Professional Documents
Culture Documents
1MRK502031-BUS D en Product Guide REG670 1.2 ANSI Customized-1
1MRK502031-BUS D en Product Guide REG670 1.2 ANSI Customized-1
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document.
© Copyright 2012 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
2 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2 Issued: February 2015
Revision: D
ABB 3
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
59N 3Uo>
ROV2 PTOV
64S RSE<
+ REX060
STTI PHIZ
D
Y 60FL 81 f< 81 f>
Y SDD RFUF SA PTUF SA PTOF
VT
78 Ucos
PSP PPAM
IEC11000201-1-en.vsd
IEC11000201 V1 EN
Figure 1. Generator protection application with generator differential, 100% stator ground fault and back-up protection
4 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
59N 3Uo>
ROV2 PTOV
64S RSE<
+ REX060
STTI PHIZ
Meter.
D CV MMXU
Y 60FL 81 f< 81 f>
Y SDD RFUF SA PTUF SA PTOF
VT
78 Ucos
PSP PPAM
64W IN>
EF4 PTOC
REG 670*1.2
IEC11000204-1-en.vsd
IEC11000204 V1 EN
Figure 2. Generator protection application for generator with split winding including generator phase differential, 100% stator ground fault and
back-up protection
ABB 5
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Meter.
D CV MMXU
Y 60FL 81 f< 81 f>
Y SDD RFUF SA PTUF SA PTOF
VT
78 Ucos
PSP PPAM
64W IN>
87W 3Id/I
EF4 PTOC
GEN PDIF
VT
59N UN> 59THD U3d/N
ROV2 PTOV STEF PHIZ
64S RSE<
+ REX060
STTI PHIZ
REG 670*1.2
IEC11000206-1-en.vsd
IEC11000206 V1 EN
Figure 3. Generator protection application for generator with split winding including generator phase differential, generator split-phase
differential, 100% stator ground fault and back-up protection
6 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
87T 3Id/I
T3W PDIF
Y
Unit Trafo
D 50/51 3I>
OC4 PTOC
50/51 3I>
OC4 PTOC
D 59N 3Uo>
Y
Y ROV2 PTOV
Excitation Trafo
Auxiliary Trafo
D
Y 60FL 81 f< 81 f>
Y
SDD RFUF SA PTUF SA PTOF
78 Ucos
PSP PPAM
IEC11000202-1-en.vsd
IEC11000202 V1 EN
Figure 4. Unit protection application with overall differential, generator differential, 100% stator ground fault and back-up protection. Stator
winding grounded via grounding transformer.
ABB 7
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
87T 3Id/I
T2W PDIF
D 50/51 3I>
OC4 PTOC
D
Y 59N 3Uo>
Y
ROV2 PTOV
64S RSE<
+ REX060
STTI PHIZ
REG 670*1.2
IEC11000203-1-en.vsd
IEC11000203 V1 EN
8 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Figure 5. Unit protection application with overall differential, unit transformer differential, generator differential, 100% stator ground fault and
back-up protection. Ungrounded stator winding.
ABB 9
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
87T 3Id/I
T2W PDIF
Y 50/51 3I>
OC4 PTOC
D 59N 3Uo>
ROV2 PTOV
64S RSE<
D + REX060
Y STTI PHIZ
Y
59N 3Uo>
ROV2 PTOV
VT 60FL 81 f< 78 Ucos
D
Y SDD RFUF SA PTUF PSP PPAM
Y
51/67 3I-> 50AE U/I> 21 Z< 24 U/f>
OC4 PTOC AEG GAPC ZMH PDIS OEX PVPH
IEC11000207-1-en.vsd
IEC11000207 V1 EN
Figure 6. Unit protection application with overall differential, unit transformer differential, generator differential, 100% stator ground fault and
back-up protection. Stator winding grounded via primary resistor.
10 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
2. Available functions
REG670
Differential protection
Impedance protection
ABB 11
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
REG670
Current protection
NS4PTOC 46I2 Four step directional negative phase sequence overcurrent protection 0-2
SDEPSDE 67N Sensitive directional residual overcurrent and power protection 0-2
NS2PTOC 46I2 Negative sequence time overcurrent protection for machines 0-2
Voltage protection
STEFPHIZ 59THD 100% stator earth fault protection, 3rd harmonic based 0-1
Frequency protection
Multipurpose protection
12 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
REG670
Control
APC30 3 Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) incl. interlocking 0-1
SLGGIO Logic rotating switch for function selection and LHMI presentation 15
Logic
Monitoring
CVMMXN Measurements 6
ABB 13
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
REG670
Metering
Designed to communicate
REG670
Station communication
14 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
3. Differential protection damage even to other components in the power plant, such as
turbine and generator-turbine shaft.
Generator differential protection GENPDIF (87G)
Short circuit between the phases of the stator windings causes To limit the damage due to stator winding short circuits, the
normally very large fault currents. The short circuit gives risk of fault clearance must be as fast as possible (instantaneous). If
damages on insulation, windings and stator iron core. The large the generator block is connected to the power system close to
short circuit currents cause large forces, which can cause other generating blocks, the fast fault clearance is essential to
maintain the transient stability of the non-faulted generators.
ABB 15
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Normally, the short circuit fault current is very large, that is,
significantly larger than the generator rated current. There is a Two-winding applications
risk that a short circuit can occur between phases close to the
neutral point of the generator, thus causing a relatively small
fault current. The fault current can also be limited due to low 152 352
excitation of the generator. Therefore, it is desired that the
detection of generator phase-to-phase short circuits shall be
relatively sensitive, detecting small fault currents. xx05000048_ansi.vsd
ANSI05000048 V1 EN
152 352
252 452
xx05000051_ansi.vsd
ANSI05000051 V1 EN
16 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
three–winding power transformer with two circuit Restricted earth-fault protection, low impedance REFPDIF (87N)
breakers and two CT-sets on one side
Restricted fault protection, low-impedance function (REFPDIF,
152 252
87N) can be used on all solidly or low-impedance grounded
windings. The REFPDIF (87N) function provides high sensitivity
552
and high speed tripping as it protects each winding separately
and thus does not need inrush stabilization.
