the braking power is dissipated by a suitable braking resistor, it is implemented by braking
Choppers ("BU") and braking resistors.
When the speed (frequency) of an asynchronous motor is reduced rapidly, the motor works as an asynchronous generator supplying the
inverter again. Part of the energy is dissipated within the motor (with torque corresponding to about 10-20% of the rated motor torque), the rest
of the energy is accumulated on capacitors of the inverter intermediate circuit with the voltage increase at their ends. To avoid reaching too high
voltage values with consequent tripping of the inverter maximum voltage protection, the dynamic braking unit is used.
An electronic circuit detects the voltage on the inverter’s capacitor assembly and when its voltage exceeds to preset value, the power transistor
of the braking unit is enabled, which enables the braking resistor parallel to the capacitor bank.
As soon as the DC voltage returns to normal values, the power transistor is disabled.
The "BU" is controlled in such a way as to keep a constant average UDC voltage on its D.C. bus.
The minimum UDC voltage threshold level, corresponding to chopper turn-off, must be selected so to maintain all the diodes of the rectifier in
the off-state by a reverse voltage, while braking. The turn-on threshold level should be lower than DC voltage protection intervention.
In addition, turn-on and turn-off threshold levels, compared with the expected line voltage variations, must be high enough to prevent unwanted
braking Chopper turn-on in normal motoring conditions. threshold.
Power and current flow during braking may be represented as shown in the following figures.
+Vdc bus Id
PF
IR
Ic UDCif
Supply
=
line
-Vdc bus
IR = Id + Ic
Id
+Vdc bus
PF
Ic
UDCef
=
Supply
line
-Vdc bus
Ic = Id
PF = power regenerated by the motor during braking;
Id = D.C. current obtained from conversion of motor recovered power during braking;
Ic = capacitor bank current;
IR = braking resistor current;
UDCif = D.C. bus voltage value resulting in chopper turn-on;
UDCef = D.C. bus voltage value resulting in chopper turn-off.
IMGT30015EN/IT 1
GT3000-LARGE BUA1
For each D.C bus, the time behaviour of D.C. bus currents and voltages are shown in the following diagrams:
UDC
U D C if
U DCmf
U D C ef
tim e
t off t on t off t on t off t on
Id
I dm
tim e
IC
I dm
tim e
IR
I dm
tim e
The level UDCmf, corresponds to the average voltage value controlled by the “BU” during braking;
The values of UDCmf and Id are calculated with the following formulae:
UDCif + UDCef 1130 + 1145 UDCmf t on
UDCmf = = = 1138 V Id = ∗
2 2 RF t on + t off
2 IMGT30015EN/IT
BUA1 GT3000-LARGE
2 IDENTIFICATION CODE
The braking unit is identifiede by the following code:
1,2 3 4 5,6,7 8 9
BU A 1 1K3 K N
Product series
Cooling A = Air
W = Water
Generation
Rated Data See table 3.1
3 TECHNICAL DATA
Table 3.1
Inverter type Braking Unit SAP Braking Voltage Minimum resistor value Cont. Power Switch
code V ( *Rb) Ohm KW
GTA1700K - GTA11K1K BUA1700K 1138 1 509/763
GTA11K1K - GTA11K3K BUA11K1K 1138 0,8 633/927
GTA11K3K - GTA11K7K BUA11K3K 1000084792 1138 0,6 802/1141
BUA1700K
Braking cycle with P f KW 1149 655 633 605 582 542 520 509
minimum resistance Id A 1017 580 560 535 515 480 460 450
Rmin = 1Ω duty cycle s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
Braking cycle P f KW 1149 1074 1034 972 927 836 791 763
with optimized R Ω 1 1,08 1,12 1,19 1,25 1,38 1,46 1,52
resistance value Id A 1017 950 915 860 820 740 700 675
R_f(Ω) duty cycle s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
BUA11K1K
Braking cycle with P f KW 1464 848 808 763 729 672 644 633
minimum resistance Id A 1296 750 715 675 645 595 570 560
Rmin = 0,8Ω duty cycle 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
Braking cycle P f KW 1464 1367 1311 1215 1147 1028 961 927
with optimized R Ω 0,8 0,85 0,88 0,95 1 1,13 1,2 1,25
resistance value Id A 1296 1210 1160 1075 1015 910 850 820
R_f(Ω) duty cycle s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
BUA11K3K
Braking cycle with P f KW 1983 1130 1074 994 949 848 825 802
minimum resistance Id A 1755 1000 950 880 840 750 730 710
Rmin = 0,6Ω duty cycle s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
Braking cycle P f KW 1983 1842 1740 1582 1469 1288 1192 1141
with optimized R Ω 0,6 0,63 0,67 0,73 0,79 0,9 0,97 1
resistance value Id A 1755 1630 1540 1400 1300 1140 1055 1010
R_f(Ω) duty cycle s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
Ipk = Id-2/120s / 0,9
• The braking unit is supplied without the braking resistor.
