Calculation and Specification of Lightings and Electrical Terminals

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 26

DESIGN IV ELECTRICAL SYSTEM

DOUBLE DEGREE ON MARINE


ENGINEERING
ITS – HOCHSCHULE WISMAR

CALCULATION AND
SPECIFICATION OF LIGHTINGS
AND ELECTRICAL TERMINALS
Doc.No. 01 - 42 19 SD029- EL

Prepared by Approved by
Rev. Date Remark Muzami Thahir Ir. Sardono Sarwito,
M.Sc.
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 2 of 21
TERMNINALS
I. INTRODUCTION
The lighting is media for illumination so you can feel comfort in activities both
inside and outside the room. Lighting including the use of both light sources such as
lamps and natural lighting which is obtained through the Windows, skylights or light
shelves during the day. Daylighting (using windows, skylights, or light shelves) is
sometimes used as a primary source of light during the day in the building. This can
save energy. lighting is a major component of energy consumption in the building.
The right lighting can improve the performance of tasks, improve the appearance of
the area, or have a positive psychological effect on the occupants.
II. OBJECTIVES
1. Determining the reflection factor from celling, wall and floor
2. Calculate the resulting light every lamp.
3. Calculate the lighting required in one room
4. Calculate amount of lamp required in one room
5. Determine amount of socket-outlet, depend on equipment and requirement
required in one room

III.REFERENCES
1. Sardono Sarwito Diktat “The Design of Ship’s Electrical Installation”

IV. LIST OF ABBREVATIONS


CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 3 of 21
TERMNINALS

-     p : Length of spa ce (m)


-     l : Brea dth of spa ce (m)
-     H : Height of working desk (m)
-     t : Height from floor to la mp (m)
-     k : Fa ctor
-     E : Intensit of illumina tion (lux)
-     Φ : Flux (lumen)
-     d : Diversity
-     f : Fa ctor la mp
-n : Amount of la mp

V. SYSTEM DESCRIPTION
The lighting is media for illumination so you can feel comfort in activities both
inside and outside the room. In the ship there are several kinds of lamp types that
will be used, depending on the function of the room. After selecting the type of
lamp that fits the room then it will get the number of lamp needed. For
requirement amount of socket-outlet depend on the equipment and requirement in
a space. After know amount of lamp and socket-outlet needed, so known amount
of power requirement for lightnings and socket-outlet.

VI. DESIGN REQUIREMENTS


No Key Equipment Reference Parameter Design
Sardono Sarwito Diktat “The
To get amount of
1 Type of Lamp Design of Ship’s Electrical
lamp
Installation”
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 4 of 21
TERMNINALS
Table 1.1. Design Requirements

VII. SUMMARY OF CALCULATION


POWER
NO LOCATION
Watt Kw
1 Main Deck 6100 6.1
2 Poop Deck 8082 8.082
3 Boat Deck 4245 4.245
4 Bridge Deck 9006 9.006
5 Navigation Deck 3241 3.241
6 Tween Deck 3024 3.024
7 Engine Platform 440 0.44
Total Power Required 34138 34.138

VIII. DETAIL OF CALCULATION


A. MAIN DECK
Room Dimension   Index
N Area
ROOM P L T H h Room
o
(m) (m) (m) (m) (m) A (m2) (k)
1 Oiler 1 4.7 2.4 3 0.7 2.3 11.28 0.691
2 Oiler 2 4.5 2.9 3 0.7 2.3 13.05 0.767
3 Oiler 3 4.5 2.5 3 0.7 2.3 11.25 0.699
4 Sea Man 4.2 3 3 0.7 2.3 12.60 0.761
5 Engine Foreman 3.5 3 3 0.7 2.3 10.50 0.702
6 Cadet 4.7 2.6 3 0.7 2.3 12.22 0.728
7 Steward 4.5 2.6 3 0.7 2.3 11.70 0.716
8 Chef 4.2 3 3 0.7 2.3 12.60 0.761
9 Laundry 3.6 2.1 3 0.8 2.2 7.56 0.603
10 Mess Room 3.75 3 3 0.77 2.23 11.25 0.747
11 Lavatory 4.3 3 3 0.7 2.3 12.90 0.768
12 Pantry 3.6 2.1 3 0.8 2.2 7.56 0.603
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 5 of 21
TERMNINALS
13 Safety Equipment Store 3.2 3 3 0.7 2.3 9.60 0.673
14 Mushola 3.5 2.6 3 0.7 2.3 9.10 0.649
15 AC Control Room 6.7 3 3 0.7 2.3 20.10 0.901
16 Paint Deck Storage 6.7 3 3 0.8 2.2 20.10 0.942
17 Steering Gear Room 6.6 4 3 0.8 2.2 26.40 1.132
18 Gangway Front 10 6 3   3 60.00 1.250
19 Gangway Left 5 2 3   2.5 10.00 0.571
20 Gangway Right 5 2 3   2.5 10.00 0.571
21 Gangway Back 4.5 3.5 3   2.5 15.75 0.788
22 Up to Poop Deck 5 1 3   2.5 5.00 0.333
Downstairs to
23 E/R   5 1 3   3.00 5.00 0.278