ABB 17
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
The most typical CT CB CB CT The Pole slip protection (PSPPPAM ,78) function shall detect
application
The most complicated pole slip conditions and trip the generator as fast as possible if
application - autotransformer
the locus of the measured impedance is inside the generator-
transformer block. If the centre of pole slip is outside in the
IEC05000058-2-en.vsd
IEC05000058-2 V1 EN
power grid, the first action should be to split the network into
Figure 8. Examples of applications of the REFPDIF two parts, after line protection action. If this fails there should
be operation of the generator PSPPPAM (78) in zone 2, to
prevent further damages to the generator, shaft and turbine.
A short circuit may occur in the external power grid, close to Four step phase overcurrent protection OC4PTOC (51/67)
the generator. If the fault clearing time is too long, the generator The four step phase overcurrent protection function OC4PTOC
will accelerate so much, that the synchronism cannot be (51/67) has independent inverse time delay settings for step 1
maintained. and 4. Step 2 and 3 are always definite time delayed.
Un-damped oscillations occur in the power system, where All IEC and ANSI inverse time characteristics are available
generator groups at different locations, oscillate against each together with an optional user defined time characteristic.
other. If the connection between the generators is too weak the
magnitude of the oscillations will increase until the angular The directional function is voltage polarized with memory. The
stability is lost. function can be set to be directional or non-directional
independently for each of the steps.
The operation of a generator having pole slip will give risk of
damages to the generator, shaft and turbine. Second harmonic blocking level can be set for the function and
can be used to block each step individually
18 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
EF4PTOC (51N/67N) can also be used to provide a system No specific sensitive current input is needed.SDEPSDE can be
back-up for example, in the case of the primary protection set as low 0.25% of IBase.
being out of service due to communication or voltage
Thermal overload protection, two time constant TRPTTR (49)
transformer circuit failure.
If a power transformer or generator reaches very high
Directional operation can be combined together with temperatures the equipment might be damaged. The insulation
corresponding communication logic in permissive or blocking within the transformer/generator will have forced ageing. As a
teleprotection scheme. Current reversal and weak-end infeed consequence of this the risk of internal phase-to-phase or
functionality are available as well. phase-to-ground faults will increase. High temperature will
degrade the quality of the transformer/generator insulation.
EF4PTOC (51N/67N) can be configured to measure the residual
current from the three-phase current inputs or the current from The thermal overload protection estimates the internal heat
a separate current input. content of the transformer/generator (temperature)
continuously. This estimation is made by using a thermal model
Four step negative sequence overcurrent protection NS4PTOC of the transformer/generator with two time constants, which is
(4612) based on current measurement.
Four step negative sequence overcurrent protection (NS4PTOC,
(4612) ) has an inverse or definite time delay independent for Two warning pickup levels are available. This enables actions
each step separately. in the power system to be done before dangerous temperatures
are reached. If the temperature continues to increase to the trip
All IEC and ANSI time delayed characteristics are available value, the protection initiates a trip of the protected transformer/
together with an optional user defined characteristic. generator.
ABB 19
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Current check with extremely short reset time is used as check By using optional metering class CT inputs accuracy of 0,5%
criterion to achieve high security against inadvertent operation. can be achieved for steam turbine applications.
Contact check criteria can be used where the fault current Negative sequence time overcurrent protection for machines
through the breaker is small. NS2PTOC (46I2)
Negative-sequence time overcurrent protection for machines
CCRBRF (50BF) can be single- or three-phase initiated to allow NS2PTOC (46I2) is intended primarily for the protection of
use with single pole tripping applications. For the three-phase generators against possible overheating of the rotor caused by
version of CCRBRF (50BF) the current criteria can be set to negative sequence current in the stator current.
operate only if two out of four for example, two phases or one
phase plus the residual current pickups. This gives a higher The negative sequence currents in a generator may, among
security to the back-up trip command. others, be caused by:
Normally the own breaker is tripped to correct such a situation. To provide an effective protection for the generator for external
If the situation warrants the surrounding breakers should be unbalanced conditions, NS2PTOC (46I2) is able to directly
tripped to clear the unsymmetrical load situation. measure the negative sequence current. NS2PTOC (46I2) also
has a time delay characteristic which matches the heating
The Polediscrepancy protection function CCRPLD (52PD)
2
operates based on information from auxiliary contacts of the characteristic of the generator I 2 t = K as defined in standard
circuit breaker for the three phases with additional criteria from IEEE C50.13.
unsymmetrical phase currents when required.
where:
Directional over/underpower protection GOPPDOP/GUPPDUP
(32/37) I2 is negative sequence current expressed in
per unit of the rated generator current
The directional over-/under-power protection GOPPDOP (32)/
GUPPDUP (37) can be used wherever a high/low active, t is operating time in seconds
reactive or apparent power protection or alarming is required. K is a constant which depends of the
The functions can alternatively be used to check the direction of generators size and design
active or reactive power flow in the power system. There are a NS2PTOC (46I2) has a wide range of K settings and the
number of applications where such functionality is needed. sensitivity and capability of detecting and tripping for negative
Some of them are: sequence currents down to the continuous capability of a
generator.
• generator reverse power protection
• generator low forward power protection A separate output is available as an alarm feature to warn the
• detection of over/under excited generator operator of a potentially dangerous situation.
