ABB 11kV Terminal Box Layout

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

High voltage terminal box for IEC motors

The picture shows high voltage terminal box with its


main technical data below.

Technical data: Materials:


Voltage (max.) 11.0 kV Box welded sheet steel (thickness
Current (max.) 400 A min. 3 mm)
No of cables (max.) 1 per phase Cable gland plate steel
Cross section of cables (max.) 300 mm2/cable Connection screws Bronze Bz
Cable gland blind gland (1 pce) Isolators epoxy casting resin
Clearance (min.) 100 mm Grounding pad stainless steel
Creepage (min.) 158 mm
Gross volume 122 dm3 Other features:
Usable volume 116 dm3 - rigid welded construction
Connection screws M16 (3 pcs) - ample size for making connections of supply cables
Connection nuts tightening torque 40 Nm - box turnable to allow cable entry from left or right side
Ground connections M12 (both in- and - box turnable in steps of 90°
outside) - either 3-phase or 1-phase cables can be connected
Weight 62 kg - pressure relief plate in the bottom of the box in case
Protection IP66 of an arching short circuit
Standard DIN 42962 TEIL 2, C2 - different cable glands available

Figure above: High voltage terminal box. Dimensions in mm.

54 ABB/ BU Machines / HV Induction motors IEC catalogue / Engineered motors EN 05-2006