• The braking resistor can be selected by using the formulas in sub-paragraph 5.
• The maximum braking power is available with a resistor value calculated according the braking time.
IMGT300015EN/IT 3
GT3000-LARGE BUA1
4 IMGT30015EN/IT
BUA1 GT3000-LARGE
PR
PL = 0 Pm
UDC
=
Supply line
PF = Pm * ηmot * ηinv
- Vdc bus PR = PF
Proper selection of “BU” power module and braking resistor rating is based on braking duty cycle (Braking power value and load duty times)
The four typical braking cycle are:
(this duty cycle is applicable in the case of constant braking torque applied tF
to a load consisting of mere inertia) T
- emergency braking: in this case, for a mere inertia load, the power maintains a rectangular wave-shape, but the duty cycle is not repetitive.
IMGT300015EN/IT 5
GT3000-LARGE BUA1
taking into account that RFmax cannot be exceeded, even at maximum operating temperature of the resistor.
UDCmf
Finally, the maximum current value of the “BU” power module is calculated, by means of the formula: I =
d
[A ] and the “BU” module
RF
shall be selected so that its continuous D.C. rated current shall be greater than or equal to Id.
Finally, the braking resistor data to be provided to the resistor manufacturer are: R = RF, P = PF, Ud = UDCmf
Also in this case the values of RFMAX and IDC must be calculated as shown in
the above paragraph 5.1; the “BU” module shall be selected so that its PF
continuous D.C. rated current shall be greater than or equal to IDC
tF
T
6 IMGT30015EN/IT
BUA1 GT3000-LARGE
This resistance value, RFmax, is the maximum allowable value for proper braking 2
UDCmf
operation, as it must be: PF < PR =
F RF
The above formula suggests that the selected value RF of the braking resistor must be lower than RFmax as calculated above.
The braking resistance value RF must be higher than the minimum allowed value. R min < R F < R Fmax
The braking energy to be dissipated in such braking resistor may be calculated as: 1 2 πN1
2
EF = ∗J ∗ [Joule]
2 tot 60
In the case of emergency braking, it should be checked whether the required motor stop time, ∆tF, can really be met. This entails that it must
be checked whether the expected braking torque CF can be delivered by the motor.
The rated torque of the motor is: Pnom
C nom = [N ∗ m]
ω nom
where: Pnom = rated power of the motor [W]
ωnom = rated speed of the motor [rad/s].
To comply with the given motor and inverter limits, the following condition must be C F < C nom
satisfied:
Should the braking torque CF be higher than the maximum available torque, the ω max
stop time shall be longer than the value used in previous calculations. In such ∆t Fmin = J tot ∗
case the calculation procedure must therefore be repeated with a longer time that C nom
can be evaluated by the following formula:
IMGT300015EN/IT 7
GT3000-LARGE BUA1
protection tripping) M1 - 8 M1 - 8
M1 - 9
Input to restore braking unit control board protections
M1 10-11 This is the reset command in the case of external protection or gate unit
shutdown command. N.O. contact (closed =
The reset command must be given by the Drive Control reset command. (Or by protection reset)
a programmable digital output of the logic I/O expansion board, according to the
M1 - 10
following logic:
Note: The tripping due to thermal protection of the braking resistor requires an
internal reset performed using the push-button PS3 of XCHRFC. M1 - 11
8 IMGT30015EN/IT
BUA1 GT3000-LARGE
DL3 XCHFRC
JP1 DL4
R11
R4 R40 R41
IC12 EEPROM
DL2
JP4
PS3
RZ
DL1
P1 P2 P3 P4 P5 P6 P7
JP2 JP3
3 2 1 2 1
K1
PS1 PS2
M2
1 2 3 1 2 3 4 5 6 7 8 9
M1
10 11 12 13 14 15 16 17 18
Layout XCHFRB control board
DL1: green led, when ON it indicates that no protection is active.