• detection of reversed active power flow
20 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
OV2PTOV (59) has an extremely high reset ratio to allow To detect a ground fault on the windings of a generating unit
settings close to system service voltage. one may use a neutral point overvoltage protection, a neutral
point overcurrent protection, a zero sequence overvoltage
Two step residual overvoltage protection ROV2PTOV (59N) protection or a residual differential protection. These
Residual voltages may occur in the power system during protections are simple and have served well during many years.
ground faults. However, at best these simple schemes protect only 95% of the
stator winding. They leave 5% close to the neutral end
Two step residual overvoltage protection ROV2PTOV (59N)
unprotected. Under unfavorable conditions the blind zone may
function calculates the residual voltage from the three-phase
extend up to 20% from the neutral.
voltage input transformers or measures it from a single voltage
ABB 21
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
The 95% stator ground fault protection measures the harmonic protection either the 3rd harmonic voltage differential
fundamental frequency voltage component in the generator star principle, the neutral point 3rd harmonic undervoltage principle
point and it operates when it exceeds the preset value. By or the terminal side 3rd harmonic overvoltage principle can be
applying this principle approximately 95% of the stator winding applied. However, differential principle is strongly
can be protected. In order to protect the last 5% of the stator recommended. Combination of these two measuring principles
winding close to the neutral end the 3rd harmonic voltage provides coverage for entire stator winding against ground
measurement can be performed. In 100% Stator E/F 3rd faults.
RN Rf Transformer
uN x 1- x uT
Samples of the Samples of the
neutral voltage 1 or 100 % terminal voltage
from which the from which the
fundamental and 3rd harmonic
3rd harmonic voltage is filtered
Neutral point fundamental frequency
voltages are out
over-voltage protection 5% - 100%
filtered out over- voltage protection 10%– 100%
3rd harmonic
Differential
differential
0% – 30%
0% - 30% ANSI10000202-1-en.vsd
ANSI10000202 V1 EN
22 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
General current and voltage protection CVGAPC The rotor ground fault protection is based on injection of an AC
The protection module is recommended as a general backup voltage to the isolated field circuit. In non-faulted conditions
protection with many possible application areas due to its there will be no current flow associated to this injected voltage.
flexible measuring and setting facilities. If a rotor ground fault occurs, this condition will be detected by
the rotor ground fault protection. Depending on the generator
The built-in overcurrent protection feature has two settable owner philosophy this operational state will be alarmed and/or
current pickups. Both of them can be used either with definite the generator will be tripped. An injection unit is required for
time or inverse time characteristic. The overcurrent protection rotor ground fault protection (RXTTE4) and a protective resistor
steps can be made directional with selectable voltage polarizing on plate for correct operation.
quantity. Additionally they can be voltage and/or current
controlled/restrained. 2nd harmonic restraining facility is
available as well. At too low polarizing voltage the overcurrent 9. Secondary system supervision
feature can be either blocked, made non directional or ordered
to use voltage memory in accordance with a parameter setting. Current circuit supervision CCSRDIF (87)
Open or short circuited current transformer cores can cause
Additionally two overvoltage and two undervoltage steps, either unwanted operation of many protection functions such as
with definite time or inverse time characteristic, are available differential, ground-fault current and negative-sequence current
within each function. functions.
The general function suits applications with underimpedance It must be remembered that a blocking of protection functions
and voltage controlled overcurrent solutions. The general at an occurrence of open CT circuit will mean that the situation
function can also be utilized for generator transformer will remain and extremely high voltages will stress the
protection applications where positive, negative or zero secondary circuit.
sequence components of current and voltage quantities are
typically required. Current circuit supervision (CCSRDIF, 87) compares the
residual current from a three phase set of current transformer
Additionally, generator applications such as loss of field, cores with the neutral point current on a separate input taken
inadvertent energizing, stator or rotor overload, circuit breaker from another set of cores on the current transformer.
head flash-over and open phase detection are just a few of
possible protection arrangements with these functions.
ABB 23
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
A detection of a difference indicates a fault in the circuit and is SESRSYN (25) function includes a built-in voltage selection
used as alarm or to block protection functions expected to give scheme for double bus and breaker-and-a-half or ring busbar
unwanted tripping. arrangements.
Fuse failure supervision SDDRFUF Manual closing as well as automatic reclosing can be checked
The aim of the fuse failure supervision function (SDDRFUF) is to by the function and can have different settings.
block voltage measuring functions at failures in the secondary
circuits between the voltage transformer and the IED in order to For systems which are running asynchronous a synchronizing
avoid unwanted operations that otherwise might occur. function is provided. The main purpose of the synchronizing
function is to provide controlled closing of circuit breakers when
The fuse failure supervision function basically has three different two asynchronous systems are going to be connected. It is
algorithms, negative sequence and zero sequence based used for slip frequencies that are larger than those for
algorithms and an additional delta voltage and delta current synchronism check and lower than a set maximum level for the
algorithm. synchronizing function.
The negative sequence detection algorithm is recommended for However this function can not be used to automatically
IEDs used in isolated or high-impedance grounded networks. It synchronize the generator to the network.
is based on the negative-sequence measuring quantities, a high
value of voltage without the presence of the negative-sequence Apparatus control APC
current 3I 2. The apparatus control functions are used for control and
supervision of circuit breakers, disconnectors and grounding
The zero sequence detection algorithm is recommended for switches within a bay. Permission to operate is given after
IEDs used in directly or low impedance grounded networks. It evaluation of conditions from other functions such as
is based on the zero sequence measuring quantities, a high interlocking, synchronism check, operator place selection and
value of voltage 3V 0 without the presence of the residual external or internal blockings.
current 3I 0.
Apparatus control features:
• Select-Execute principle to give high reliability
For better adaptation to system requirements, an operation
• Selection function to prevent simultaneous operation
mode setting has been introduced which makes it possible to
• Selection and supervision of operator place
select the operating conditions for negative sequence and zero
• Command supervision
sequence based function. The selection of different operation
• Block/deblock of operation
modes makes it possible to choose different interaction
• Block/deblock of updating of position indications
possibilities between the negative sequence and zero sequence
• Substitution of position indications
based algorithm.
• Overriding of interlocking functions
A criterion based on delta current and delta voltage • Overriding of synchrocheck
measurements can be added to the fuse failure supervision • Operation counter
function in order to detect a three phase fuse failure, which in • Suppression of Mid position
practice is more associated with voltage transformer switching
during station operations.
