Professional Documents
Culture Documents
Ls Gipam 115
Ls Gipam 115
Contents Features
Technical specifications
Communications
N-2-4
N-2-6
N-2-8
External & MMI N-2-9
Operation curves N-2-10
Wirings N-2-12
Ordering & Dimension N-2-15
Digital Integrated Protection & Monitoring Device
Features
GIPAM
Digital Integrated Protection & Monitoring Equipment
GIPAM is a multifunction, microprocessor-based protection equipment suitable
for all types of applications such as distribution feeders.
It can be also be used for management and backup protection of buses,
transformers, and power lines.
Drawout structure for panel mounting
User-friendly front panel to monitor, program, and test the GIPAM
Data communication with a host computer
N-2-4
Protection
● Multi-functions offering a wide choice of protective options
OCR, 50/51
OCGR, 50/51N
OVR, 59
UVR, 27
OVGR, 64G
SGR, 67G
POR, 47
● Displaying status via digital LCD and analog Bar graph for better visualization
Communication
�Modbus/RS-485 N2
�I-NET / LS customized protocol
GIPAM-115
N-2-5
Digital Integrated Protection & Monitoring Device
Technical specifications
Rating
Type Specification
Frequency 60Hz/50Hz
PT 110V
Voltage
GPT 190V
CT 5A
Current
ZCT 200/1.5mA
Input
Control Voltage AC/DC 110V or DC 125V
PT Max. 0.5VA
Burden
CT Max. 1.0VA
2 In for 3 hours
Current circuit
Overload Withstand 20 In for 2 seconds
Air 8kV
ESD (Electrostatic Discharge)
Contact 6kV
Non-impact place
Others
Non-air pollution place
×H×
Dimension (W× ×D) 437×210×165 mm
Weight 10.5kg
N-2-6
Protection functions
Measurement functions
0~190(V)
Zero-phase voltage, Vo - Vo, Vo_max(peak)
Bar graph 0~120%
0~9,999MW
Active power, Watts ±1.0%
Bar graph 0~120%
0~999,999MWh
Active energy, Wh
Bar graph 0~120%
±1.0%
N2
0~999,999MVarh
Reactive energy, Varh ±1.0%
Bar graph 0~120%
GIPAM-115
N-2-7
Digital Integrated Protection & Monitoring Device
Communications
Modbus/RS-485
�Operation mode: Differential
�Distance: Max. 1.2km
�Cable : SCADA system
General RS-485 shielded twist
2-pair cable
Modbus/RS-485
�Baud rate :
9600bps, 19200bps, 38400bps
�Transmission method: Half-Duplex
�Termination: 150Ω
N-2-8
External & MMI
①
⑨
②
⑩
④
⑪
⑤
⑥
Control keys
⑦ ⑧ ⑫ ⑬ ⑭ ⑮ � � � � �
N2
GIPAM-115
N-2-9
Digital Integrated Protection & Monitoring Device
Operation curves
0.14
SI, Standard Inverse T= D2, Definite Time T=2
(I / IS)0.02 - 1
13.5
VI, Very Inverse T= D4, Definite Time T=4
(I / IS) - 1
80
EI, Extremely Inverse T= D8, Definite Time T=8
(I / IS)2 - 1
120
LI, Long Inverse T=
(I / IS) - 1
100
10
1.2 10
Operation time, sec
Operation time, sec
0.6
1 0.4
0.3
0.2
1
1.2
0.1
0.6
0.4
0.05 0.3
0.1
0.2
0.1
0.1
0.05
0.01 0.01
1 10 20 1 10 20
N-2-10
EI curves for OCR and OCGR LI curves for OCR and OCGR
1000 10000
100
1000
10
10
1.2
1.2
0.6
0.1 0.4 0.6
0.3 0.4
0.2 0.3
0.1 0.2
1
0.01 0.05 0.1
0.05
0.001 0.1
1 10 20 1 10 20
Definite Time curves for UVR and OVR Operation phase characterictic of SGR
135
UVR Setting OVR Setting
60
Operation time, sec
10
0.1
N2
315
0.2 0.8 0.9 1 1.6
GIPAM-115
N-2-11
Digital Integrated Protection & Monitoring Device
Wirings
Input Output
Comm
terminals
Note) 1. Avoid connectting GIPAM parallel with the other devices that generate noises.
2. Press the clear switch to initialize all data after installation.
N-2-12
1P 2W
1P 3W
N2
GIPAM-115
N-2-13
Digital Integrated Protection & Monitoring Device
Wirings
3P 3W
3P 4W
(NCT is available)
ZCT GPT
N-2-14
Dimension & Ordering
Dimensions
Cutout
Ordering
GIPAM-115 FI RS M 60Hz
N2
Protection Communication Protocol Frequency
GIPAM-115
N-2-15