Distribution Boards Schedules-Hub 4
Distribution Boards Schedules-Hub 4
Distribution Board Ref.: SMDB-1-EV2(TYPICAL 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 25 mm² XLPE/LS0H/SWA(FR)
CABLE EARTHING 1C 16 mm² LS0H
Supplied From: MDB Volts: 400/230
L1/1 9.53
L3/1 9.53
L1/2 3.62
L3/2 3.62
L1/3
L3/3
L1/4
L2/4 SPACE
L3/4
Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00
Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 13.15 13.15 13.15
A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 3.03 3.03 3.03
D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel
Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 11.35
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB
Distribution Board Ref.: DB-LIGHTINGS TYPE 3(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 10 mm² XLPE/LS0H/SWA
CABLE EARTHING 1C 10 mm² LS0H
Supplied From: MDB Volts: 400/230
L1/1 LIGHTING CIRCUIT PROVISION FOR OUTDOOR LV YARD/MDB ROOM Radial B B 6 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 1.57
L2/1 LIGHTINGS AT CHILLED WATER PUMP ROOM Radial B B 11 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 2.30
L3/1 LIGHTINGS AT ELECTRICAL ROOM Radial B B 3 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 0.59
L1/2 LIGHTINGS AT ICT ROOM Radial B B 2 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 0.33
L2/2 LIGHTINGS AT BMS SECURITY ROOM Radial B B 3 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 0.59
L3/2 EXTERNAL LIGHTINGS Radial B B 5 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 2.17
L1/3 LIGHTINGS AT PUMP ROOM Radial B B 4 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 1.03
L2/4 SPACE
L3/4 SPACE
L1/5 SPACE
L2/5 SPACE
L3/5 SPACE
L1/6 SPACE
L2/6 SPACE
L3/6 SPACE
Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00
Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 2.93 2.89 2.76
A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.68 0.67 0.64
D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel
Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 2.50
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB
Distribution Board Ref.: DB-POWER TYPE 4(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 10 mm² XLPE/LS0H/SWA
CABLE EARTHING 1C 10 mm² LS0H
Supplied From: MDB Volts: 400/230
L1/1 POWER SOCKETS OUTLET FOR OUTDOOR LV YARD Radial B B 2 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 1.57
L3/1 POWER SOCKETS OUTLET AT ELECTRICAL ROOM Radial B B 2 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 1.57
L3/2 POWER SOCKETS OUTLET AT PUMP ROOM Radial B B 2 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 1.57
L2/3 POWER FOR LIGHTING CONTROL PANEL(LCP) Radial B B 1 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 8.00
L3/3 POWER SOCKETS OUTLET AT CHILLLED WATER PUMP ROOM Radial B B 3 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 2.35
L1/4 POWER SOCKETS OUTLET AT BMS ROOM Radial B B 3 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 2.35
L1/2 POWER SOCKETS OUTLET AT ICT ROOM Radial B B 3 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 2.35
L2/5 SPACE
L3/5 SPACE
L1/6 SPACE
L2/6 SPACE
L3/6 SPACE
Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00
Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 7.04 8.00 7.83
A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 1.62 1.84 1.80
D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel
Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 6.58
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB
Distribution Board Ref.: ESMDB-1 TYPE 4(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 50 mm² XLPE/LS0H/SWA(FR)
CABLE EARTHING 1C 25 mm² LS0H
Supplied From: GEN Volts: 400/230
L1/1 9.71
L3/1 9.71
L1/2 16.39
L3/2 16.39
L1/3 6.50
L3/3 6.50
L1/4 27.54
L3/4 27.54
L1/5
L3/5
L1/6
L3/6
Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00
Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 60.13 60.13 60.13
A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 13.83 13.83 13.83
D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel
Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 51.87
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB
Distribution Board Ref.: DB-HVAC TYPE 4(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 16 mm² XLPE/LS0H/SWA
CABLE EARTHING 1C 16 mm² LS0H
Supplied From: ESMDB-1 Volts: 400/230
L1/1 POWER FOR INDOOR UNIT IN ELECTRICAL ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 2P 8.15
L2/1 POWER FOR INDOOR UNIT IN ICT ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 2P 8.91
L3/1 POWER FOR INDOOR UNIT IN PUMP ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 2P 8.15
L1/2 POWER FOR INDOOR UNIT IN CHILLED WATER PUMP ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 2P 14.13
L1/4 SPACE
L2/4 SPACE
L3/4 SPACE
L1/5 SPACE
L2/5 SPACE
L3/5 SPACE
L1/6 SPACE
L2/6 SPACE
L3/6 SPACE
Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00
Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 22.28 8.91 8.15
A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 5.13 2.05 1.88
D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel
Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 11.31
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB
Distribution Board Ref.: DB-ICT TYPE 4(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 10 mm² XLPE/LS0H/SWA(FR)
CABLE EARTHING 1C 10 mm² LS0H
Supplied From: ESMDB-1 Volts: 400/230
L1/1 POWER FOR FACP PANEL Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 3.00
L2/1 POWER FOR DDC PANEL Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 10.00
L3/1 POWER FOR NETWORK EQUIPMENT AT ICT ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 4.35
L1/2 POWER FOR NETWORK EQUIPMENT AT ICT ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 4.35
L3/2 POWER FOR SECURITY SYSTEM (IBMS) Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 2.17
L1/3 POWER PROVISION FOR WAP UNITS Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 1.30
L3/3 POWER FOR PANIC DOORS Radial F B 5 3C 2x4 1x4 MCB 20 A 1P+N 3.91
L1/4 SPACE
L2/4 SPACE
L3/4 SPACE
L1/5 SPACE
L2/5 SPACE
L3/5 SPACE
L1/6 SPACE
L2/6 SPACE
L3/6 SPACE
Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00
Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 8.65 10.00 10.43
A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 1.99 2.30 2.40
D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel
Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 6.70
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB
Distribution Board Ref.: MCC-CWP-EV1 Location: U-HUB TYPE 4 FEEDER PHASE 4C 95 mm² XLPE/LS0H/SWA(FR)
CABLE EARTHING 1C 50 mm² LS0H
Supplied From: MDB Volts: 400/230
L1/1 29.89
L3/1 29.89
L1/2 29.89
L3/2 29.89
L1/3 29.89
L3/3 29.89
L1/4 29.89
L3/4 29.89
L1/5
L3/5
L1/6
L3/6
L1/7
L2/7 SPACE
L3/7
L1/8
L2/8 SPACE
L3/8
Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00
Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 29.89 29.89 29.89
A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 20.63 20.63 20.63
D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel
Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 77.34