RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: SMDB-1-EV2(TYPICAL 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 25 mm² XLPE/LS0H/SWA(FR)
CABLE EARTHING 1C 16 mm² LS0H
Supplied From: MDB Volts: 400/230

No. of 3P Ways: 4 Phase: 3 CABLE


LENGTH 0
Incoming Device Rating: 80AT/125AF IP Rating: IP42 (M) % Cummulative VD,VD2

Short Circuit Level, S.C. (KA): 25 Load Spare Capacity(%): 25

Form Type: Form-2

Tabulated Voltage Cummulative,


Protective Length,Lh Length, Lb LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m m mV/m/A % % Phase A Phase B Phase C

L1/1 9.53

L2/1 DB-POWER Radial A E 1 4C 10 10 MCCB 40 3 11 9.53

L3/1 9.53

L1/2 3.62

L2/2 DB-LIGHTING Radial A E 1 4C 10 10 MCCB 40 3 14 3.62

L3/2 3.62

L1/3

L2/3 SPARE MCCB 40 3

L3/3

L1/4

L2/4 SPACE

L3/4

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 13.15 13.15 13.15

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 3.03 3.03 3.03

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 9.08

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 11.35
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: DB-LIGHTINGS TYPE 3(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 10 mm² XLPE/LS0H/SWA
CABLE EARTHING 1C 10 mm² LS0H
Supplied From: MDB Volts: 400/230

No. of SP Ways: 18 Phase: 3 CABLE


LENGTH 14
Incoming Device Rating: 40AT/125AF IP Rating: IP42 (M) % Cummulative VD,VD2

Short Circuit Level, S.C. (KA): 12.5 Load Spare Capacity(%): 25

Form Type: Form-1

No. of Tabulated Voltage Cummulative,


Length,Lh Length, Lb LOAD CURRENT,IL(Amps)
Circuit Cable Installation Elements Line Cable CPC Cable Protective Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of Cores Poles
Type Type Method (Normal + Size(mm²) Size(mm²) Device Type Device Rating
Emergency) m m mV/m/A % % Phase A Phase B Phase C

L1/1 LIGHTING CIRCUIT PROVISION FOR OUTDOOR LV YARD/MDB ROOM Radial B B 6 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 1.57

L2/1 LIGHTINGS AT CHILLED WATER PUMP ROOM Radial B B 11 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 2.30

L3/1 LIGHTINGS AT ELECTRICAL ROOM Radial B B 3 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 0.59

L1/2 LIGHTINGS AT ICT ROOM Radial B B 2 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 0.33

L2/2 LIGHTINGS AT BMS SECURITY ROOM Radial B B 3 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 0.59

L3/2 EXTERNAL LIGHTINGS Radial B B 5 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 2.17

L1/3 LIGHTINGS AT PUMP ROOM Radial B B 4 3C 2x2.5 1x2.5 RCBO (100mA) 10 A 1P+N 1.03

L2/3 SPARE RCBO (100mA) 10 A 1P+N

L3/3 SPARE RCBO (100mA) 10 A 1P+N

L1/4 SPARE RCBO (100mA) 10 A 1P+N

L2/4 SPACE

L3/4 SPACE

L1/5 SPACE

L2/5 SPACE

L3/5 SPACE

L1/6 SPACE

L2/6 SPACE

L3/6 SPACE

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 2.93 2.89 2.76

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.68 0.67 0.64

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 1.00

Installation Method: Demand Load(KVA) 2.00

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 2.50
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: DB-POWER TYPE 4(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 10 mm² XLPE/LS0H/SWA
CABLE EARTHING 1C 10 mm² LS0H
Supplied From: MDB Volts: 400/230

No. of SP Ways: 18 Phase: 3 CABLE


LENGTH 11
Incoming Device Rating: 40AT/125AF IP Rating: IP42 (M) % Cummulative VD,VD2

Short Circuit Level, S.C. (KA): 12.5 Load Spare Capacity(%): 25

Form Type: Form-1

Tabulated Voltage Cummulative,


Length,Lh Length, Lb LOAD CURRENT,IL(Amps)
Circuit Cable Installation No. of Line Cable CPC Cable Protective Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of Cores Poles
Type Type Method Elements Size(mm²) Size(mm²) Device Type Device Rating
m m mV/m/A % % Phase A Phase B Phase C

L1/1 POWER SOCKETS OUTLET FOR OUTDOOR LV YARD Radial B B 2 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 1.57