Two types of command models can be used:
• Direct with normal security
10. Control • SBO (Select-Before-Operate) with enhanced security
24 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Control operation can be performed from the local HMI under same role as functions GOOSEBINRCV (for IEC 61850) and
authority control if so defined. MULTICMDRCV (for LON).
AutomationBits, command function for DNP3.0 AUTOBITS • TIMERSET function has pick-up and drop-out delayed
AutomationBits function for DNP3 (AUTOBITS) is used within outputs related to the input signal. The timer has a settable
PCM600 to get into the configuration of the commands coming time delay.
through the DNP3 protocol. The AUTOBITS function plays the
ABB 25
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Alarm limits can be set and used as triggers, e.g. to generate Indications DRPRDRE
trip or alarm signals. To get fast, condensed and reliable information about
disturbances in the primary and/or in the secondary system it is
The function requires that the IED is equipped with the mA input
important to know, for example binary signals that have
module.
changed status during a disturbance. This information is used in
Event counter CNTGGIO the short perspective to get information via the local HMI in a
Event counter (CNTGGIO) has six counters which are used for straightforward way.
storing the number of times each counter input has been
activated.
26 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
There are three LEDs on the local HMI (green, yellow and red), The function is characterized by great flexibility and is not
which will display status information about the IED and the dependent on the operation of protection functions. It can
Disturbance report function (triggered). record disturbances not detected by protection functions. Up to
ten seconds of data before the trigger instant can be saved in
The Indication list function shows all selected binary input the disturbance file.
signals connected to the Disturbance report function that have
changed status during a disturbance. The disturbance recorder information for up to 100
disturbances are saved in the IED and the local HMI is used to
Event recorder DRPRDRE view the list of recordings.
Quick, complete and reliable information about disturbances in
the primary and/or in the secondary system is vital, for example, Event function
time-tagged events logged during disturbances. This When using a Substation Automation system with LON or SPA
information is used for different purposes in the short term (for communication, time-tagged events can be sent at change or
example corrective actions) and in the long term (for example cyclically from the IED to the station level. These events are
functional analysis). created from any available signal in the IED that is connected to
the Event function (EVENT). The event function block is used for
The event recorder logs all selected binary input signals remote communication.
connected to the Disturbance report function. Each recording
can contain up to 150 time-tagged events. Analog and double indication values are also transferred
through EVENT function.
The event recorder information is available for the disturbances
locally in the IED. IEC61850 generic communication I/O function SPGGIO
IEC61850 generic communication I/O functions (SPGGIO) is
The event recording information is an integrated part of the used to send one single logical signal to other systems or
disturbance record (Comtrade file). equipment in the substation.
Trip value recorder DRPRDRE IEC61850 generic communication I/O functions MVGGIO
Information about the pre-fault and fault values for currents and IEC61850 generic communication I/O functions (MVGGIO)
voltages are vital for the disturbance evaluation. function is used to send the instantaneous value of an analog
signal to other systems or equipment in the substation. It can
The Trip value recorder calculates the values of all selected
also be used inside the same IED, to attach a RANGE aspect to
analog input signals connected to the Disturbance report
an analog value and to permit measurement supervision on that
function. The result is magnitude and phase angle before and
value.
during the fault for each analog input signal.
Measured value expander block RANGE_XP
The trip value recorder information is available for the
The current and voltage measurements functions (CVMMXN,
disturbances locally in the IED.
CMMXU, VMMXU and VNMMXU), current and voltage sequence
The trip value recorder information is an integrated part of the measurement functions (CMSQI and VMSQI) and IEC 61850
disturbance record (Comtrade file). generic communication I/O functions (MVGGIO) are provided
with measurement supervision functionality. All measured
Disturbance recorder DRPRDRE values can be supervised with four settable limits: low-low limit,
The Disturbance recorder function supplies fast, complete and low limit, high limit and high-high limit. The measure value
reliable information about disturbances in the power system. It expander block (RANGE_XP) has been introduced to enable
facilitates understanding system behavior and related primary translating the integer output signal from the measuring
and secondary equipment during and after a disturbance. functions to 5 binary signals: below low-low limit, below low
Recorded information is used for different purposes in the short limit, normal, above high-high limit or above high limit. The
perspective (for example corrective actions) and long output signals can be used as conditions in the configurable
perspective (for example functional analysis). logic or for alarming purpose.
Time synchronization
The time synchronization source selector is used to select a
common source of absolute time for the IED when it is a part of
a protection system. This makes it possible to compare event
and disturbance data between all IEDs in a station automation
system.
ANSI07000083 V1 EN
15. Human machine interface Figure 10. Example of medium graphic HMI
28 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
ABB 29
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
30 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
B C
D
xx05000003.vsd
IEC05000003 V1 EN
xx05000004.vsd
IEC05000004 V1 EN
Case size A B C D E F
(inches)
Mounting alternatives See ordering for details about available mounting alternatives.
• 19” rack mounting kit
• Wall mounting kit
ABB 31
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
1MRK002801-AC-2-670-1.2-PG V1 EN
32 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
1MRK002801-AC-3-670-1.2-PG V1 EN
ABB 33
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
1MRK002801-AC-4-670-1.2-PG V1 EN
34 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
1MRK002801-AC-5-670-1.2-PG V1 EN
ABB 35
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
1MRK002801-AC-6-670-1.2-PG V1 EN
1MRK002802-AB-10-670-1.2-PG-ANSI V1 EN
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-processing function blocks.