Armature Reflection Factor


Intensity
No index Σ type power rc rw rf
Luxs       (watt)      
1 100 9 1 FL 20 0.75 0.5 0.1
2 100 9 1 FL 20 0.75 0.5 0.1
3 100 9 1 FL 20 0.75 0.5 0.1
4 100 9 1 FL 20 0.75 0.5 0.1
5 100 9 1 FL 20 0.75 0.5 0.1
6 100 9 1 FL 20 0.75 0.5 0.1
7 100 9 1 FL 20 0.75 0.5 0.1
8 100 9 1 FL 20 0.75 0.5 0.1
9 200 4B 2 FL 15 0.75 0.5 0.1
10 200 10B 1 FL 20 0.75 0.5 0.1
11 100 4 1 FL 15 0.75 0.5 0.1
12 200 10B 2 FL 20 0.75 0.5 0.1
13 60 13 1 FL 20 0.75 0.5 0.1
14 100 10B 1 FL 20 0.75 0.5 0.1
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 6 of 21
TERMNINALS
15 60 13 1 FL 20 0.75 0.5 0.1
16 60 13 1 FL 20 0.75 0.5 0.1
17 60 13 1 FL 20 0.75 0.5 0.1
18 35 9 1 FL 20 0.75 0.5 0.1
19 35 9 1 FL 20 0.75 0.5 0.1
20 35 9 1 FL 20 0.75 0.5 0.1
21 35 9 1 FL 20 0.75 0.5 0.1
22 40 6 1 FL 20 0.75 0.5 0.1
23 40 6 1 FL 20 0.75 0.5 0.1

Range of Efficiency Light


Diversity Light
No efficiency Lux
k1 Eff 1 k2 Eff 2
(d) Φ (lumen)
0.
1 6 0.262 0.8 0.314 0.286 0.7 3950 1750
0.
2 6 0.262 0.8 0.314 0.305 0.7 4274 1750
0.
3 6 0.262 0.8 0.314 0.288 0.7 3911 1750
0.
4 6 0.262 0.8 0.314 0.304 0.7 4147 1750
0.
5 6 0.262 0.8 0.314 0.289 0.7 3638 1750
0.
6 6 0.262 0.8 0.314 0.295 0.7 4139 1750
0.
7 6 0.262 0.8 0.314 0.292 0.7 4003 1750
0.
8 6 0.262 0.8 0.314 0.304 0.7 4147 1750
9

0.
6 0.285 0.8 0.322 0.286 0.7 5295 2625
10 0. 0.329 0.8 0.407 0.386 0.7 5822 1750
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 7 of 21
TERMNINALS
6
0.
11 6 0.285 0.8 0.368 0.355 0.7 3635 1312.5
0.
12 6 0.329 0.8 0.407 0.330 0.7 4580 3500
0.
13 6 0.329 0.8 0.407 0.358 0.7 1611 1750
0.
14 6 0.329 0.8 0.407 0.348 0.7 2615 1750
0.
15 8 0.407 1 0.445 0.426 0.7 2830 1750
0.
16 8 0.407 1 0.445 0.434 0.7 2779 1750
17 1 0.445 1.25 0.489 0.468 0.7 3383 1750
18 1 0.35 1.25 0.379 0.379 0.7 5541 1750
0.
19 6 0.262     0.250 0.7 1403 1750
0.
20 6 0.262     0.250 0.7 1403 1750
0.
21 6 0.262 0.8 0.314 0.311 0.7 1774 1750
0.
22 6 0.15     0.083 0.7 2400 1750
0.
23 6 0.15     0.069 0.7 2880 1750

Σ armature Stop Contact (A)


