Professional Documents
Culture Documents
Modeling Heat Recovery Plants in Hourly Analysis Program (HAP) v4.90 by Carrier
Modeling Heat Recovery Plants in Hourly Analysis Program (HAP) v4.90 by Carrier
Great progress has been made increasing building energy efficiency over the Page 6
past four decades by improving the efficiency of individual building components. Frequently Asked
Among these components are wall, roof and window assemblies, lighting, and Questions
heating, ventilation and air-conditioning (HVAC) equipment such as chillers,
DX equipment, pumps and fans. But after 40 years of steady improvement, Page 8
the industry is nearing the physical and economic limits for further component 2015 Training Class
efficiency improvements. To advance building energy efficiency to even higher Schedule
levels, engineers and owners are changing their focus from maximizing
component efficiency, to maximizing system efficiency.
(Continued on page 2)
Modeling Heat Recovery Plants in Hourly Analysis Program
(HAP) v4.90 by Carrier
In buildings using hydronic cooling and heating, produces chilled water to serve cooling loads.
one attractive system efficiency strategy is the heat Cooling-only chillers serve any remaining
recovery plant. In a heat recovery plant, part or cooling load. Figure 1, on next page, is a
all of the chiller heat rejection that would normally simplified diagram of this particular heat
occur via a cooling tower or an air-cooled condenser recovery configuration.
is captured and used for service hot water (SHW)
2. Air Cooled Chiller with Heat Recovery
and/or space heating duty. This can reduce or even
Condenser - One or more air-cooled chillers
eliminate energy use by water heaters and hot water
are equipped with dual condensers:
boilers.
(1) a refrigerant-to-water condenser to recover
Determining whether your building project is a good heat to serve building heating demands, and
candidate for heat recovery can be a challenging (2) a refrigerant-to-air condenser to reject
task. Suitability depends on the building load profile heat to the atmosphere when heat output
and how frequently simultaneous demands for cooling exceeds heating demand or heating demand
and heating exist, as well as equipment full-load does not exist.
and part-load efficiencies. Often the energy use of
3. Heat Exchanger in Condenser Loop - A
one system component will increase while others
plate frame heat exchanger is placed between
decrease. The net savings is a matter of whether
the condenser water loop and hot water loop.
energy efficiency gains offset losses elsewhere in the
Chillers are run at elevated condenser water
system. Further, heat recovery plants often require
temperatures in order to allow heat transfer
additional components and controls, thus increasing
from the condenser loop to the hot water loop
first cost so viability is dependent on rapid payback
via the heat exchanger.
through energy cost savings.
4. Dedicated Heat Recovery Chiller in the
Given this situation, energy modeling is an important
Condenser Loop - A water-to-water heat
tool to help engineers evaluate the economic
pump chiller is placed between the condenser
feasibility of heat recovery plant applications. HAP
water loop and the hot water loop. The heat
v4.90, released by Carrier in December 2014,
pump chiller operates in heating priority,
provides extensive new features to help you quickly
extracting heat from the condenser loop to
and effectively carry out this evaluation. HAP provides
heat water in the hot water loop.
modeling features for six of the common heat
recovery strategies employed today, and options 5. Chiller with Double Bundle Condenser - One
for modeling multiple variations of each. This not or more water-cooled chillers are equipped with
only allows study and optimization of an individual a double-bundle condenser, allowing the chiller
strategy, but also comparison of performance to reject heat to the hot water loop when
between different heat recovery strategies. heating demands exist, or to the condenser loop
when heating demands do not exist.
1. Dedicated Heat Recovery Chiller in
Parallel with Cooling-Only Chillers - A 6. Chiller with Desuperheater - One or more
water-to-water heat pump chiller is placed in chillers are equipped with a desuperheater - a
parallel with cooling-only chillers. The heat heat exchanger at the compressor outlet that
pump chiller operates in heating priority to recovers high temperature sensible superheat
serve hot water demands. It simultaneously from the discharge refrigerant gas to heat water.
2
CARRIER® eDESIGN SUITE NEWS
What is Infiltration?
Infiltration is the uncontrolled inward leakage of
outdoor air directly into the conditioned space.
It can result from leakage around windows and
Figure 1: Simplified Diagram of a Dedicated Heat doors resulting from wind and air pressure effects.
Recovery Chiller in Parallel with Cooling-Only Chillers Infiltration can also be the result of other factors
Heat Recovery Plant such as the frequent opening and closing of
entryway doors in the building.