DL2: green led, when ON it indicates that ±24 V power supply is available.
PS1: Reset all board protections (e.g. IGBT desaturation protection).
JP1: Jumper: selection between 1 or 2 braking power module.
JP2: Jumper: selection of input signal (differential input amplifier or TV Lem.
JP3: Jumper:connection of terminal 5 to P.
RZ : Load resistor, its value is related to inverter current size.
M1 : Terminal for input and output signals
The board samples the IGBT command of the braking module. The two trimmers P2 and P3 allow to set the parameters necessary to the
microprocessor to process the thermal image of the braking resistor. The software recreates the thermal curve of the braking resistor and emits
a block signal in case of excessive temperature and requires the input of 2 parameters:
Pr.0 = time constant of the resistor Parameter settable within a range of 0 – 251 [sec] acting on trimmer P2.
Pr.1 = (Pf /Pnr ) x 10 Parameter settable within a range of 0 – 251 [p.u.] acting on trimmer P3.
Dove:
Pf = braking power = (Braking voltage)2 /Braking resistance
Pnr =braking resistor rated power.
Example:
Resistor time constant Tau = 240 s
Braking voltage Vf = 2080 V
Braking resistor Rf = 3 ohm
Resistor rated power PnR = 80kW
2
V 2
f 2080
R
Pr.0 = 240 Pr .1= 10 × f
= 10 × 3 = 180
P 80000
nR
The display of parameters occurs through the display with 7 segments and the push-button PS2, while the calibration occurs by means of the
trimmers and of the push-button PS2, the storage occurs using push-button PS3.
The display of the parameters occurs as follows: by pressing the push-button PS2 the following parameters are scrolled sequentially. When the
point is displayed at 7 segments it does not indicates a decimal position but the assignment to a given parameter as indicated in the following
table.
IMGT300015EN/IT 9
GT3000-LARGE BUA1
By pressing the push-button PS2, the parameters from Pr.0 to Pr.7 are scrolled sequentially.
To input the parameters proceed as follows:
Using the push-button PS2 scroll all displayable parameters and position on the wished one (Pr.0 or Pr.1).
Rotate the related trimmer until the wished value is displayed.
Press the push-button PS3 to pass the new values to the microprocessor.
The occurred acquisition of the parameters can be verified by displaying the parameters Pr.2 and Pr.3 indicating respectively the resistor time
constant and the normalized braking power used by the microprocessor.
To set the value of Tau, it is necessary to access parameter Pr.0 (always using push-button PS2) and rotate the trimmer P2 until the display
indicates the previously calculated value; if for example this value is 245, the display shows 245.
At this point, it is necessary to store the value by pressing the microprocessor PS3 reset key, so that the set value is acquired; on the contrary,
by pressing push-button PS2 and accessing parameter Pr.2 (Tau acquired), the value would differ from the set one and consequently the
calculated thermal curve would not correspond to the wished one.
At display enabling, it shows Pr.0. If for example current Tau value was 230, one would read 230. To read the acquired Tau value, it is
necessary to press the push-button PS2 twice and the reading is: 23.0.
To set the current Pn1 value, access parameter Pr.1 as given in table and act on the trimmer P3 until the display shows the previously
calculated value, if for example this was 124, the display shows 124.
At this point, it is necessary to store the value by pressing the microprocessor PS3 reset key.
Now, by pressing once again this push-button PS2 to display the acquired Pn1 value (Pr.3), the display shows the value 12.4..
Once these parameters have been input and stored, it is possible to display the thermal protection tripping value calculated by the
microprocessor (Pr.4) that if it was for example 210, it is showed on the display (after having selected the parameter by PS2) as 2.10.
During operation it is possible to see the value reached by the resistor thermal curve: press the push-button PS2 and access parameter Pr.5, if
the added value was for example 104 this would be shown on the display as: 1.04. .
Example of calculation of the parameters to be input:
Braking resistor data: Braking module tripping and disabling data as per manual (GT3000-LARGE, Vinp: 525-690)
Ohmic value 2 ohm VDCif 1145V (braking tripping)
Braking power 700Kw VDCef 1130V (braking exclusion)
Tau time constant 500 sec. VDCmf 1138V (average braking)
10 IMGT30015EN/IT
BUA1 GT3000-LARGE
WARNING THE BUA1 BRAKING UNIT DOESN'T HAVE THE INTERNAL PRECHARGE.