Power Armature
No n N 2 4 6 10
    (Watt) n1 n2 n3 n4
1 2.26 2 40 1      
2 2.44 2 40 1      
3 2.23 2 40 1      
4 2.37 2 40 1      
5 2.08 2 40 1      
6 2.37 2 40 1      
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 8 of 21
TERMNINALS
7 2.29 2 40 1      
8 2.37 2 40 1      
9 2.02 2 60   2    
10 3.33 3 60 1      
11 2.77 4 60        
12 1.31 1 40 1      
13 0.92 1 20        
14 1.49 1 20        
15 1.62 2 40 1      
16 1.59 1 20        
17 1.93 2 40        
18 3.17 3 60        
19 0.80 1 20        
20 0.80 1 20        
21 1.01 1 20        
22 1.37 1 20        
23 1.65 2 40        
Quantity Total 40 - 11 2 0 0
- 820 3872 1408 0 0
Power Total
6100

B. POOP DECK
Room Dimension   Index
Area
No ROOM P L T H h Room
(m) (m) (m) (m) (m) A (m2) (k)
1 Quarter Master 1 3.4 3.2 3.0 0.7 2.3 10.9 0.717
2 Quarter Master 2 3.2 3.2 3.0 0.7 2.3 10.2 0.696
3 Quarter Master 3 3.2 3.2 3.0 0.7 2.3 10.2 0.696
4 Boastwain 3.2 3.2 3.0 0.7 2.3 10.2 0.696
5 Clinic 4.7 3.1 3.0 0.7 2.3 14.6 0.812
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 9 of 21
TERMNINALS
6 Library 3.1 3 3.0 0.7 2.3 9.3 0.663
7 Lavatory 3.1 3.1 3.0 0.7 2.3 9.6 0.674
8 Mess Room 5.3 2.7 3.0 0.7 2.3 14.3 0.778
Emergency Pump
9 Room 2.7 1.8 3.0 0.7 2.3 4.9 0.470
10 AHU 2.5 1.5 3.0 0.7 2.3 3.8 0.408
11 Galley 3.1 3 3.0 0.7 2.3 9.3 0.663
12 Mess Room 6 3 3.0 0.7 2.3 18.0 0.870
13 Cold Storage 2.6 1.7 3.0 0.7 2.3 4.4 0.447
14 Dry Storage 2.6 1.7 3.0 0.7 2.3 4.4 0.447
15 Foam Room 2.2 1.5 3.0 0.7 2.3 3.3 0.388
16 CO2 Room 2 1.7 3.0   3.0 3.4 0.306
Emergency
17 Generator 3 2.7 3.0   3.0 8.1 0.474
18 Gangway PS 14.5 1.5 3.0   3.0 21.8 0.453
19 Gangway SB 14.5 1.5 3.0   3.0 21.8 0.453
20 Gangway Back 4 2 3.0   3.0 8.0 0.444
21 Gangway Outer PS 18 2 3.0   3.0 36.0 0.600
22 Gangway Outer SB 18 2 3.0   3.0 36.0 0.600
23 Gangway Outer Back 11 5 3.0   3.0 55.0 1.146
24 Upstairs 5 1 3.0   3.0 5.0 0.278
25 Downstairs 5 1 3.0   3.0 5.0 0.278

Armature Reflection Factor


Intensity
No index Σ type power rc rw rf
Luxs       (watt)      
1 100 9 1 FL 20 0.75 0.5 0.1
2 100 9 1 FL 20 0.75 0.5 0.1
3

100 9 1 FL 20 0.75 0.5 0.1


4 100 9 1 FL 20 0.75 0.5 0.1
5 200 10B 2 FL 20 0.75 0.5 0.1
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 10 of 21
TERMNINALS
6 200 10B 1 FL 20 0.75 0.5 0.1
7

100 4 1 FL 20 0.75 0.5 0.1


8

60 10B 1 FL 20 0.75 0.5 0.1


9

200 13 1 FL 20 0.75 0.5 0.1


10
60 13 1 FL 10 0.75 0.5 0.1
11 200 10B 2 FL 20 0.75 0.5 0.1
12 200 10B 1 FL 20 0.75 0.5 0.1
13 60 13 1 FL 15 0.75 0.5 0.1
14 60 13 1 FL 15 0.75 0.5 0.1
15 200 13 1 FL 20 0.75 0.5 0.1
16 40 13 1 FL 15 0.75 0.5 0.1
17 40 13 1 FL 15 0.75 0.5 0.1
18 35 9 1 FL 20 0.75 0.5 0.1
19 35 9 1 FL 20 0.75 0.5 0.1
20 35 9 1 FL 20 0.75 0.5 0.1
21 30 6 2 FL 20 0.75 0.5 0.1
22 30 6 2 FL 20 0.75 0.5 0.1
23 30 6 2 FL 20 0.75 0.5 0.1
24 40 6 1 FL 20 0.75 0.5 0.1
25 40 6 1 FL 20 0.75 0.5 0.1