36 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
configuration
(50/60 Hz)
12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
9I+3V, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V
9I+3V, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V
5I, 1A+4I, 5A+3V 1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V
7I+5V, 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
7I+5V, 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
6I, 5A+1I, 1A+5V 5A 5A 5A 5A 5A 5A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
3I, 5A+4I, 1A+5V 5A 5A 5A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
3IM, 1A+4IP, 1A+5V 1AM 1AM 1AM 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
*) *) *)
3IM, 5A+4IP, 5A+5V 5AM 5AM 5AM 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
*) *) *)
6I+6V, 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
6I+6V, 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
3I, 5A+3I, 1A+6V 5A 5A 5A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
6I, 1A 1A 1A 1A 1A 1A 1A - - - - - -
6I, 5A 5A 5A 5A 5A 5A 5A - - - - - -
*) Metering
1MRK002802-AB-7-670-1.2-PG-ANSI V1 EN
ABB 37
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
1MRK002802-AB-11-670-1.2-PG-ANSI V1 EN
Figure 15. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, etc. and input contacts named XB to
rear position X32, X42, etc.
1MRK002802-AB-12-670-1.2-PG-ANSI V1 EN
Figure 16. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, etc. and output contacts named
XB to rear position X32, X42, etc.
1MRK002802-AB-13-670-1.2-PG-ANSI V1 EN
Figure 17. Static output module (SOM). Output contacts named XA corresponds to rear position X31, X41, etc. and output contacts named XB
to rear position X32, X42, etc.
1MRK002802-AB-14-670-1.2-PG-ANSI V1 EN
Figure 18. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, etc. and output contacts named XB to
rear position X32, X42, etc.
1MRK002802-AB-15-670-1.2-PG-ANSI V1 EN
38 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
1MRK002802-AB-8-670-1.2-PG-ANSI V1 EN
ABB 39
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified
requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Table 7. TRM - Energizing quantities, rated values and limits for protection transformer modules
Current In = 1 or 5 A (0.2-40) × In
Frequency fn = 60/50 Hz ± 5%
40 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer modules
Current In = 1 or 5 A (0-1.8) × In at In = 1 A
(0-1.6) × In at In = 5 A
Frequency fn = 60/50 Hz ± 5%
Power consumption -
each mA-board £2W
each mA input £ 0.1 W
Number of channels 1 or 2
ABB 41
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Auxiliary DC voltage
Binary inputs 16 -
Power consumption
24/30 V, 50mA max. 0.05 W/input -
48/60 V, 50mA max. 0.1 W/input
125 V, 50mA max. 0.2 W/input
220/250 V, 50mA max. 0.4 W/input
220/250 V, 110mA max. 0.5 W/input
42 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 13. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
ABB 43
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
44 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
ABB 45
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
220V / 0.2A
250V / 0.15A
Table 18. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0s 10A
0.2s 30A
1.0s 10A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
46 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
90-250 V DC ± 20%
Interruption interval
0–50 ms
No restart
ABB 47
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fn ± 1.0%
Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fn ±5.0%
protection (10% content)
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
1.4-2.7 GHz
48 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Damp heat test, steady state Test Ca for 4 days at +40 °C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55 °C and humidity 93 to 95% (1 cycle = 24 IEC 60068-2-30
hours)
Test According to
Immunity EN 50263
Emissivity EN 50263
ABB 49
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Differential protection
50 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 30. Restricted earth fault protection, low impedance REFPDIF (87N)
ABB 51
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
52 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Impedance protection
ABB 53
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Current protection
Inverse characteristics, see 16 curve types See table 99, table 100 and table 101
table 99, table 100 and table 101
54 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Inverse characteristics, see table 18 curve types See table 99, table 100 and table
99, table 100 and table 101 101
ABB 55
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 39. Four step negative sequence overcurrent protection NS4PTOC (46I2)
Inverse characteristics, see table 18 curve types See table 99, table 100 and table
99, table 100 and table 101 101
Minimum operate current for step (1.00 - 10000.00)% of IBase ± 1.0% of In at I < In
1-4 ± 1.0% of I at I > In
56 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 40. Sensitive directional residual overcurrent and power protection SDEPSDE (67N)
At low setting:
(0.25-1.00)% of In: ±0.05% of In
(1.00-5.00)% of In: ±0.1% of In
At low setting:
(0.25-1.00)% of In: ±0.05% of In
(1.00-5.00)% of In: ±0.1% of In
Inverse characteristics, see 19 curve types See table 99, table 100 and table 101
table 99, table 100 and table
101
ABB 57
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 40. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) , continued
Function Range or value Accuracy
Table 41. Thermal overload protection, two time constants TRPTTR (49)
Operate time: Ip = load current before overload IEC 60255–8, ±5% + 200 ms
occurs
æ I 2 - I p2 ö Time constant τ = (1–500)
t = t × ln ç 2 ÷ minutes
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 1)
I = Imeasured
Alarm pickup 1 and 2 (50–99)% of heat content trip ± 2.0% of heat content trip
value
Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip
Phase current pickup for blocking of contact function (5-200)% of lBase ± 1.0% of In at I £ In
± 1.0% of I at I > In
58 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
*) To achieve this accuracy for reverse power protection it is also recommended to apply setting AngleN=-179.3 degrees instead of standard 180
degrees. This setting will help to minimize the overall measurement error ensuring the above stated accuracy for this application.
*) To achieve this accuracy for reverse power protection it is also recommended to apply setting AngleN=-179.3 degrees instead of standard 180
degrees. This setting will help to minimize the overall measurement error ensuring the above stated accuracy for this application.