IMGT300015EN/IT 11
8
12
+ +/RE+
Fu Rb
TH
RE -
GT3000-LARGE
CONNECTIONS
Fu
- -
GROUND BAR
BRAKING-UNIT CAPACITY
BUA1700K 2700 microF 1300 m3 / h
230V 0,7A BUA11K1K 3600 microF
50/60Hz BUA11K3K 4500 microF
BLACK
WHITE
N
230V-50 / 60Hz BLACK
1,45A L
IMGT30015EN/IT
BUA1
BUA1 GT3000-LARGE
9 DIMENSIONS
380 750
1104.5
1337
A A
475
232.5
420 150
11
25
413.75
330
171.5
25
SEZIONE A-A
164.75
IMGT300015EN/IT 13
GT3000-LARGE BUA1
40 43
B B
202
M10
-
40
123.5
+ /RE+
40
113.5
RE-
40
395
SEZIONE B-B
14 IMGT30015EN/IT
BUA1 GT3000-LARGE
5
1
1
1
4
4
2
2
2312
3 SID 0
2 E1 120
T
00
0 ON
FR
IMGT300015EN/IT 15
GT3000-LARGE BUA1
16 IMGT30015EN/IT
GT3000-LARGE
Codice: IMGT30015EN/IT
Revisione: 0.1
Data: Dic-07
Answer Drives S.r.l. vi ringrazia per aver scelto un prodotto della famiglia GT3000 e per eventuali segnalazioni utili a migliorare questo manuale.
INDICE
Indice i
Prefazione iii
Norme di sicurezza iv
1: Introduzione 1
2: Codice di Identificazione 3
3: Dati tecnici 3
8 Collegamenti 12
9 Dimensioni 13
IMGT30015EN/IT i
BUA1 GT3000-LARGE
ii IMGT30015EN/IT
Prefazione
Questo manuale fornisce informazioni dettagliate e le norme di sicurezza in merito all’installazione ed alla messa in servizio, all’uso ed alla
manutenzione dell’unita’ freno autonoma.
Il manuale è stato redatto per operatori specializzati coinvolti nell’installazione, montaggio, messa in funzione e manutenzione, ed adotta tre
differenti tipologie di sicurezza corredate dai loro simboli di identificazione per indicare informazioni che richiedono una attenzione speciale:
Indica un’azione scorretta che potrebbe determinare situazioni pericolose per gli operatori. Inoltre,
ATTENZIONE ! avvisa il personale di possibili pericoli che potrebbero verificarsi durante le operazioni di manutenzione.
Tensione pericolosa Segnala la presenza di alte tensioni con il conseguente rischio di morte o shock
elettrico per gli operatori.
Indica le situazioni che potrebbero metter a rischio l’incolumita delle persone e/o danneggiare le
apparecchiature.
Indica una procedura che dovrebbe essere seguita o evitata per eseguire in modo corretto le operazioni
AVVERTENZA di installazione, riparazione o sostituzione senza danneggiare l’inverter.
Indica operazioni nell’ambito delle quali devono essere evitate le scariche elettrostatiche.
IMGT30015EN/IT iii
BUA1 GT3000-LARGE
NORME DI SICUREZZA
Questa sezione contiene informazioni riguardanti la sicurezza, necessarie ed utili per il personale che opera con l’unità. Le informazioni sono
generali e riguardano i rischi, sia per gli operatori che per il personale di manutenzione, relativi al funzionamento e alla manutenzione dell’unita’
freno. Il mancato rispetto di tali norme puo’ mettere a repentaglio l’incolumita’ delle persone con rischio di morte e danneggiare l’unità
frenatura, l’inverter, il motore o la macchina operatrice.
Prima di operare con l’unita’ leggere le istruzioni di sicurezza relative sia all’unita’ freno che all’inverter.
Tutte le operazioni di manutenzione elettrica ed installazione sull’unita’ devono essere eseguite da tecnici
qualificati.
Tutte le procedure standard di sicurezza elettrica devono essere rispettate:
ATTENZIONE! -Non toccare mai nulla all'interno dell'unita’, se non dopo essersi assicurati che non sia a temperatura
elevata e/o in tensione.
-Indossare sempre calzature antinfortunistiche isolate o in gomma e occhiali protettivi.
-Non lavorare mai da soli.
-Non collegare mai al sistema dispositivi di misura od oscilloscopi messi a terra.