Range of Efficiency Light


No efficiency Diversity Light
Lux
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 11 of 21
TERMNINALS
k1 Eff 1 k2 Eff 2 (d) Φ (lumen)
0. 3721.5
1 6 0.262 0.8 0.314 0.292 0.7 6 2500
0. 3569.5
2 6 0.262 0.8 0.314 0.287 0.7 7 2500
0. 3569.5
3 6 0.262 0.8 0.314 0.287 0.7 7 2500
0. 3569.5
4 6 0.262 0.8 0.314 0.287 0.7 7 2500
0. 7119.3
5 8 0.407 1 0.445 0.409 0.7 2 5000
0. 5261.4
6 6 0.329 0.8 0.407 0.354 0.7 1 2500
0. 3044.2
7 6 0.285 0.8 0.368 0.316 0.7 8 2500
0. 2155.6
8 6 0.329 0.8 0.407 0.398 0.7 1 2500
0. 3775.0
9 6 0.329     0.257 0.7 8 2500
0. 683.89
10 6 0.329     0.329 0.7 1 1250
0. 5526.7
11 6 0.329 0.8 0.353 0.337 0.7 7 5000
0. 10361.
12 8 0.329 1 0.382 0.347 0.7 7 2500
0. 1082.1
13 6 0.329     0.245 0.7 9 1875
0. 1082.1
14 6 0.329     0.245 0.7 9 1875
0. 3103.9
15 6 0.329     0.213 0.7 5 2500
0. 413.37
16 6 0.329     0.329 0.7 4 1875
0. 984.80
17 6 0.329     0.329 0.7 2 1875
0. 2905.5
18 6 0.262     0.262 0.7 3 2500
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 12 of 21
TERMNINALS
19 0. 0.262     0.262 0.7 2905.5 2500
6 3
0.
20 6 0.262     0.262 0.7 1068.7 2500
0.
21 6 0.15     0.150 0.7 7200 5000
0.
22 6 0.15     0.150 0.7 7200 5000
23 1 0.22 1.25 0.25 0.220 0.7 7500 5000
0. 1333.3
24 6 0.15     0.150 0.7 3 2500
0. 1333.3
25 6 0.15     0.150 0.7 3 2500

Σ armature Stop Contact (A)


Power Armature
No n N 2 4 6 10
    (Watt) n1 n2 n3 n4
1 1.49 1 20 1      
2 1.43 1 20 1      
3 1.43 1 20 1      
4 1.43 1 20 1      
5 1.42 1 40 1      
6 2.10 2 40 1      
7 1.22 1 20        
8 0.86 1 20 1      
9 1.51 1 20        
10 0.55 1 10        
11 1.11 1 40       2
12 4.14 4 80        
13 0.58 1 15   2    
14 0.58 1 15        
15 1.24 1 20        
16 0.22 1 15        
17 0.53 1 15        
18 1.16 2 40        
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 13 of 21
TERMNINALS
19 1.16 2 40        
20

0.43 1 20        
21

1.44 1 40        
22

1.44 1 40        
23
1.50 1 40        
24 0.53 1 20        
25 0.53 1 20        
Quantity Total 28 - 7 2 0 2
- 690 2464 1408 0 3520
Power Total
8082

C. BOAT DECK
Index
Area
Room Dimension   Room
No ROOM
P L T H h
(m) (m) (m) (m) (m) A (m2) (k)
1 Radio Operator Room 3.2 3 3 0.7 2.3 9.60 0.673
2 Officer Asst 1 3.2 3 3 0.7 2.3 9.60 0.673
3 Officer Asst 2 3.2 3 3 0.7 2.3 9.60 0.673
4 2nd Engineer 3.2 3 3 0.7 2.3 9.60 0.673
5 3rd Engineer 3.2 3 3 0.7 2.3 9.60 0.673
6 Meeting Room 4.2 3 3 0.7 2.3 12.60 0.761
7 Mess Room 4 3 3 0.7 2.3 12.00 0.745
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 14 of 21
TERMNINALS
8 Lavatory 3 1.2 3 0.7 2.3 3.60 0.373
10 Multimedia Room   2.8 1.8 3 0.4 2.6 5.04 0.421
11 Pantry 2.25 5.5 3 0.7 2.3 12.38 0.694
12 Gangway PS 7.8 1.2 3   3 9.36 0.347
13 Gangway SB 7.8 1.2 3   3 9.36 0.347
14 Gangway Back 5.3 4.2 3   3 22.26 0.781
15 Gangway Outer PS 11 2 3   3 22.00 0.564
16 Gangway Outer SB 11 2 3   3 22.00 0.564
17 Gangway Outer Back 10.5 7.5 3   3 78.75 1.458
18 Upstairs 5 1 3   3 5.00 0.278
19 Downstairs 5 1 3   3 5.00 0.278