ABB 59
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 46. Negative sequence time overcurrent protection for machines NS2PTOC (46I2)
Operate value, step 1 and 2, negative sequence overcurrent (3-500)% of IBase ± 1.0% of In at I < In
± 1.0% of I at I > In
K=1.0-99.0 ± 5% + 40 ms
Inverse time characteristic step 1, I 22t = K
K=0.01-20.00 ± 10% + 40 ms
Reset time, inverse characteristic step 1, I 22t = K
Table 47. Accidental energizing protection for synchronous generator AEGGAPC (50AE)
60 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Voltage protection
Inverse time characteristics for step 1 and step 2, see table 103 - See table 103
Inverse time characteristics for steps 1 and 2, see table 102 - See table 102
ABB 61
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Inverse time characteristics for low and high step, see table 104 - See table 104
(0.18 × TD)
IEEE : t =
( M - 1) 2
EQUATION1645 V1 EN (Equation 2)
where M = (E/f)/(Vn/fn)
62 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Filter characteristic: -
Fundamental Reject third harmonic by 1–40
Third harmonic Reject fundamental harmonic by
1–40
ABB 63
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Frequency protection
VMin=(50-150)% of Vbase
Exponent=0.0-5.0
t_MaxTripDelay=(0.000-60.000)
s
t_MinTripDelay=(0.000-60.000)
s
Exponent
é V - VMin ù
ëVNom - VMin úû
t=ê
EQUATION1559 V1 EN (Equation 3)
V=Vmeasured
Operate time, pickup function 100 ms typically at fset -0.5 Hz to fset +0.5 Hz -
64 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
ABB 65
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Multipurpose protection
See table 99 and table 100 Parameter ranges for customer defined See table 99 and table 100
characteristic no 17:
TD: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Voltage level where voltage memory takes over (0.0 - 5.0)% of VBase ± 0.5% of Vn
Pickup overvoltage, step 1 and 2 (2.0 - 200.0)% of VBase ± 0.5% of Vn for V<Vn
± 0.5% of V for V>Vn
Pickup undervoltage, step 1 and 2 (2.0 - 150.0)% of VBase ± 0.5% of Vn for V<Vn
± 0.5% of V for V>Vn
66 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
High and low voltage limit, voltage dependent operation (1.0 - 200.0)% of VBase ± 1.0% of Vn for V<Vn
± 1.0% of V for V>Vn
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
ABB 67
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 58. Rotor earth fault protection (64R) based on General current and voltage protection (CVGAPC) and RXTTE4
68 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
ABB 69
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Control
Table 61. Synchronizing, synchronism check and energizing check SESRSYN (25)
Voltage high limit for synchronism check (50.0-120.0)% of VBaseBus and ± 0.5% of Vn at V ≤ Vn
VBaseLine ± 0.5% of V at V > Vn
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ± 2.0 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ± 2.0 degrees
Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ± 0.5% of Vn
synchrocheck
tMaxSynch, which resets synchronizing function if no close has been made (0.000-60.000) s ± 0.5% ± 10 ms
before set time
Voltage high limit for energizing check (50.0-120.0)% of VBaseBus and ± 0.5% of Vn at V ≤ Vn
VBaseLine ± 0.5% of V at V > Vn
Voltage low limit for energizing check (10.0-80.0)% of VBaseBus and ± 0.5% of Vn
VBaseLine
70 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Logic
LogicAND 60 60 160 - -
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicRSMemory 10 10 20 - -
LogicGate 10 10 20 - -
Boolean 16 to Integer 4 4 8 - -
Boolean 16 to integer 4 4 8 - -
with Logic Node
Integer to Boolean 16 4 4 8 - -
Integer to Boolean 16 4 4 8 - -
with Logic Node
ABB 71
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Monitoring
72 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
ABB 73
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Maximum number of events in the Sequence of events 1000, first in - first out -
Maximum total recording time (3.4 s recording time and maximum number of channels, 340 seconds (100 recordings) at -
typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz
Function Value
Resolution 1 ms
Function Value
Function Value
Resolution 1 ms
74 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Function Value
Function Value
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) at 50 Hz
of channels, typical value) 280 seconds (80 recordings) at 60 Hz
ABB 75
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Metering
Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import
76 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Station communication
Function Value
Protocol DNP3.0
Function Value
Protocol LON
Function Value
Protocol SPA
Function Value
ABB 77
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Table 87. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
78 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Transmission rate / Data rate 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s
Clock source Internal or derived Internal or derived Internal or derived from received
from received from received signal signal
signal
ABB 79
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Hardware
IED
Table 90. Water and dust protection level according to IEC 60529
Connection system
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
80 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled measurement ± 1.0 ms typically
values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
Function Value
Accuracy +/-2μs
ABB 81
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
82 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Inverse characteristic
æ A ö
t = ç P + B ÷ × td
ç ( I - 1) ÷
è ø
EQUATION1651 V1 EN
Reset characteristic:
tr
t = × td
(I 2
-1 )
EQUATION1652 V1 EN
I = Imeasured/Iset
ABB 83
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
æ A ö
t = ç P ÷ × td
ç ( I - 1) ÷
è ø
EQUATION1653 V1 EN
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms
TR
t = × td
(I PR
- CR )
EQUATION1655 V1 EN
I = Imeasured/Iset
84 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è td ø
EQUATION1657 V1 EN
I = Imeasured/Iset
td
t =
æ V - VPickup ö
ç ÷
è VPickup ø
EQUATION1661 V1 EN
V = Vmeasured
td × 480
t =
2.0
æ V - VPickup ö
ç 32 × - 0.5 ÷ - 0.035
è VPickup ø
EQUATION1662 V1 EN
td × 480
t =
3.0
æ V - VPickup ö
ç 32 × - 0.5 ÷ - 0.035
è VPickup ø
EQUATION1663 V1 EN
ABB 85
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
td
t =
æ VPickup - V ö
ç ÷
è VPickup ø
EQUATION1658 V1 EN
V = Vmeasured
td × 480
t = + 0.055
2.0
æ VPickup - V ö
ç 32 × - 0.5 ÷
è VPickup ø
EQUATION1659 V1 EN
V = Vmeasured
V = Vmeasured
86 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
V = Vmeasured
ABB 87
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
21. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in
combination with other functions and that some functions require specific hardware selections.
Please refer to the available functions table for included application functions.
Product specification
Basic IED 670 platform and common functions housed in selected casing
Default:
The IED connect CD contains configuration alternative. Use the PCM600 to create or modify the configuration. The PCM600 can also be used for
adaptation of an included example configuration.