L2/1 SPARE RCBO (30mA) 32 A 1P+N

L3/1 POWER SOCKETS OUTLET AT ELECTRICAL ROOM Radial B B 2 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 1.57

L1/2 SPARE RCBO (30mA) 32 A 1P+N

L2/2 SPARE RCBO (30mA) 32 A 1P+N

L3/2 POWER SOCKETS OUTLET AT PUMP ROOM Radial B B 2 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 1.57

L1/3 SPARE RCBO (30mA) 32 A 1P+N 3.13

L2/3 POWER FOR LIGHTING CONTROL PANEL(LCP) Radial B B 1 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 8.00

L3/3 POWER SOCKETS OUTLET AT CHILLLED WATER PUMP ROOM Radial B B 3 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 2.35

L1/4 POWER SOCKETS OUTLET AT BMS ROOM Radial B B 3 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 2.35

L2/4 SPARE RCBO (30mA) 32 A 1P+N

L1/2 POWER SOCKETS OUTLET AT ICT ROOM Radial B B 3 3C 4x4 2x4 RCBO (30mA) 32 A 1P+N 2.35

L1/5 SPARE RCBO (30mA) 32 A 1P+N

L2/5 SPACE

L3/5 SPACE

L1/6 SPACE

L2/6 SPACE

L3/6 SPACE

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 7.04 8.00 7.83

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 1.62 1.84 1.80

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 5.26

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 6.58
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: ESMDB-1 TYPE 4(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 50 mm² XLPE/LS0H/SWA(FR)
CABLE EARTHING 1C 25 mm² LS0H
Supplied From: GEN Volts: 400/230

No. of 3P Ways: 6 Phase: 3 CABLE


LENGTH 20
Incoming Device Rating: 125AT/250AF IP Rating: IP55 (M) % Cummulative VD,VD2

Short Circuit Level, S.C. (KA): 35 Load Spare Capacity(%): 25

Form Type: Form-4

Tabulated Voltage Cummulative,


Protective Length,Lh Length, Lb LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m m mV/m/A % % Phase A Phase B Phase C

L1/1 9.71

L2/1 DB-ICT Radial E E 1 4C 10 10 MCCB 40 3 25 9.71

L3/1 9.71

L1/2 16.39

L2/2 DB-HVAC Radial E E 1 4C 16 16 MCCB 63 3 20 16.39

L3/2 16.39

L1/3 6.50

L2/3 DB-PPP Radial E E 1 4C 16 16 MCCB 63 3 30 6.50

L3/3 6.50

L1/4 27.54

L2/4 MCC-PWP Radial E E 1 4C 16 16 MCCB 63 3 30 27.54

L3/4 27.54

L1/5

L2/5 SPARE MCCB 63

L3/5

L1/6

L2/6 SPACE MCCB 63

L3/6

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 60.13 60.13 60.13

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 13.83 13.83 13.83

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 41.50

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 51.87
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: DB-HVAC TYPE 4(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 16 mm² XLPE/LS0H/SWA
CABLE EARTHING 1C 16 mm² LS0H
Supplied From: ESMDB-1 Volts: 400/230

No. of SP Ways: 18 Phase: 3 CABLE


LENGTH 20
Incoming Device Rating: 63AT/125AF IP Rating: IP42 (M) % Cummulative VD,VD2

Short Circuit Level, S.C. (KA): 12.5 Load Spare Capacity(%): 25

Form Type: Form-1

Tabulated Voltage Cummulative,


Length,Lh Length, Lb LOAD CURRENT,IL(Amps)
Circuit Cable Installation No. of Line Cable CPC Cable Protective Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of Cores Poles
Type Type Method Elements Size(mm²) Size(mm²) Device Type Device Rating
m m mV/m/A % % Phase A Phase B Phase C

L1/1 POWER FOR INDOOR UNIT IN ELECTRICAL ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 2P 8.15

L2/1 POWER FOR INDOOR UNIT IN ICT ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 2P 8.91

L3/1 POWER FOR INDOOR UNIT IN PUMP ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 2P 8.15