Armature Reflection Factor


Intensity
No index Σ type power rc rw rf
Luxs       (watt)      
1 100 9B 1 FL 20 0.75 0.5 0.1
2 100 9B 1 FL 20 0.75 0.5 0.1
3 100 9B 1 FL 20 0.75 0.5 0.1
4 100 9B 1 FL 20 0.75 0.5 0.1
5 100 9B 1 FL 20 0.75 0.5 0.1
6 200 10B 1 FL 20 0.75 0.5 0.1
7 200 10B 1 FL 20 0.75 0.5 0.1
8 100 4 2 FL 20 0.75 0.5 0.1
10 200 10B 1 FL 15 0.75 0.5 0.1
11 200 10B 2 FL 20 0.75 0.5 0.1
12 35 9 1 FL 20 0.75 0.5 0.1
13 35 9 1 FL 20 0.75 0.5 0.1
14 35 9 1 FL 20 0.75 0.5 0.1
15 30 6 1 FL 15 0.75 0.5 0.1
16 30 6 1 FL 15 0.75 0.5 0.1
17 30 6 1 FL 15 0.75 0.5 0.1
18 40 6 1 FL 20 0.75 0.5 0.1
19 40 6 1 FL 20 0.75 0.5 0.1
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 15 of 21
TERMNINALS

Range of Efficiency Light


Diversity Light
No efficiency Lux
k1 Eff 1 k2 Eff 2
(d) Φ (lumen)
0. 3415.9
1 6 0.262 0.80 0.314 0.281 0.7 4 2500
0. 3415.9
2 6 0.262 0.80 0.314 0.281 0.7 4 2500
0. 3415.9
3 6 0.262 0.80 0.314 0.281 0.7 4 2500
0. 3415.9
4 6 0.262 0.80 0.314 0.281 0.7 4 2500
0. 3415.9
5 6 0.262 0.80 0.314 0.281 0.7 4 2500
0. 6306.8
6 8 0.407 1.00 0.445 0.400 0.7 6 2500
0. 6222.7
7 6 0.329 0.80 0.407 0.386 0.7 2 2500
0. 2033.6
8 6 0.285     0.177 0.7 8 5000
0. 4362.3
10 6 0.329     0.231 0.7 1 1875
0. 6766.7
11 6 0.329 0.80 0.407 0.366 0.7 8 5000
0. 1250.3
12 6 0.262     0.262 0.7 8 2500
0. 1250.3
13 6 0.262     0.262 0.7 8 2500
0. 2973.6
14 6 0.262     0.262 0.7 6 2500
0.
15 6 0.15     0.150 0.7 4400 1875
0.
16 6 0.15     0.150 0.7 4400 1875
17 1 0.22 1.25 0.25 0.275 0.7 8590.9 1875
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 16 of 21
TERMNINALS
1
0. 1333.3
18 6 0.15     0.150 0.7 3 2500
0. 1333.3
19 6 0.15     0.150 0.7 3 2500

Σ armature Stop Contact (A)


Power Armature
No n N 2 4 6 10
    (Watt) n1 n2 n3 n4
1 1.95 2 40 1      
2 1.95 2 40 1      
3 1.95 2 40 1      
4 1.95 2 40 1      
5 1.95 2 40 1      
6 3.60 4 80 1      
7 3.56 3 60 1      
8 0.58 2 80        
10 3.32 3 45 2      
11 1.93 2 80 1      
12 0.71 1 20        
13 0.71 1 20        
14 1.70 2 40        
15 3.35 1 15        
16 3.35 1 15        
17 6.55 2 30        
18 0.76 1 20        
19 0.76 1 20        

Quantity Total 34 - 10 0 0 0
- 725 3520 0 0 0
Power Total
4245
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 17 of 21
TERMNINALS