-Non rimuovere mai gli schermi di sicurezza.
-Fare sempre estrema attenzione quando si maneggiano dei componenti o si eseguono misure all'interno
del quadro.
• PERICOLO! -L’unita’ freno e tutti gli altri dispositivi collegati DEVONO ESSERE MESSI A TERRA IN MODO ADEGUATO.
-Non rimuovere la resistenza connessa tra il morsetto 5 di M1 e terra (vedi cap.2.3)
-Le tensioni sui morsetti di uscita dell’unita’ sono pericolose sia quando l'inverter è attivato, sia quando lo stesso
non è in funzione.
-Se l'unità è installata in quadro, non farla mai funzionare con le porte del quadro aperte.
• PERICOLO! RISCHIO DI INCENDIO, GRAVE DANNO!
-Non applicare potenza all'inverter e/o all’unità se si presume che all'interno del contenitore o dei componenti sia
penetrata umidità, polvere od agenti chimici caustici/corrosivi.
• PERICOLO! RISCHIO DI INCENDIO, GRAVE DANNO O FERITE!
L’unita freno é un dispositivo di tipo aperto e deve essere installata rigidamente secondo le istruzioni del presente
MANUALE ed in totale conformità con le norme e regole esistenti.
-Non immagazzinare mai materiale infiammabile dentro, sopra o vicino all’unita’.
iv IMGT30015EN/IT
1 INTRODUZIONE
Il motore elettrico puo' funzionare anche come generatore trasformando l'energia meccanica all'albero in energia elettrica ai morsetti; durante
questo funzionamento il motore elettrico si comporta come un freno rispetto alla macchina operatrice accoppiata.
Con riferimento al modo in cui la potenza viene trasferita dal bus DC alla linea di alimentazione si distinguono:
Frenatura a recupero. Prevede l'immissione dell'energia elettrica prodotta dalla frenatura sulla linea di alimentazione e richiede un
altro inverter 1 (in sostituzione del ponte a diodi ) per trasferire la potenza dal bus D.C. alla rete.
Frenatura dinamica. Prevede la dissipazione in calore, su un resistore opportuno, dell'energia elettrica prodotta dalla frenatura e
richiede un chopper ("BU") ed un resistore di frenatura.
Quando la velocita’ (frequenza) di un motore asincrono viene ridotta rapidamente, il motore lavora come un generatore asincrono alimentando
ancora l’inverter
L’energia prodotta viene dissipata in piccola parte nelle perdite del motore e dell'inverter (con una coppia corrispondente a circa il 10-20% della
coppia nominale del motore) ed in gran parte viene accumulata nei condensatori del banco filtri con conseguente aumento del valore di
tensione del bus DC. Per evitare di raggiungere valori di tensione troppo elevati con conseguente intervento della protezione di massima
tensione viene utilizzata l'unita' di frenatura.
Un circuito elettronico rileva la tensione del bus DC e quando questa supera un certo valore limite, onde evitare l'intervento della protezione di
massima tensione, il chopper provvede ad inserire in parallelo al bus DC una resistenza opportunamente dimensionata in cui viene dissipata
l'energia prodotta dal motore e parte dell'energia accumulata nei condensatori del banco filtri; l'intervento del chopper avrà quindi l'effetto di far
diminuire la tensione del bus DC. Una volta raggiunto un valore minimo della tensione del bus DC, il chopper disinserirà la resistenza.
Il chopper viene controllato in modo da mantenere costante il valore medio della tensione UDC sul bus DC.
Il valore minimo della soglia di tensione, in corrispondenza del quale si ha la disabilitazione del chopper, deve essere scelto in modo tale che il
i diodi del ponte di alimentazione, durante la frenatura, siano bloccati.
La soglia di intervento della BU deve essere inferiore alla soglia di intervento della protezione di massima tensione DC.
Le soglie di intervento e di disabilitazione della BU, comparate con le variazioni di tensione di rete accettate, devono essere sufficientemente
alte da prevenire l'inserzione indesiderata della BU in condizioni di funzionamento normale.
