Manejadora de Aire V1
Manejadora de Aire V1
Prepared By:
Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 9 0.320 No Sí
Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 D 0.329 M
Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.329 10 0
2 0.320 10 0
Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.000 0.830 1.000 1 0.700
Check Figures
Total Air Handler Supply Air (based on a 19° TD): 948 CFM
Total Air Handler Vent. Air (100.00% of Supply): 948 CFM
Total Conditioned Air Space: 324 Sq.ft
Supply Air Per Unit Area: 2.9231 CFM/Sq.ft
Area Per Cooling Capacity: 80.5135 Sq.ft/Ton
Cooling Capacity Per Area: 0.0124 Tons/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 4.03 Tons
Laboratorio
228 0 14,726 630 None None
3 MicrobiologÍa
3 0 846 0 0 0
4pm December
2,280 0.00 3.71 0 0 846
Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,603 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,603 CFM
Total Conditioned Air Space: 391 Sq.ft
Supply Air Per Unit Area: 4.1032 CFM/Sq.ft
Area Per Cooling Capacity: 56.2859 Sq.ft/Ton
Cooling Capacity Per Area: 0.0178 Tons/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 6.94 Tons
DesinfecciÓn Y
103 0 5,458 420 None 4/Hr
6 EsterelizaciÓn
2 0 279 0 0 69
7pm December
1,030 0.00 2.71 0 0 48
Almacén Material
94 0 6,793 210 None 4/Hr
7 Esteril
1 0 347 0 0 63
7pm December
938 0.00 3.70 0 0 60
Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,009 CFM
Total Air Handler Vent. Air (17.19% of Supply): 174 CFM
Total Conditioned Air Space: 260 Sq.ft
Supply Air Per Unit Area: 3.8779 CFM/Sq.ft
Area Per Cooling Capacity: 115.4538 Sq.ft/Ton
Cooling Capacity Per Area: 0.0087 Tons/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.25 Tons
Zone 2-Lab Hematologia - Air Handler 2 (Uma- Laboratorio), Group 0 peaks (sensible) in December at
4pm.
Roof-1-9-Susp.C-L 117 0.50 25.0 0.320 933 0.000 0
Wall-1-SSE-D-M 126 0.83 29.8 0.329 1,228 0.000 0
Partition-2-1 425.1 10/0 0.329 1,399 0.000 0
Gls-SSE-1-90-Tran 13.6 1.000 23 1.000 313 0.000 0
0%S-0-WS-Solar 13.6 0.700 156 0.300 446
Lights-Prof=1 117 1.000 398
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 2.0 1.000 500 400
Sub-total 10,335 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 10,852 420 0
Zone 3-Laboratorio MicrobiologÍa - Air Handler 2 (Uma- Laboratorio), Group 0 peaks (sensible) in
December at 4pm.
Roof-1-9-Susp.C-L 228 0.50 25.0 0.320 1,824 0.000 0
Wall-1-SSE-D-M 205 0.83 29.8 0.329 2,006 0.000 0
Partition-2-1 630.5 10/0 0.329 2,074 0.000 0
Gls-SSE-1-90-Tran 26.4 1.000 23 1.000 607 0.000 0
0%S-0-WS-Solar 26.4 0.700 156 0.300 866
Lights-Prof=1 228 1.000 778
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 3.0 1.000 750 600
Sub-total 14,024 600 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 14,726 630 0
Zone 4-Vestibulo - Air Handler 2 (Uma- Laboratorio), Group 0 peaks (sensible) in December at 4pm.
Roof-1-9-Susp.C-L 46 0.50 25.0 0.320 368 0.000 0
Partition-1-1 383.5 10/0 0.329 1,262 0.000 0
Lights-Prof=1 46 1.000 157
Zone 5-Prep Y Empaque Ester - Air Handler 3 (Uma-esterlizaciÓn), Group 0 peaks (sensible) in
December at 7pm.
Roof-1-9-Susp.C-L 64 0.50 27.0 0.320 549 0.000 0
Partition-1-1 165.1 10/0 0.329 543 0.000 0
Partition-2-1 65 10/0 0.329 214 0.000 0
Lights-Prof=1 64 1.000 217
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 2.0 1.000 500 400
Sub-total 7,141 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 7,498 420 0
Zone 7-Almacén Material Esteril - Air Handler 3 (Uma-esterlizaciÓn), Group 0 peaks (sensible) in
December at 7pm.