D. BRIDGE DECK
Index
Area
Room Dimension   Room
No ROOM
P L T H h
(m) (m) (m) (m) (m) A (m2) (k)
1 Captain Room 3.1 3.25 2.5 0.7 1.8 10.08 0.881
2 Chief Eng. Room 3.1 3.25 2.5 0.7 1.8 10.08 0.881
3 Chief Officer Room 3.1 3.25 2.5 0.7 1.8 10.08 0.881
4 Captain Office 3.2 3.1 2.5 0.7 1.8 9.92 0.875
5 Chief Eng. Office 3.2 3.1 2.5 0.7 1.8 9.92 0.875
6 Chief Officer Office 3.2 3.1 2.5 0.7 1.8 9.92 0.875
7 Chief Off. Day Room 3.2 3.1 2.5 0.7 1.8 9.92 0.875
8 Meeting Room 3.75 3 2.5 0.7 1.8 11.25 0.926
9 Toilet Capten 1.6 1.1 2.5 0.4 2.1 1.76 0.310
10 Toilet Chief Engineer 1.6 1.1 2.5 0.4 2.1 1.76 0.310
11 Toilet Chief Officer 1.6 1.1 2.5 0.4 2.1 1.76 0.310
12 Mess Room 3 3 2.5 0.4 2.1 9.00 0.714
13 Pantry 3.3 3 2.5 0.7 1.8 9.90 0.873
14 Gangway PS 4.5 1.2 2.5   2.5 5.40 0.379
15 Gangway SB 4.5 1.2 2.5   2.5 5.40 0.379
16 Gangway Back 5 3 2.5   2.5 15.00 0.750
17 Gangway Outer PS 9 2.3 2.5   2.5 20.70 0.733
18 Gangway Outer SB 9 2.3 2.5   2.5 20.70 0.733
19 Gangway Outer Back 12 5 2.5   2.5 60.00 1.412

Armature Reflection Factor


Intensity
No index Σ type power rc rw rf
Luxs       (watt)      
1 100 9B 2 FL 20 0.75 0.5 0.1
2 100 9B 2 FL 20 0.75 0.5 0.1
3 100 9B 2 FL 20 0.75 0.5 0.1
4 100 9B 2 FL 20 0.75 0.5 0.1
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 18 of 21
TERMNINALS
5 100 9B 2 FL 20 0.75 0.5 0.1
6 100 9B 2 FL 20 0.75 0.5 0.1
7 100 9B 2 FL 20 0.75 0.5 0.1
8 200 10B 2 FL 20 0.75 0.5 0.1
9 100 4 1 FL 15 0.75 0.5 0.1
10 100 4 1 FL 15 0.75 0.5 0.1
11 100 4 1 FL 15 0.75 0.5 0.1
12 200 10B 1 FL 15 0.75 0.5 0.1
13 200 10B 2 FL 20 0.75 0.5 0.1
14 35 9 1 FL 20 0.75 0.5 0.1
15 35 9 1 FL 20 0.75 0.5 0.1
16 35 9 1 FL 20 0.75 0.5 0.1
17 30 6 2 FL 15 0.75 0.5 0.1
18 30 6 2 FL 15 0.75 0.5 0.1
19 30 6 2 FL 15 0.75 0.5 0.1

Range of Efficiency Light


Diversity Light
No efficiency Lux
k1 Eff 1 k2 Eff 2
(d) Φ (lumen)
0. 3065.4
1 8 0.314 1 0.35 0.329 0.7 6 5000
0. 3065.4
2 8 0.314 1 0.35 0.329 0.7 6 5000
0. 3065.4
3 8 0.314 1 0.35 0.329 0.7 6 5000
0. 3029.3
4 8 0.314 1 0.35 0.327 0.7 7 5000
0. 3029.3
5 8 0.314 1 0.35 0.327 0.7 7 5000
0. 3029.3
6 8 0.314 1 0.35 0.327 0.7 7 5000
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 19 of 21
TERMNINALS
7 0. 0.314 1 0.35 0.327 0.7 3029.3 5000
8 7
8
0. 6683.1
8 0.314 1 0.35 0.337 0.7 7 5000
0. 1193.6
9 6 0.285     0.147 0.7 8 1875
0. 1193.6
10 6 0.285     0.147 0.7 8 1875
0. 1193.6
11 6 0.285     0.147 0.7 8 1875
0. 4818.3
12 6 0.329 0.8 0.407 0.374 0.7 6 1875
0. 4546.7
13 6 0.329 0.8 0.407 0.435 0.7 5 5000
0. 1142.1
14 6 0.262     0.165 0.7 8 2500
0. 1142.1
15 6 0.262     0.165 0.7 8 2500
0.
16 8 0.262 0.8 0.314 #DIV/0! 0.7 #DIV/0! 2500
0. 12311.
17 6 0.15 0.8   0.050 0.7 1 3750
0. 12311.
18 6 0.15 0.8   0.050 0.7 1 3750
6681.2
19 1 0.22 1.25 0.25 0.269 0.7 2 3750