Option:
Customer specific configuration On request
Rule: Same connection type for Power supply modules and I/O modules must be ordered
Compression terminals 1MRK 002 960-AA
Logic
Optional functions
88 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Differential protection
1 2
Transformer differential protection, two winding (T2WPDIF, 87T) Qty: 1MRK 002 901-AC
1 2
Transformer differential protection, three winding (T3WPDIF, 87T) Qty: 1MRK 002 901-CC
1 2 3 4 5 6
1Ph High impedance differential protection (HZPDIF, 87) Qty: 1MRK 002 901-HB
1 2
Generator differential protection (GENPDIF, 87G) Qty: 1MRK 002 901-PB
1 2 3
Restricted earth fault protection, low impedance (REFPDIF, 87N) Qty: 1MRK 002 901-EB
Impedance protection
1 2
Directional impedance element for mho characteristic (ZDMRDIR, 21D) Qty: 1MRK 002 924-PA
1 2
Loss of excitation (LEXPDIS, 40) Qty: 1MRK 002 925-MB
Note: If ROTIPHIZ or STTIPHIZ is ordered, Injection equipment is also required, see section
Accessories, "Injection equipment"
Sensitive rotor earth fault protection, injection based (ROTIPHIZ, 64R) Qty: 1MRK 002 908-YA
ABB 89
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Current protection
1 2 3 4
Instantaneous phase overcurrent protection (PHPIOC, 50) Qty: 1MRK 002 906-AC
1 2 3 4 5 6
Four step phase overcurrent protection (OC4PTOC, 51/67) Qty: 1MRK 002 906-BD
1 2
Instantaneous residual overcurrent protection (EFPIOC, 50N) Qty: 1MRK 002 906-CC
1 2 3 4 5 6
Four step residual overcurrent protection (EF4PTOC, 51N/67N) Qty: 1MRK 002 906-DD
1 2
Four step directional negative phase sequence overcurrent protection (NS4PTOC, 46I2) Qty: 1MRK 002 906-DM
1 2
Sensitive directional residual overcurrent and power protection (SDEPSDE, 67N) Qty: 1MRK 002 907-DC
1 2 3
Thermal overload protection, two time constants (TRPTTR, 49) Qty: 1MRK 002 906-NC
1 2 3 4
Breaker failure protection (CCRBRF, 50BF) Qty 1MRK 002 906-RC
1 2 3 4
Pole discrepancy protection (CCRPLD, 52PD) Qty: 1MRK 002 907-AC
1 2 3 4
Directional underpower protection (GUPPDUP, 37) Qty: 1MRK 002 902-FB
1 2 3 4
Directional overpower protection (GOPPDUP, 32) Qty: 1MRK 002 902-GB
1 2
Negative sequence time overcurrent protection for machines (NS2PTOC, 46I2) Qty: 1MRK 002 902-LA
1 2
Accidental energizing protection for synchronous generator (AEGGAPC, 50AE) Qty: 1MRK 002 902-NA
90 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Voltage protection
1 2
Two step undervoltage protection (UV2PTUV, 27) Qty: 1MRK 002 908-AC
1 2
Two step overvoltage protection (OV2PTOV, 59) Qty: 1MRK 002 908-DC
1 2 3
Two step residual overvoltage protection (ROV2PTOV, 59N) Qty: 1MRK 002 908-GC
1 2
Overexcitation protection (OEXPVPH, 24) Qty: 1MRK 002 908-MC
1 2
Voltage differential protection (VDCPTOV, 60) Qty: 1MRK 002 924-TB
100% Stator E/F 3rd harmonic (STEFPHIZ, 59THD) Qty: 1MRK 002 908-TB
Frequency protection
1 2 3 4 5 6
Underfrequency protection (SAPTUF, 81) Qty: 1MRK 002 908-NC
1 2 3 4 5 6
Overfrequency protection (SAPTOF, 81) Qty: 1MRK 002 908-RC
1 2 3
Rate-of-change frequency protection (SAPFRC, 81) Qty: 1MRK 002 908-SB
Multipurpose protection
1 2 3 4 5 6
General current and voltage protection (CVGAPC) Qty: 1MRK 002 902-AB
7 8 9 10 11 12
1 2 3 4 5
Current circuit supervision (CCSRDIF, 87) Qty: 1MRK 002 914-AB
1 2 3
Fuse failure supervision (SDDRFUF) Qty: 1MRK 002 914-GC
ABB 91
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Control
1 2
Synchrocheck, energizing check and synchronizing (SESRSYN, 25) Qty: 1MRK 002 916-AD
Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) incl. interlocking 1MRK 002 916-RD
1 2 3 4
Tap changer control and supervision, 6 binary inputs, coded binary (Binary, BCD, Gray) Qty: 1MRK 002 925-PC
(TCMYLTC, 84)
1 2 3 4
Tap changer control and supervision, 32 binary inputs, one per position (TCLYLTC, 84) Qty: 1MRK 002 924-UB
Station communication
Optional hardware
Human machine hardware interface
92 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
ABB 93
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Analog system
Transformer input module, compression terminals 3IM, 1A+4IP, 1A+5U, Qty: 1 2 1MRK 002 247-EA
50/60 Hz
Transformer input module, compression terminals 3IM, 5A+4IP, 5A+5U, Qty: 1 2 1MRK 002 247-EB
50/60 Hz
94 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Transformer input module, ring lug terminals 3IM, 1A+4IP, 1A+5U, Qty: 1 2 1MRK 002 247-EC
50/60 Hz
Transformer input module, ring lug terminals 3IM, 5A+4IP, 5A+5U, Qty: 1 2 1MRK 002 247-ED
50/60 Hz
ABB 95
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Note: One Analog digital conversion module, with time synchronization is always delivered with each Transformer input module.
Case size
When ordering I/O modules, observe the maximum quantities according to tables below.
Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be
freely placed.
Note: Maximum quantity of I/O modules depends on the type of connection terminals.