Il flusso delle potenze e delle correnti durante la frenatura è rappresentato, in funzione dello stato del chopper, nelle figure seguenti:
+Vdc bus Id
PF
IR
Ic UDCif
Rete
=
-Vdc bus
IR = Id + Ic
Id
+Vdc bus
PF
Ic
UDCef
=
Rete
Ic = Id
-Vdc bus
PF = Potenza generata
Id = Corrente continua
Ic = Corrente nel banco di condensatori
IR = Corrente nel resistore di frenatura
UDCif = Valore del bus DC a cui si ha l'intervento del chopper
UDCef = Valore del bus DC a cui si ha l'esclusione del chopper
1
tale sistema è conosciuto come "active front end"
IMGT30015EN/IT 1
GT3000-LARGE BUA1
Gli andamenti temporali delle correnti e della tensione sul bus DC sono i seguenti:
UDC
U D C if
U DCmf
U D C ef
tem po
t off t on t off t on t off t on
Id
I dm
tem po
IC
I dm
tem po
IR
I dm
tem po
La grandezza UDCmf rappresenta il valore medio di tensione controllato dal chopper in fase di frenatura.
I valori di UDCmf ed Id vengono calcolati mediante le seguenti relazioni:
UDCif + UDCef 1130 + 1145 UDCmf t on
UDCmf = = = 1138 V Id = ∗
2 2 RF t on + t off
2 IMGT30015EN/IT
BUA1 GT3000-LARGE
2 CODICE DI IDENTIFICAZIONE
L'unita' di frenatura è identificata dal codice commerciale seguente:
1,2 3 4 5,6,7 8 9
BU A 1 1K3 K N
Serie prodotto
Raffreddamento A = Aria
W = Acqua
Generazione
Dati nominali Vedere tabella 1.3
3 DATI TECNICI
Tabella 3-1
Tipo inverter Unita' di frenatura Codice SAP Valore minimo del resistore Tensione di frenatura Potenza continuativa
( *Rb) Ohm V KW
GTA1700K - GTA11K1K BUA1700K 1 1138 509/763
GTA11K1K - GTA11K3K BUA11K1K 0,8 1138 633/927
GTA11K3K - GTA11K7K BUA11K3K 1000084792 0,6 1138 802/1141
BUA1700K
Ciclo di frenatura P_f KW 1149 655 633 605 582 542 520 509
con resistenza Id A 1017 580 560 535 515 480 460 450
Rmin = 1Ω ciclo s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
Ciclo di frenatura P_f KW 1149 1074 1034 972 927 836 791 763
con resistenza R Ω 1 1,08 1,12 1,19 1,25 1,38 1,46 1,52
ottimizzata Id A 1017 950 915 860 820 740 700 675
R_f(Ω)
ciclo s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
BUA11K1K
Ciclo di frenatura P_f KW 1464 848 808 763 729 672 644 633
con resistenza Id A 1296 750 715 675 645 595 570 560
Rmin = 0,8Ω ciclo 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
Ciclo di frenatura P_f KW 1464 1367 1311 1215 1147 1028 961 927
con resistenza R Ω 0,8 0,85 0,88 0,95 1 1,13 1,2 1,25
ottimizzata Id A 1296 1210 1160 1075 1015 910 850 820
R_f(Ω)
ciclo s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
BUA11K3K
Ciclo di frenatura P_f KW 1983 1130 1074 994 949 848 825 802
con resistenza Id A 1755 1000 950 880 840 750 730 710
Rmin = 0,6Ω ciclo s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
Ciclo di frenatura P_f KW 1983 1842 1740 1582 1469 1288 1192 1141
con resistenza R Ω 0,6 0,63 0,67 0,73 0,79 0,9 0,97 1
ottimizzata Id A 1755 1630 1540 1400 1300 1140 1055 1010
R_f(Ω)
ciclo s 2/120 5/120 10/120 20/120 30/120 60/120 90/120 cont
Ipk = Id-2/120s / 0,9
• L’unità di frenatura viene fornita senza il resistore.
• Il resistore di frenatura può essere calcolato secondo le formule riportate nel paragrafo 5.
• La massima potenza di frenatura è disponibile con un resistore il cui valore ohmico è adeguato al tempo di frenatura richiesto.
IMGT30015EN/IT 3
GT3000-LARGE BUA1
FUNZIONAMENTO: Far funzionare in un luogo stabile e protetto dalle intemperie secondo IEC 721-3-3.
Da 0 a 40 °C. (Da 32 a 104 °F) – Se la temperatura ambiente supera i + 40°C (104 °F), ridurre la corrente
Temperatura ambiente
nominale d’uscita del 2,5% per ogni °C. (max. 55°C – max. 131°F ).