Σ armature Stop Contact (A)


Power Armature
No n N 2 4 6 10
    (Watt) n1 n2 n3 n4
1 1.63 2 80 2      
2 1.63 2 80 2      
3 1.63 2 80 2      
4 1.65 2 80 2      
5 1.65 2 80 2      
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 20 of 21
TERMNINALS
6 1.65 2 80 2      
7 1.65 2 80 2      
8 0.75 1 40 2      
9 1.57 1 15        
10 1.57 1 15        
11 1.57 1 15        
12 0.39 1 15 1      
13 1.10 1 40 1     1
14 2.19 2 40        
15 2.19 2 40        
16 #DIV/0! 2 40        
17 0.30 1 30        
18 0.30 1 30        
19 0.56 1 30        
Quantity Total 29 - 18 0 0 1
- 910 6336 0 0 1760
Power Total
9006

E. NAVIGATION DECK
Index
Area
Room Dimension   Room
No ROOM
P L T H h
(m) (m) (m) (m) (m) A (m2) (k)
1 Battery Room 3 2.2 2.5 0.7 1.8 6.60 0.705
2 Document Room 2.3 2.3 2.5 1.5 1 5.29 1.150
3 Radio Chart Room 3 2.2 2.5 0.7 1.8 6.60 0.705
4 Cargo Control Room 2.8 1.1 2.5 0.7 1.8 3.08 0.439
5 Wheel House 11 3.2 2.5 0.7 1.8 35.20 1.377
6

Toilet 2.25 2 2.5 0.4 2.1 4.50 0.504


CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 21 of 21
TERMNINALS
7 Gangway PS 4.7 2.2 2.5   2.5 10.34 0.599
8

Gangway SB 4.7 2.2 2.5   2.5 10.34 0.599


10 ESEP Room 3 2.3 2.5   2.5 6.90 0.521
Gangway Outer
11 Back   16.9 2.25 2.5   2.5 38.03 0.794
12 Downstairs 5 1 2.5   2.5 5.00 0.333

Armature Reflection Factor


Intensity
No index Σ type power rc rw rf
Luxs       (watt)      
1 40 4 1 FL 15 0.75 0.5 0.1
2 40 4 1 FL 15 0.75 0.5 0.1
3 40 4 1 FL 15 0.75 0.5 0.1
4 150 10B 2 FL 20 0.75 0.5 0.1
5 200 10B 2 FL 20 0.75 0.5 0.1
6 100 4 1 FL 15 0.75 0.5 0.1
7 35 6 1 FL 15 0.75 0.5 0.1
8 35 6 1 FL 15 0.75 0.5 0.1
10 30 4 2 FL 15 0.75 0.5 0.1
11 30 4B 2 FL 15 0.75 0.5 0.1
12 35 6 1 FL 15 0.75 0.5 0.1

Light
Range of Efficiency efficiency Diversity Light
Lux
No
k1 Eff 1 k2 Eff 2
(d) Φ (lumen)
803.33
1 0.6 0.285 0.8 0.368 0.329 0.7 9 1875
506.94
2 1 0.406 1.25 0.425 0.417 0.7 8 1875
803.33
3 0.6 0.285 0.8 0.368 0.329 0.7 9 1875
4 0.6 0.329     0.241 0.7 1920.3 5000
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 22 of 21
TERMNINALS
6
15005.
5 1.25 0.489 1.5 0.45 0.469 0.7 4 5000
1730.5
6 0.6 0.295 0.8 0.368 0.260 0.7 5 1875
2412.6
7 0.6 0.15     0.150 0.7 7 1875
2412.6
8 0.6 0.15     0.150 0.7 7 1875
726.31
10 0.6 0.285     0.285 0.7 6 3750
3554.4
11 0.6 0.285 0.8 0.322 0.321 0.7 3 3750
1166.6
12 0.6 0.15     0.150 0.7 7 1875

Σ armature Stop Contact (A)


Power Armature
No n N 2 4 6 10
    (Watt) n1 n2 n3 n4
1 0.61 1 15        
2 0.39 1 15        
3 0.61 1 15 1 2    
4 0.55 1 40 1      
5 4.29 4 160 1      
6 1.32 1 15        
7 1.84 2 30        
8 1.84 2 30        
10 0.28 1 30 1      
11 1.35 2 60        
12 0.89 1 15        