The chiller’s condenser then rejects the latent heat of Difficult to Predict
condensation to the atmosphere by conventional means. While it may seem reasonable to include the
effects of infiltration in the building design, arriving
In addition to these new modeling features, Carrier
at an order of magnitude is difficult. Infiltrating
also provides application articles called “eHelps” to help
air is dependent on many factors such as the air
engineers effectively use HAP to model heat recovery
tightness of the building envelope, overall quality
projects. One article is provided for each of the six heat
of workmanship, entryway design, building siting,
recovery strategies modeled in HAP.
prevailing winds, building height, and other physical
Each article contains: characteristics resulting from construction. Since
• A system diagram. each project is different, engineers have found that
• A brief explanation of basic of system predicting infiltration amounts and duration is not
configuration and operation. straightforward.
• A survey of system advantages and
In addition to the unpredictable nature of this
disadvantages and keys to successful application.
task, infiltrating air is at ambient conditions (hot in
• A step-by-step tutorial explaining how to use
summer, cold in winter), has both a sensible and a
HAP to model the system.
latent component and may not occur at all hours.
• A summary of key simulation pitfalls to watch for.
Infiltration is a space level load. As such, it impacts
HAP eHelp articles can be found in the Software Support the supply airflow calculation to the space which in
section of our web site (carrier.com/commercial). turn is the basis for fan and duct sizing.
(Continued on page 4)
3
Modeling Infiltration In HAP
(Continued from page 3)
4
CARRIER® eDESIGN SUITE NEWS
than units of cfm/sqft of exterior wall or actual cfm. Limiting Infiltration - The New Focus
The Infiltration Occurs item in HAP offers two ANSI®/ASHRAE®/IES® Standard 90.1- 2010 Section
choices for modeling hourly variation of infiltration 5.4.3 has addressed air leakage through the building
airflow: envelope. Specific items required are:
1. Only When Fan Off. This option will limit 1. Continuous Air Barrier - An air barrier shall be
infiltration load calculations to those hours during installed around the building that resists both
which the fan/thermostat schedule for the system positive and negative pressures such as wind,
serving the space has been scheduled for the stack effect, and mechanical ventilation
“unoccupied” mode. This option is NOT used to 2. Fenestration and Door - Performance requirements
model situations in which the building is positively are specified
pressurized during “occupied” hours (which is when
3. Weather Seals - Required where specified such as
the system is running continuously). Therefore,
loading dock doors
infiltration will only occur during the “unoccupied”
hours. (During unoccupied periods, the system 4. Vestibule Design - Specific design requirements for
actually cycles on and off to maintain the night both single and multi-story buildings
conditions so this choice really means “during the The goal is to prevent the uncontrolled leakage of
unoccupied cycle only.”) air both into and out of conditioned spaces. ASHRAE
2. All Hours. With this option, infiltration loads now seems to focus reduction of air leakage versus
will be calculated for all hours of the 24 hour day, providing more data to predict air leakage.
regardless of whether the system is in “occupied” Conclusion
or “unoccupied” mode. This option is used to model
Infiltration results in larger sizes for heating and
situations in which the building is not pressurized or
cooling equipment, ductwork, fans, and associated
the negligible when the system is on. As a result,
electrical and mechanical services to serve the
infiltration occurs for all hours of the day.
equipment. Also, unwanted infiltration can bring
Industry Findings thermal discomfort and complaints, increased energy
Infiltration is a topic that has received a lot of consumption, and even damage due to mold growth.
discussion but not a lot of research. The ASHRAE® Predicting infiltration quantity is and will remain a
Fundamentals Handbook, Chapter 16.25 contains judgment call for the HVAC design engineer. Stringent
interesting information on “Commercial and requirements in ASHRAE 90.1 - 2010 are aimed at
Institutional Air Leakage.” To summarize their reducing the infiltration heat loss and heat gain for a
findings, ASHRAE research found that infiltration commercial building. Factors like workmanship and
rates in eight U.S. office buildings ranged from testing accuracy of the building envelope will always
0.21 to 1.03 CFM/sf (of envelope area) at 0.3” w.g. affect actual results.
pressure differential and that typical infiltration rates If a decision has been made to include infiltration
are 0.10, 0.30 and 0.60 CFM/sf for tight, average in the building design, HAP will calculate infiltration
and leaky walls. based on any one of three input parameters that the
In addition, ASHRAE Std. 90.1-2013 App G Section HVAC engineer feels is applicable.
