STRUCTURAL CALCULATIONS
for

RETIREMENT HOME
EXHAUST STACK

Prepared by:
Craig T. Christy, P.E.
July 19, 2002

CONSULTING COMPANY
Page 19 - 2    

532558393.xls    
Page 19 - 3    
RETIREMENT HOME
EXHAUST STACK 19
532558393.xls    

Christy
7/17/21
ENGINEERING with the SPREADSHEET
Copyright 2006 American Society of Civil Engineers

TABLE OF CONTENTS
Seismic Zone 3
Wind 150 mph
Frost 18"
Soil 2000 psf
Corrosion 1/16"

Seismic Calculation 20-1 to 20-4

Wind 21-1 to 21-3

Vortex Shedding
Summary 23-1
Wind -- wind governs 23-2
Seismic moment and deflection 23-3 to 23-4
Natural frequency of structure 23-5
Vortex shedding per PVDH 23-6 to 23-8
Cantilever vibration per DPE 23-9 to 23-10
Shell buckling stresses 23-11 to 23-12
Ovaling -- provide stiffeners to upper shells 23-13 to 23-15
Breeching 23-16 to 23-18

Bolt Patterns 24-1 to 24-2

Bolt Threads 25-1 to 25-6

Anchor Bolt Pullout 27-1 to 27-7

Roark Flat Plates 28-1 to 28-4

Trapezoidal Soil Loading 30-1 to 30-2


Triangular Soil Loading 30-3

Foundation Design 31-1 to 31-2

Reinforced Concrete Beam Design 33-1 to 33-12

Concrete Shear 34-1 to 34-2

Stack Drawings 35-1 to 35-6

Note: Calculations for vortex shedding are adopted from several sources and give varying
answers. These calculations bracket the wind speed at which the stack oscillates
and the force of those oscillations. Page 19 - 4    