Maximum quantity of I/O modules, with ring lug terminals, module limits see above
Case sizes Maximum in case Possible locations for I/O modules
with ringlugs
1/1 x 19”, one (1) TRM 7 P3, P5, P7, P9, P11, P13, P15 1MRK 000 151-NC
1/1 x 19”, two (2) TRM 5 P3, P5, P7, P9, P11 1MRK 000 151-ND
3/4 x 19”, one (1) TRM 4 P3, P5, P7, P9 1MRK 000 151-NB
96 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC
withstand capability is further increased.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Binary input module (BIM) 16 inputs
RL 24-30 VDC, 30 mA Qty: 1 2 3 4 5 6 7 1MRK 000 508-DB
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
ABB 97
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Binary input module (BIM) with enhanced pulse counting capabilities, 16 inputs
RL 24-30 VDC Qty: 1 2 3 4 5 6 7 1MRK 000 508-HA
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
Binary output module 24 output relays (BOM) Qty: 1 2 3 4 5 6 7 1MRK 000 614-AB
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
98 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Make IOM with 50 mA inrush current the primary choice. IOM with 50 mA inrush current fulfill additional standards. As a
consequence the EMC withstand capability is further increased.
IOM with 30 mA inrush current is still available.
Binary input/output module (IOM) 8 inputs, 10 outputs, 2 high-speed outputs
RL 24-30 VDC, 30 mA Qty: 1 2 3 4 5 6 1MRK 000 173-GB
Binary input/output module (IOM with MOV), 8 inputs, 10 outputs, 2 high-speed outputs
RL 24-30 VDC Qty: 1 2 3 4 5 6
1MRK 000 173-GC
ABB 99
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Note: Optical ethernet module, 2 glass interfaces is not allowed together with SLM.
Optical ethernet module, 1 channel glass 1MRK 002 266-AA
Serial and LON communication module, supports SPA/IEC 60870-5-103, LON and DNP 3.0
Serial/LON plastic interface 1MRK 001 608-AB
Galvanic RS485 communication module for DNP 3.0 1MRK 002 309-AA
Time synchronization
Engineering facilities
19” rack mounting kit for 1/2 x 19” case or 2 x RHGS6 or RHGS12 Quantity: 1MRK 002 420-BB
19” rack mounting kit for 3/4 x 19” case or 3 x RHGS6 Quantity: 1MRK 002 420-BA
19” rack mounting kit for 1/1 x 19” case Quantity: 1MRK 002 420-CA
Note: Wall mounting not recommended with communication modules with fibre connection (SLM, OEM, Quantity: 1MRK 002 420-DA
LDCM)
Wall mounting kit for terminal
Flush mounting kit + IP54 sealing (factory mounted). Cannot be ordered separately thus must be Quantity: 1MRK 002 420-EA
specified when ordering a terminal.
100 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Accessories
GPS antenna and mounting details
Cable for antenna, (Appx. 131 ft) Quantity: 1MRK 001 665-BA
External interface converter from C37.94 to G703 Quantity: 1 2 1MRK 002 245-AA
External interface converter from C37.94 to G703.E1 Quantity: 1 2 1MRK 002 245-BA
Due to the high flexibility of our product and the wide variety of The normally open "In test mode" contact 29-30 on the RTXP
applications possible the test switches needs to be selected for test switches should be connected to the input of the test
each specific application. function block to allow activation of functions individually during
testing.
Select your suitable test switch based on the available contacts
arrangements shown in the reference documentation. Test switches type RTXP 24 is ordered separately. Please refer
to Section "Related documents" for reference to corresponding
However our proposals for suitable variants are: documents.
Two winding transformer with internal neutral on current RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and
circuits. Two pcs can be used in applications for three winding the on/off switch for dc-supply are ordered separately. Please
transformers in single or multi-breaker arrangement (ordering refer to Section "Related documents" for reference to
number RK926 315-BD) corresponding documents.
ABB 101
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V 1 2 3
operating voltage Quantity: RK795101-MA
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100V Quantity: RK795101-MB
operating voltage
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 100-400V 1 2 3
operating voltage Quantity: RK795101-CB
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 100-400V Quantity: RK795101-DC
operating voltage
102 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Injection equipment
Casing
1/2 x 19" rack casing Basic
Backplane module (BPM) Basic
Human machine interface
HMI and logic module (HLM) Basic
Injection modules
Rule: Stator injection module (SIM) is required if 100% stator earth fault protection, injection
based (STTIPHIZ) is selected/active in REG670
Stator injection module (SIM) 1MRK 002 544-AA
Rule: Rotor injection module (RIM) is required if Sensitive rotor earth fault protection, injection
based (ROTIPHIZ) is selected/active in REG670
Rotor injection module (RIM) 1MRK 002 544-BA
Extra IP54 mounting seal + Flush mounting kit for terminal 1MRK 002 420-EA
Rule: REX061 requires REX060 and that Rotor injection module (RIM) is selected in REX060 and
that Sensitive rotor earth fault protection, injection based (ROTIPHIZ) is selected/active in REG670.
Coupling capacitor unit (REX061) Quantity: 1MRK 002 550-AA
Rule: REX062 requires REX060 and that Stator injection module (SIM) is selected in REX060 and
that 100% stator earth fault protection, injection based (STTIPHIZ) is selected/active in REG670
Shunt resistor unit (REX062) Quantity: 1MRK 002 555-AA
Combiflex
ABB 103
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Injection unit for Rotor earth fault protection (RXTTE 4) Quantity: 1MRK 002 108-BA
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference
manual, Installation and commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB
104 ABB
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Type of prime mover: steam , gas , hydro , pumpstorage , nuclear , other ______________________
ABB 105
Generator protection REG670 ANSI 1MRK502031-BUS D
Customized
Product version: 1.2
Related documents
106 ABB
107
Contact us
ABB Inc.
3450 Harvester Road
Burlington, ON L7N 3W5, Canada
Phone Toll Free: 1-800-HELP-365,
menu option #8