Professional Documents
Culture Documents
Design Change Request (DCR) : PT - Barata Indonesia
Design Change Request (DCR) : PT - Barata Indonesia
BARATA INDONESIA
LGE001-CSA-STR-101-10 1 150KV SS STELL STRUCTURE DISCONNECTING SWITCH W/EARTH (LA) SECTION &
DETAIL
LGE001-CSA-CAL-103 1 150 kV Switchyard Structure Calculation - Lightning Arrester (LA)
In previous document approved, there was only 1 type of Lightning Arrester (LA). But in actual there was needed separated
type between Lightning Arrester (LA) in Generator Transformer and Switchyard area. And also to accommodate cable
clearance in Town Feeder Transformer (TFT). For quantity type 1, 18 to be 15 and for type 2, 6 to be 9.
CONTRACTOR RESPON :
Adjust steel structure of Lightning Arrester (LA) in Town Feeder Transformer (TFT) area from height 3556 mm to 4056 mm,
except in TFT area, Steel structure design doesn’t change
OE'S COMMENT :
OWNER'S COMMENT :
SIGNATURE :