Umidità relativa Da 5 a 95% senza condensa
Livelli di (Schede senza rivestimento) – Gas chimici: IEC 721-3-3, Classe 3C2
contaminazione Parti solide: IEC 721-3-3, Classe 32C
Fino a 1000 m (3280 ft) sul livello del mare. Oltre i 1000 m (3280 ft) sul livello del mare, la corrente nominale
Altitudine d’uscita viene ridotta di 1% per ogni 100 m (328 ft) aggiuntivi.
Altezza massima 3000 m (9840 ft)
Vibrazioni Max. 0.3 mm (da 2 a 9 Hz), max. 1 m/s2 (da 9 a 200 Hz) sinusoidali (Classe 3 M1)
• Evitare l’esposizione a gas corrosivi, incluso l’idrogeno solforato
Considerazioni
ambientali • Evitare l’esposizione a campi magnetici forti, radiazioni nucleari e alti livelli di RFI da trasmettitori di
comunicazione
IMMAGAZZINAGGIO: Immagazzinare in un imballo protettivo e in ambiente protetto secondo IEC 721-3-1.
Temperatura ambiente Da -40°C a +70°C (Da -40°F a +158°F)
Umidità relativa Da 5 a 95%, senza condizioni di condensa o congelamento (classe 1K3)
Pressione atmosferica Da 70 a 106 kPa
Vibrazioni Max 1.5 mm (da 2 a 9 Hz), max. 5 m/s2 (da 9 a 200 Hz) sinusoidale (classe 1M3)
Shock Max. 100 m/s2, 11 ms (classe 1M3).
Livelli di Schede senza rivestimento – Gas chimici: CEI 721-3-3, classe 3C2
contaminazione Parti solide: CEI 721-3-3, classe 32C
• Evitare l’esposizione a gas corrosivi, incluso l’idrogeno solforato
Considerazioni
• Evitare l’esposizione a campi magnetici forti, radiazioni nucleari e alti livelli di RFI da trasmettitori di
ambientali
comunicazione
TRASPORTO: Trasportare l’inverter nel suo imballo protettivo secondo CEI 721.3.2.
Temperatura ambiente Da -25 a +70 °C. (Da -13°F a +158°F)
Umidità relativa Max. 95% a 40 °C. – Max. 95% a 104 °F.
Pressione atmosferica Da 60 a 106 kPa
Vibrazioni Max 3.5 mm (da 2 a 9 Hz), max. 10m/s2 (da 9 a 200 Hz) sinusoidali (classe 2M1).
Shock max 100 m/s2, 11 ms. (max. 328 m/s2, 11 ms.)
250 mm, 0,82 ft (peso inferiore a 100 kg)
Caduta libera
100 mm, 0,33 ft (peso superiore a 100 kg)
4 IMGT30015EN/IT
BUA1 GT3000-LARGE
PR
PL = 0 Pm
UDC
=
Rete
PF = Pm * ηmot * ηinv
- Vdc bus PR = PF
Per la scelta della taglia del chopper ed il dimensionamento del resistore di frenatura è necessario conoscere i dati del ciclo di frenatura
richiesto (valore della potenza di frenatura e tempi del ciclo di carico).
I quattro cicli di frenatura tipici sono:
Frenatura continuativa (PF = costante);
PF
Frenatura di emergenza: in tale caso, per un carico puramente inerziale, la potenza mantiene un forma rettangolare ma il ciclo non è ripetitivo
IMGT30015EN/IT 5
GT3000-LARGE BUA1
c) il ciclo di frenatura non coincide con uno dei cicli specificati ma T è minore di 120 sec;
in questo caso non si possono utilizzare direttamente i valori di corrente riportati nelle tabelle delle taglie, ma è necessario ricavare il
valore di Id tF/T da utilizzare calcolandolo in base ai valori riportati nelle tabelle a parità di duty-cycle.
Esempio:
t f = 3 s
Dati ciclo frenatura ; valore calcolato di corrente media nel chopper: Id =1000 A
T = 80 s
3 5
Poichè: = 0.0375 è circa uguale a: = 0.042
80 120
si utilizza come valore Id 3/80 il valore Id 5/120 e si sceglie: con resistenza standard la BUA11K3K con I d-5/120 =1000A > Id
con resistenza ottimizzata la BUA11K1K con I d-5/120 =1210A > Id
Per quanto riguarda il dimensionamento del resistore di frenatura, i dati da fornire al costruttore sono:
R = RF P = PF (con ciclo tF/T rettangolare) Ud = UDCmf
6 IMGT30015EN/IT
BUA1 GT3000-LARGE
La suddetta formula mostra che il valore scelto RF del resistore di frenatura deve essere inferiore a Rfmax calcolata in precedenza.
