Professional Documents
Culture Documents
HVAC Fundamentals Solution
HVAC Fundamentals Solution
1. Draw the vapour-compression cycle. State the refrigerant flow direction and
energy flow at each of the components. What will you experience if the
refrigerant flow is reversed?
f e
a b
3 2
Pcond= 1.75 MPa, Tcond =
60°C
3 2
Pcond= 1.75 MPa, Tcond =
60°C
Deg of superheat
= 15 °C
The new enthalpy at the compressor inlet is: h 1 = 270 kJ/kg. Therefore,
the new cooling capacity and compressor work are:
𝑄𝑒𝑣𝑎𝑝 126
𝐶𝑂𝑃 = = = 2.62
𝑊𝑖𝑛,𝑐𝑜𝑚𝑝 (38.5/0.8)
𝑄𝑒𝑣𝑎𝑝 122.5
𝐶𝑂𝑃 = = = 3.11
𝑊𝑖𝑛,𝑐𝑜𝑚𝑝 (31.5/0.8)
𝑄𝑒𝑣𝑎𝑝 126
𝐶𝑂𝑃 = = = 3.6
𝑊𝑖𝑛,𝑐𝑜𝑚𝑝 (28/0.8)
Direct Expansion
System
Air-cooled Water-cooled
c. At 50% part load condition, if the chiller efficiency is 0.74 kW/RT, what
is the chiller input power?
Answer:
1530 𝑘𝑊
𝐶𝑂𝑃 = = 𝟔. 𝟑𝟕𝟓
240 𝑘𝑊
240 𝑘𝑊
𝐶ℎ𝑖𝑙𝑙𝑒𝑟 𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = = 𝟎. 𝟓𝟓 𝒌𝑾/𝑹𝒕𝒐𝒏
435 𝑅𝑡𝑜𝑛
Additional information:
• The designed delta T (ΔT) is 5.5 °C for both evaporator and condenser.
• The designed flow rate for chilled water and condenser water is 45.8
l/s and 52.7 l/s respectively.
• The compressor efficiency is 90%
• Cooling towers, chilled and condenser water pump power: 18 kW, 16
kW & 18 kW respectively.
Answer:
𝑘𝑊 𝑃𝑜𝑤𝑒𝑟 𝑖𝑛𝑝𝑢𝑡(𝑘𝑊)
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 (𝑇𝑜𝑛) = 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑(𝑇𝑜𝑛)
170+18+16+18
= 196
= 1.13𝑘𝑊/𝑅𝑇
𝑘𝑊 𝑃𝑜𝑤𝑒𝑟 𝑖𝑛𝑝𝑢𝑡(𝑘𝑊)
f. 𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 (𝑇𝑜𝑛) = 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑(𝑇𝑜𝑛)
159+18+16+18
= 300
= 0.70 𝑘𝑊/𝑅𝑇
h. The part load efficiency is very poor as can be seen from the above
calculation. The main reason is due to the constant flow rate even with
a varying load. This will result in low delta T which deviates from the
designed delta T. One solution to solve this problem is to install VSD
to reduce the flow rate for both chilled water and condenser water
loop. This will also reduce energy consumption at the pumps.
a) From the above parameters, calculate the cooling load (in kW) that the
chiller is delivering
b) Calculate the cooling load (in RT)
c) If the full-load cooling capacity of the chiller is 120 Ton, what part-load
percentage is the chiller operating at?
d) Calculate the input power (in kW) to the chiller (Assume a power factor of
0.92)
e) Calculate the chiller efficiency (in kW/RT).
f) Calculate the expected condenser water flow rate. (Given that the
compressor efficiency is 90%)
Answer:
a) From the chilled-water parameters, calculate the cooling load (in kW) that the
chiller is delivering.
Qevap = m x c w x delta T
= 16.6 x 4.19 x (12.5 – 7.1)
= 376 kW
f) Calculate the expected condenser water flow rate. (Given that the heat balance
is 0%)
Qcond = m x c w x delta T
m = 439.7/(4.19 x (33.2-28.6))
= 22.8 kg/s = 22.8 l/s
Answer:
For pressure dependent VAV box control, the room temperature controls the
VAV damper position directly, whereas for pressure independent VAV box
control, the room temperature adjust the air flow set point first, and the air
flow sensor control the VAV damper position.
2. Given that the room is cooled by cold air distributed into the room through a
Pressure Independent VAV box, describe the course of event when a cabinet
is placed in front of the thermostat.
Course of event:
• When the cabinet is placed in front of the thermostat, the temperature
sensor reading will increase and will be higher than the true space
temperature.
• Thus, the air flow set point will increase accordingly.
• This will cause the VAV damper to throttle open to allow more cold air to
enter the room.
• Static pressure reading in the supply air duct will start to decrease with the
opening of VAV damper.
• VSD installed at the SA fan will respond by increasing the fan speed.
Consequences:
• Room will be overcooled.
• Energy consumption at the AHU will increase.
True value
= 27.85°C
Course of event:
• If the wet bulb temperature sensor is faulty and gives a lower value, it will cause
the approach temperature to be higher than its true value.
• Since the set point is 1 °C, the VSD installed at the cooling tower fans will
respond by increasing its fan speed.
• If the set point cannot be achieved, the cooling tower fans will operate at
maximum speed continuously.
Consequences:
• There will be energy wastage at the cooling tower fans.
Chiller 1 – 500 RT
Chiller 2 – 500 RT
Chiller 3 – 300 RT
Chiller 4 – 300 RT
Given that the chiller sequence is 2341 2143, describe the chiller staging
with reference to the load profile shown below.
1000
Cooling load (Rton)
800
600
400
200
0 4 8 12 16 20 24
Time of day (hrs)
At 4.30pm, Chiller 4 will stop as the load is below 800RT (1000RT x 80%)
At 9pm, Chiller 1 will stop as the load is below 400RT (500 x 80%)
At 11pm, Chiller 2 will stop by time schedule.
Configuration 1
3 x 800 RT + 2 x 350 RT chiller (Capital cost: $2,600,000)
Configuration 2
6 x 500 RT chiller (Capital cost: $3,200,000)
2000
1600
Cooling load (Rton)
1200
% load 100 80 60 40 20
800 Chiller A (800 Rton) 0.54 0.48 0.51 0.66 0.8
Chiller B (500 Rton) 0.51 0.49 0.54 0.63 0.77
400
Chiller C (350 Rton) 0.55 0.57 0.59 0.63 0.71
0 4 8 12 16 20 24
Time of day (hrs)
Configuration 2:
b. What is the weekly energy consumption for both chillers, given that the
office building requires 300 RT of cooling for the whole of Saturday and
Sunday?
Configuration 1:
Configuration 2:
Pumps:
5. Reduce flow losses
6. Avoid over sizing pump
7. Avoid oversizing motor
8. Use high efficiency pump
9. Use high efficiency motor
10. Use VSD to reduce flow