Roof-1-9-Susp.C-L 94 0.50 27.0 0.320 810 0.000 0
Partition-1-1 146.9 10/0 0.329 483 0.000 0
Partition-2-1 107.9 10/0 0.329 355 0.000 0
Partition-3-1 254.8 10/0 0.329 838 0.000 0
Lights-Prof=1 94 1.000 320
Equipment-Prof=1 1,000 1.000 3,412 0
People-Prof=1 1.0 1.000 250 200
Sub-total 6,469 200 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 6,793 210 0
Zone 2-Lab Hematologia peaks (sensible) in December at 4pm, Air Handler 2 (Uma- Laboratorio), Group
0, 10.7 x 10.9, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 117 0.50 25.0 0.320 933 0.000 0
Wall-1-SSE-D-M 126 0.83 29.8 0.329 1,228 0.000 0
Partition-2-1 425.1 10/0 0.329 1,399 0.000 0
Gls-SSE-1-90-Tran 13.6 1.000 23 1.000 313 0.000 0
0%S-0-WS-Solar 13.6 0.700 156 0.300 446
Lights-Prof=1 117 1.000 398
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 2.0 1.000 500 400
Sub-total 10,335 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 10,852 420 0
Zone 3-Laboratorio MicrobiologÍa peaks (sensible) in December at 4pm, Air Handler 2 (Uma- Laboratorio),
Group 0, 15.1 x 15.1, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 228 0.50 25.0 0.320 1,824 0.000 0
Wall-1-SSE-D-M 205 0.83 29.8 0.329 2,006 0.000 0
Partition-2-1 630.5 10/0 0.329 2,074 0.000 0
Gls-SSE-1-90-Tran 26.4 1.000 23 1.000 607 0.000 0
0%S-0-WS-Solar 26.4 0.700 156 0.300 866
Lights-Prof=1 228 1.000 778
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 3.0 1.000 750 600
Sub-total 14,024 600 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 14,726 630 0
Zone 4-Vestibulo peaks (sensible) in December at 7pm, Air Handler 2 (Uma- Laboratorio), Group 0, 4.6 x
10.0, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 46 0.50 27.0 0.320 397 0.000 0
Partition-1-1 383.5 10/0 0.329 1,262 0.000 0
Zone 5-Prep Y Empaque Ester peaks (sensible) in December at 7pm, Air Handler 3 (Uma-esterlizaciÓn),
Group 0, 12.7 x 5.0, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 64 0.50 27.0 0.320 549 0.000 0
Partition-1-1 165.1 10/0 0.329 543 0.000 0
Partition-2-1 65 10/0 0.329 214 0.000 0
Lights-Prof=1 64 1.000 217
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 2.0 1.000 500 400
Sub-total 7,141 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 7,498 420 0
Zone 6-DesinfecciÓn Y EsterelizaciÓn peaks (sensible) in December at 7pm, Air Handler 3 (Uma-
esterlizaciÓn), Group 0, 13.2 x 7.8, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 103 0.50 27.0 0.320 890 0.000 0
Partition-1-1 273 10/0 0.329 898 0.000 0
Lights-Prof=1 103 1.000 351
Equipment-Prof=1 750 1.000 2,559 0
People-Prof=1 2.0 1.000 500 400
Sub-total 5,198 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 5,458 420 0
Zone 7-Almacén Material Esteril peaks (sensible) in December at 7pm, Air Handler 3 (Uma-esterlizaciÓn),
Group 0, 11.3 x 8.3, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 94 0.50 27.0 0.320 810 0.000 0
Partition-1-1 146.9 10/0 0.329 483 0.000 0
Partition-2-1 107.9 10/0 0.329 355 0.000 0
Partition-3-1 254.8 10/0 0.329 838 0.000 0
Lights-Prof=1 94 1.000 320
Equipment-Prof=1 1,000 1.000 3,412 0
People-Prof=1 1.0 1.000 250 200
Sub-total 6,469 200 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 6,793 210 0