L1/2 POWER FOR INDOOR UNIT IN CHILLED WATER PUMP ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 2P 14.13

L2/2 SPARE MCB 20 A 2P

L3/2 SPARE MCB 20 A 2P

L1/3 SPARE MCB 20 A 2P

L2/3 SPARE MCB 20 A 2P

L3/3 SPARE MCB 20 A 2P

L1/4 SPACE

L2/4 SPACE

L3/4 SPACE

L1/5 SPACE

L2/5 SPACE

L3/5 SPACE

L1/6 SPACE

L2/6 SPACE

L3/6 SPACE

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 22.28 8.91 8.15

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 5.13 2.05 1.88

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 9.05

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 11.31
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: DB-ICT TYPE 4(TYPICAL FOR 6 Nos.) Location: U-HUB TYPE 4 FEEDER PHASE 4C 10 mm² XLPE/LS0H/SWA(FR)
CABLE EARTHING 1C 10 mm² LS0H
Supplied From: ESMDB-1 Volts: 400/230

No. of SP Ways: 18 Phase: 3 CABLE


LENGTH 25
Incoming Device Rating: 40AT/125AF IP Rating: IP42 (M) % Cummulative VD,VD2

Short Circuit Level, S.C. (KA): 12.5 Load Spare Capacity(%): 25

Form Type: Form-1

Tabulated Voltage Cummulative,


Length,Lh Length, Lb LOAD CURRENT,IL(Amps)
Circuit Cable Installation No. of Line Cable CPC Cable Protective Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of Cores Poles
Type Type Method Elements Size(mm²) Size(mm²) Device Type Device Rating
m m mV/m/A % % Phase A Phase B Phase C

L1/1 POWER FOR FACP PANEL Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 3.00

L2/1 POWER FOR DDC PANEL Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 10.00

L3/1 POWER FOR NETWORK EQUIPMENT AT ICT ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 4.35

L1/2 POWER FOR NETWORK EQUIPMENT AT ICT ROOM Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 4.35

L2/2 SPARE MCB 20 A 1P+N

L3/2 POWER FOR SECURITY SYSTEM (IBMS) Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 2.17

L1/3 POWER PROVISION FOR WAP UNITS Radial F B 1 3C 2x4 1x4 MCB 20 A 1P+N 1.30

L2/3 SPARE MCB 20 A 1P+N

L3/3 POWER FOR PANIC DOORS Radial F B 5 3C 2x4 1x4 MCB 20 A 1P+N 3.91

L1/4 SPACE

L2/4 SPACE

L3/4 SPACE

L1/5 SPACE

L2/5 SPACE

L3/5 SPACE

L1/6 SPACE

L2/6 SPACE

L3/6 SPACE

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 8.65 10.00 10.43

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 1.99 2.30 2.40

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 5.11

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 6.70
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: MCC-CWP-EV1 Location: U-HUB TYPE 4 FEEDER PHASE 4C 95 mm² XLPE/LS0H/SWA(FR)
CABLE EARTHING 1C 50 mm² LS0H
Supplied From: MDB Volts: 400/230

No. of 3P Ways: 8 Phase: 3 CABLE


LENGTH 30
Incoming Device Rating: 200AT/250AF IP Rating: IP54 (M) % Cummulative VD,VD2

Short Circuit Level, S.C. (KA): 35 Load Spare Capacity(%): 25

Form Type: Form-4 TYPE 6

Tabulated Voltage Cummulative,


Length,Lh Length, Lb LOAD CURRENT,IL(Amps)
Circuit Cable Installation No. of Line Cable CPC Cable Protective Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of Cores Poles
Type Type Method Elements Size(mm²) Size(mm²) Device Type Device Rating
m m mV/m/A % % Phase A Phase B Phase C

L1/1 29.89

L2/1 CWP-1 (DUTY) Radial A E 1 4C 16 16 MCCB 63 3 10 29.89

L3/1 29.89

L1/2 29.89

L2/2 CWP-2 (DUTY) Radial A E 1 4C 16 16 MCCB 63 3 10 29.89

L3/2 29.89

L1/3 29.89

L2/3 CWP-3(DUTY) Radial A E 1 4C 16 16 MCCB 63 3 10 29.89

L3/3 29.89

L1/4 29.89

L2/4 CWP-4(STANDBY) Radial A E 1 4C 16 16 MCCB 63 3 10 29.89

L3/4 29.89

L1/5

L2/5 SPARE MCCB 63 3

L3/5

L1/6

L2/6 SPARE MCCB 63 3

L3/6

L1/7

L2/7 SPACE

L3/7

L1/8

L2/8 SPACE

L3/8

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 29.89 29.89 29.89

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 20.63 20.63 20.63

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.75

Installation Method: Demand Load(KVA) 61.88

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 77.34