G.3.1.5b states that infiltration rates must be ANSI® is a registered trademark of the American National
Standards Institute
calculated as 0.4 CFM/sf of envelope area
ASHRAE® is a registered trademark of the American Society of
(@ 0.3” w.g.) and modeled at exactly the same for
Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
the Baseline and Proposed building models. Refer IES® is a registered trademark of the Illuminating Engineering
to 90.1-2013 App G for more information. Society of North America
5
Frequently Asked Questions
Question 1: When defining a Building in HAP, In addition, for most grid-connected power plants
the source electric generating efficiency shown distribution line losses of about 6% of transmitted
on the Meters tab defaults to 28%. How was power occur between the plant (source) and the site.
this calculated? How do I justify if this is an Taking the average fossil fuel power plant efficiency
acceptable percentage? If it is too low, how can as 30%, the overall electric generating efficiency is
it be increased? (0.30) x (1.00 - 0.06) = 0.28 or 28%. That is the
basis of the 28% default in HAP.
Answer: This value is a user input in the Building
> Meters tab.
Question 2: How do I model shading of a
From the HAP Help system:
window from an adjacent structure in HAP?
Source Electric Generating Efficiency
Answer: Modeling shading from external
This item defines the average generating efficiency structures is a complex analysis and typically
for electric power plants that provide energy to the requires 3D (x,y,z) spatial coordinates of the
building. This value is used to calculate “source” adjacent structure surfaces. For example,
energy totals on the two Energy Budget reports. This consider an L-shaped building where one
input is only required if the program will be used to wing of the “L” shades windows on the other
generate the Energy Budget reports and local energy wing of the building at certain times of day.
codes require that both “site” and “source” energy The coordinates of the adjacent wall surface
totals be provided. If this feature is not needed, set relative to a window being shaded need
the efficiency to 100%. to be known for shading calculations to be
Further Details: Energy Budget reports generated performed. HAP currently does not require
by HAP list the “site” and “source” energy use for a (x,y,z) spatial coordinates to be specified for
building. Site energy is the actual energy consumed wall and window surfaces, but nonetheless
by equipment in the building. Source energy is an there is a way to use the standard external
estimate of the energy required to generate electricity shading geometry inputs in HAP to model a
large adjacent shading surface.
6
CARRIER® eDESIGN SUITE NEWS
Basic Concept: Consider the wall surface of the 3. Specify “Projection from Wall Surface” as the
adjacent wing as a vertical shading fin. Typically the length of the wall shading surface. For example in
shading fin is relatively close to the window (within our L-shaped building, the adjacent wing might be
12-24 inches or 30-60cm), and the projection of 200 feet wide. “Projection from Wall Surface” would
the fin from the wall is similarly relatively small. But be specified as 2400 inches (200 feet, 60960 mm or
HAP allows relative distances and dimensions of the 60.96 m). Again, distances up to 250 ft (76.2 m) are
shading fin to be very large. That allows the “fin” to accepted as input.
represent a large adjacent wall surface. Steps:
4. Finally, specify “Height Above Window” as the
1. For each window, the position of the shading surface distance from the top edge of the window to the top
relative to the window must be defined. Create one of the adjacent wall shading surface. For example, the
External Shade Geometry item for each window. Viewing window of interest might be on the first floor in a 4-story
the window from outside the building, if the adjacent wall building, and the distance from the top of the window
surface is to the left, specify a “Left Fin.” If the adjacent to the roof level of the adjacent wall might be 40 feet
wall surface is to the right, specify a “Right Fin.” (12.2 m). In this case “Height Above Window” would be
specified as 480 inches (40 feet, 12192 mm or 12.192
2. Specify “Distance from Edge of Window” to
m). Distances up to 250 ft (76.2 m) are permitted.
represent the distance from the edge of the window to
the wall shading surface. For example in an L-shaped Because the relative coordinates of the wall shading
building a particular window might be 50 feet from the surface change for each window being shaded -
wall surface of the adjacent wing. “Distance from Edge “Distance from Edge of Window” and “Height Above
of Window” would be specified as 600 inches (50 feet, Window” in particular - steps 1 through 4 above need
15240 mm or 15.24 m). Distances up to 250 ft to be repeated for each individual window on the wall
(76.2 m) are accepted as input. being shaded.
7
2015 Training Class Schedule
Location Load Energy Energy Modeling Advanced Engineering Block
Calculation for Simulation for for LEED Energy
®
Modeling Economic Load
Commercial Commercial & Atmosphere Techniques for Analysis
Buildings Buildings Credit 1 HVAC Systems