Il valore ohmico del resistore RF deve essere superiore al valore minimo ammesso R min < R F < R Fmax
dall’unita’ di frenatura, (vedere tabella 3.1)
L’energia di frenatura che deve essere dissipata nel resistore viene ricavata con la 1 2 πN1
2
IMGT30015EN/IT 7
GT3000-LARGE BUA1
M1 - 7
M1 - 8
8 IMGT30015EN/IT
BUA1 GT3000-LARGE
DL3 XCHFRC
JP1 DL4
R11
R4 R40 R41
IC12 EEPROM
DL2
JP4
PS3
RZ
DL1
P1 P2 P3 P4 P5 P6 P7
JP2 JP3
3 2 1 2 1
K1
PS1 PS2
1
M2
2 3 1 2 3 4 5 6 7 8 9
M1
10 11 12 13 14 15 16 17 18
Layout XCHFRB control board
Layout scheda controllo XCHFRB
DL1: verde, acceso indica l’assenza di protezione della scheda.
La scheda campiona il comando dell’IGBT del modulo di frenatura. I due trimmer P2 e P3 permettono di impostare i parametri necessari al
microprocessore per elaborare l’immagine termica del resistore di frenatura. Il software ricostruisce la curva termica del resistore di frenatura
ed emette un segnale di blocco in caso di sovra temperatura e richiede l’inserimento di 2 parametri :
Pr.0 = costante di tempo del resistore Parametro impostabile in un range di 0 – 251 [sec] agendo sul trimmer P2.
Pr.1 = (Pf /Pnr ) x 10 Parametro impostabile in un range di 0 – 251 [p.u.] agendo sul trimmer P3.
Dove:
Pf = potenza di frenatura = (Tensione di frenatura)2 /Resistenza di frenatura
Pnr =potenza nominale resistore di frenatura.
Esempio:
costante di tempo resistore Tau= 240S
tensione di frenatura Vf = 1138V
resistore di frenatura Rf = 3 Ω
potenza nominale resistore PnR = 80kW
V2 1 1138
2
1
Pr.0 = 240 Pr .1 = 10 × f = 10 × = 53,9
R P 3 8000
f NR
La visualizzazione dei parametri avviene tramite il display a 7 segmenti e il pulsante PS2, mentre la taratura tramite i trimmers e il pulsante
PS2, la memorizzazione resettando il microprocessore tramite il pulsante PS3.
La visualizzazione dei parametri avviene nel seguente modo : premendo il pulsante PS2 si scorrono in sequenza i seguenti parametri, dove il
puntino si display a 7 segmenti non indica un decimale ma l’assegnazione a un determinato parametro come indicato nella seguente tabella.
IMGT30015EN/IT 9
GT3000-LARGE BUA1
10 IMGT30015EN/IT
BUA1 GT3000-LARGE
IMGT30015EN/IT 11
8
12
+ +/RE+
Fu Rb
TH
RE -
GT3000-LARGE
COLLEGAMENTI
Fu
- -
BARRA DI TERRA
NERO
BIANCO
N
230V-50 / 60Hz NERO
1,45A L
IMGT30015EN/IT
BUA1
BUA1 GT3000-LARGE
9 DIMENSIONI
380 750
1104.5
1337
A A
475
232.5
420 150
11
25
413.75
330
171.5
25
SEZIONE A-A
164.75
IMGT30015EN/IT 13
GT3000-LARGE BUA1
40 43
B B
202
M10
-
40
123.5
+ /RE+
40
113.5
RE-
40
395
SEZIONE B-B
14 IMGT30015EN/IT
BUA1 GT3000-LARGE
5
1
1
1
4
4
2
2
2312
F IA 00
3
2 NC E 12
O T
10 ON
00 FR
IMGT30015EN/IT 15
GT3000-LARGE BUA1
16 IMGT30015EN/IT
Answer Drives S.r.l.
Head Office:
Viale Sarca, 336 – 20126 Milano - Italia
Operation Site:
S.S 11 Cà Sordis, 4 I-36054 Montebello
Vicentino (VI) - Italia
Ph. +39 0444 449268
Fax +39 0444 449276 1000086442
www. answerdrives.com