Quantity Total 17 - 4 2 0 0
- 425 1408 1408 0 0
Power Total
3241
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 23 of 21
TERMNINALS

F. TWEEN DECK
Room Dimension   Index
Area
No ROOM P L T H h Room
(m) (m) (m) (m) (m) A (m2) (k)
1 Engine Control Room 5.8 2 2.5 0.7 1.80 11.60 0.826
2 Gangway PS 13 4.5 3.5   3.50 58.50 0.955
3 Gangway SB 13 4.5 3.5   3.50 58.50 0.955
4 Upstairs 5 1 3.5   3.50 5.00 0.238
5 Upstairs 5 1 3.8   3.80 5.00 0.525
6 Downstairs 5 1 3.7   3.70 5.00 0.525

Armature Reflection Factor


Intensity
No index Σ type power rc rw rf
Luxs       (watt)      
1 200 14 2 FL 20 0.75 0.5 0.1
2 200 14 2 FL 20 0.75 0.5 0.1
3 200 14 2 FL 20 0.75 0.5 0.1
4 200 14 2 FL 20 0.75 0.5 0.1
5 40 13 1 FL 20 0.75 0.5 0.1
6 40 13 1 FL 20 0.75 0.5 0.1

Range of Efficiency Light


Diversity Light
No k efficiency Lux
k1 Eff 1 Eff 2
2 (d) Φ (lumen)
4387.1
1 0.8 0.522 1 0.574 0.529 0.75 7 5000
20806.
2 0.8 0.522 1 0.574 0.562 0.75 4 5000
20806.
3 0.8 0.522 1 0.574 0.562 0.75 4 5000
7659.5
4 0.6 0.329     0.131 0.75 7 5000
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 24 of 21
TERMNINALS
5 0.6 0.329     0.329 0.75 607.90 2500
3
607.90
6 0.6 0.329     0.329 0.75 3 2500

Σ armature Stop Contact (A)


Power Armature
No n N 2 4 6 10
    (Watt) n1 n2 n3 n4
1 1.17 1 40 1      
2 5.55 5 200     2  
3 5.55 5 200        
4 2.04 2 80        
5 0.32 1 20        
6 0.32 1 20        
Quantity Total 15 - 1 0 2 0
- 560 352 0 2112 0
Power Total
3024

G. ENGINE ROOM PLATFORM


No ROOM Room Dimension   Area Index
P L T H h Room
(m) (m) (m) (m) (m) A (m2) (k)
1

Space Room 1 9.3 3.6 4.3 1.6 2.7 33.48 0.96


2
Space Room 2 12.5 4 4.3 1.7 2.6 50.00 1.17
3
Space Room 3 12.5 4 4.3 1.7 2.6 50.00 1.17
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 25 of 21
TERMNINALS

Armature Reflection Factor


Intensity
No index Σ type power rc rw rf
Luxs       (watt)      
1 200 14 2 FL 20 0.75 0.5 0.1
2 200 14 2 FL 20 0.75 0.5 0.1
3 200 14 2 FL 20 0.75 0.5 0.1

Range of Efficiency Light


Diversity Light
No efficiency Lux
k1 Eff 1 k2 Eff 2
(d) Φ (lumen)
0.
1 8 0.522 1 0.574 0.564 0.75 11874 5000
16435.
2 1 0.574 1.25 0.626 0.608 0.75 9 5000
16435.
3 1 0.574 1.25 0.626 0.608 0.75 9 5000

Σ armature Stop Contact (A)


Power Armature
No n N 2 4 6 10
    (Watt) n1 n2 n3 n4
1 3.1664 3 120        
2 4.3829 4 160        
3 4.3829 4 160        
Quantity Total 11 - 0 0 0 0
- 440 0 0 0 0
Power Total
440

CALCULATION POWER REQUIRED


POWER
NO LOCATION
Watt Kw
1 Main Deck 6100 6.1
CALCULATION & Doc. No. 01 - 42 19 SD029- EL
SPECS. OF Rev. No. 01
LIGTHINGS &
ELECTRICAL Page. 26 of 21
TERMNINALS
2 Poop Deck 8082 8.082
3 Boat Deck 4245 4.245
4 Bridge Deck 9006 9.006
5 Navigation Deck 3241 3.241
6 Tween Deck 3024 3.024
7 Engine Platform 440 0.44
34.13
Total Power Required 34138 8

IX. SPECIFICATION OF EQUIPMENTS


See attachment of Doc. No. 01 - 42 19 SD029 – EL
X. DRAWING OF SYSTEM
See attachment of Doc. No. 01 - 42 19 SD029 – EL