1) Relay Data
- Applied type : 50, 51G, 46, 49, 66, 27M, 27H
- Relay type : REM615(ABB)
2) CALCULATION DATA
- Applied MOTOR : TBN BEARING OIL PUMP
- Rating : 132kW
- Rated current : 236A
- Starting current : 236A × 6.0 = 1416A
- Starting time : 8-5 = 3sec (Assumed)
- Thermal limit time : 8sec / -sec (Hot / Cold)
- Number of consec. Starts : 3times / 4times (Hot / Cold)
- Max 3Phase fault current : 42kA(base 0.4kV)
- Max Earth fault current : 54kA(base 0.4kV)
3) CT & VT DATA
- CT ratio : 400/1A, 100/1(ZCT)
- VT ratio : 400V/√3 / 110V/√3
PT
400V 110V
50 51G 46
3 3
49 66 27M
27H
400V SWGR
ACB
132kW
MOTOR
CT ZCT
400/1A 100/1A
4) 49 (MPTTR) CALCULATION
- Overload Factor
Overload Factor : 1.15
- Alarm Thermal Value
Alarm Thermal Value : 90%
- Restart Thermal Value
Restart Thermal Value : 40%
- Weighting Factor p
Weighting Factor p : 60
- Time Constant Normal / Start
@ 6 / ln[{6 2 – (60/100)}/(62 – 1.3225)] = 291s Time Constant
Normal / start : 291s
- Time Constant Stop
@ Normal/start 200% setting Time Constant stop : 582s
5) 50 (PHIPTOC) CALCULATION
- Start Value
@ Set at 250% of Motor starting current
@ 1416×2.5×(1/400) = 8.9In Start value : 8.9 In
@ Pickup current = 8.9×(400/1) = 3560A
8) 46 (MNSPTOC) CALCULATION
- Start Value
@ Set at 15% of Motor Rated current
@ 236×0.15×(1/400) = 0.09 In start value : 0.09 In
@ Pickup current = 0.09×(400/1) = 36A
- Motor start-up A
@ 236×6×(1/400) = 3.5 In Motor Start-up A : 3.5 In
REM 615
46 I2>M MNSPTOC
Group settings
Group settings
Operation Off/On - 1 = On - On
66 Is2tn< STTPMSU
Group settings
Operation Off/On -- On - On
1= IIt
2= IIt, CB
Operation mode - 1 = IIt - IIt + stall
3= IIt + stall
4= IIt+stall, CB
Counter Red rate 2.0 - 250.0 0.1 60 s/h 2