Diagnostics 9.1 Diagnostics Via LED Displays: D4x5 Commissioning and Hardware Installation Manual, 08/2008 Edition

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Diagnostics

9.1 Diagnostics via LED displays

Meaning LED display


RDY RUN STOP STOPU SF DP1 DP2 OPT
Read or write access to CF x x x x x x x
card. (yellow)
Upgrade/downgrade operation 0.5/1 x x x x x x x
running. (yellow)
The upgrade/downgrade 2/1 x x x x x x x
operation has completed (yellow)
(power OFF/ON of the
upgraded/downgraded
devices is necessary)
RUN x 1 0 0 x x x x
(green)
Transition from RUN - STOPU x 1 0 2/1 x x x x
(green) (yellow)
Transition from STOPU - RUN x 2/1 0 1 x x x x
(green) (yellow)
STOPU x 0 0 1 x x x x
(yellow)
Service mode x 2/1 0 2/1 x x x x
(green) (yellow)
Transition from STOPU - x 0 2/1 1 x x x x
STOP (yellow) (yellow)
STOP x 0 1 0 x x x x
(yellow)
Transition from STOP - x 0 1 2/1 x x x x
STOPU (yellow) (yellow)
Request for overall reset by x 0 0.5/1 0 x x x x
the D4x5 itself or via the mode (yellow)
selector
Overall reset in progress 1 0 0 0 0 0 0 0
Overall reset completed 1 0 1 0 x x x x
(green) (yellow)
An interrupt that can be 1 x x x 1 x x x
acknowledged (alarm, (green) (red)
message, note) is pending
Fault is present to which the Λ Λ Λ Λ Λ Λ Λ Λ
user program (SIMOTION) (red) (red) (red) (red) (red) (red) (red) (red)
cannot respond. The following
= мерцающий светодиод
actions may be required to
Неисправность присутствует, на которую пользовательская программа (SIMOTION) не
rectify the fault:
может ответить. Для устранения неисправности могут потребоваться следующие
• Power OFF/ON
действия:
• Examine the CF card • Питание выключено / включено
• New commissioning • Изучите CF-карту
procedure • Новая процедура ввода в эксплуатацию
• Replace the D4x5 • Замените D4x5

Sublicensing of 1 x x x 0.5/1 x x x
technology/option objects (green) (red)

D4x5
244 Commissioning and Hardware Installation Manual, 08/2008 Edition

You might also like