Centro De Salud Nueva Requena

HVAC Load Analysis


for

Prepared By:

domingo, 8 de Setiembre de 2019


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 2
Project Information
Project Title: Centro De Salud Nueva Requena
Designed By:
Date: domingo, 18 de Agosto de 2019
Comment:

Client Name: Company Name:


Address: Representative:
City: Address:
Phone: City:
Fax: Phone:
Comment: Fax:
Comment:

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 3

General Project Data Input


General Project Information
Project file name: D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0.
Anexo\0.1 Aire Acondicionado\Manejadora de Aire nuevos
cambios.CHV
Project title: Centro De Salud Nueva Requena
Project date: domingo, 18 de Agosto de 2019
Project location: Pucalpa, Ucayali, PERU
Barometric pressure: 29.331 in.Hg.
Altitude: 550 feet
Latitude: -8 Degrees
Mean daily temperature range: 8 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique zones in this project: 7

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 1.00 Watts per square foot
Equipment requirements: 1.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 5 %
Zone latent safety factor: 5 %
Zone heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 10.0 feet
Building default wall height: 13.0 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 0 0 0 0 0 0 C C C C C C C C C C C C C 0 0 0 0 0
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 4

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
December 93 70 50% 73 13.67 9
Winter 0 0

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 9 0.320 No Sí

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 D 0.329 M

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.329 10 0
2 0.320 10 0

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.000 0.830 1.000 1 0.700

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 5

Air Handler Input


Air Handler Number 1 Input Data
Name: Uma- Sala De Partos
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Cooling loads only
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 54.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 85
Static pressure across fan (in.wg.): 2.00
Summer supply duct temp rise (deg.F): 2.000
Summer return duct temp rise (deg.F): 2.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 100% sup.
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 CFM/Pr
Heating infiltration: 0 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
December 93 70 50% 73 13.67 9
Winter 0 0

Air Handler Number 2 Input Data


Name: Uma- Laboratorio
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Cooling loads only
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 54.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 85

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 6

Air Handler Input (cont'd)


Air Handler Number 2 Input Data
Static pressure across fan (in.wg.): 2.00
Summer supply duct temp rise (deg.F): 2.000
Summer return duct temp rise (deg.F): 2.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 100% sup.
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 CFM/Pr
Heating infiltration: 0 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
December 93 70 50% 73 13.67 9
Winter 0 0

Air Handler Number 3 Input Data


Name: Uma-esterlizaciÓn
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Cooling loads only
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 90.0
Leaving cooling coil temp (deg.F): 54.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 85
Static pressure across fan (in.wg.): 2.00
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 4 AC/Hr
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 CFM/Pr
Heating infiltration: 0 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 7

Air Handler Input (cont'd)


Air Handler Number 3 Input Data
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
December 93 70 50% 73 13.67 9
Winter 0 0

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 8

Air Handler #1 - Uma- Sala De Partos - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Sala De Partos 324 0 16,508 681 None None
8pm December 3 0 948 0 0 0
3,244 0.00 2.92 0 0 948
Zone Peak Totals: 324 0 16,508 681
Total Zones: 1 3 0 948 0 0 0
Unique Zones: 1 3,244 0.00 2.92 0 0 948

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 9

Air Handler #1 - Uma- Sala De Partos - Total Load Summary


Air Handler Description: Uma- Sala De Partos Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.35 HP
Fan Input: 85% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.97 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in December.
Outdoor Conditions: 91° DB, 70° WB, 75.81 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 8pm is
different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 16,508.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.980 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 15,661 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 873 Btuh
Supply duct sensible gain: 2,045 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 18,579 Btuh
Cooling Supply Air: 19,426 / (.980 X 1.1 X 19) = 948 CFM
Summer Vent Outside Air (100.0% of supply) = 948 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 18,403 Btuh 948 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 18,403 Btuh
Total sensible gain on air handling system: 36,982 Btuh
Zone space latent gain: 681 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 10,681 Btuh
Total latent gain on air handling system: 11,362 Btuh
Total system sensible and latent gain: 48,344 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 948 CFM
Total Air Handler Vent. Air (100.00% of Supply): 948 CFM
Total Conditioned Air Space: 324 Sq.ft
Supply Air Per Unit Area: 2.9231 CFM/Sq.ft
Area Per Cooling Capacity: 80.5135 Sq.ft/Ton
Cooling Capacity Per Area: 0.0124 Tons/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 4.03 Tons

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 10

Air Handler #2 - Uma- Laboratorio - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
2 Lab Hematologia 117 0 10,852 420 None None
4pm December 2 0 623 0 0 0
1,166 0.00 5.34 0 0 623

Laboratorio
228 0 14,726 630 None None
3 MicrobiologÍa
3 0 846 0 0 0
4pm December
2,280 0.00 3.71 0 0 846

4 Vestibulo 46 0 2,334 210 None None


7pm December 1 0 134 0 0 0
460 0.00 2.91 0 0 134
Zone Peak Totals: 391 0 27,912 1,260
Total Zones: 3 6 0 1,603 0 0 0
Unique Zones: 3 3,906 0.00 4.10 0 0 1,603

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 11

Air Handler #2 - Uma- Laboratorio - Total Load Summary


Air Handler Description: Uma- Laboratorio Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.59 HP
Fan Input: 85% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.96 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in December.
Outdoor Conditions: 93° DB, 70° WB, 75.68 grains
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.980 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 27,881 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,476 Btuh
Supply duct sensible gain: 3,457 Btuh
Reserve sensible gain: 27 Btuh
Total sensible gain on supply side of coil: 32,841 Btuh
Cooling Supply Air: 32,841 / (.980 X 1.1 X 19) = 1,603 CFM
Summer Vent Outside Air (100.0% of supply) = 1,603 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 34,568 Btuh 1,603 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 34,568 Btuh
Total sensible gain on air handling system: 67,409 Btuh
Zone space latent gain: 1,260 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 14,615 Btuh
Total latent gain on air handling system: 15,875 Btuh
Total system sensible and latent gain: 83,283 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,603 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,603 CFM
Total Conditioned Air Space: 391 Sq.ft
Supply Air Per Unit Area: 4.1032 CFM/Sq.ft
Area Per Cooling Capacity: 56.2859 Sq.ft/Ton
Cooling Capacity Per Area: 0.0178 Tons/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 6.94 Tons

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 12

Air Handler #3 - Uma-esterlizaciÓn - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
Prep Y Empaque
64 0 7,498 420 None 4/Hr
5 Ester
2 0 383 0 0 42
7pm December
635 0.00 6.03 0 0 66

DesinfecciÓn Y
103 0 5,458 420 None 4/Hr
6 EsterelizaciÓn
2 0 279 0 0 69
7pm December
1,030 0.00 2.71 0 0 48

Almacén Material
94 0 6,793 210 None 4/Hr
7 Esteril
1 0 347 0 0 63
7pm December
938 0.00 3.70 0 0 60

Zone Peak Totals: 260 0 19,748 1,050


Total Zones: 3 5 0 1,009 0 0 174
Unique Zones: 3 2,603 0.00 3.88 0 0 174

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 13

Air Handler #3 - Uma-esterlizaciÓn - Total Load Summary


Air Handler Description: Uma-esterlizaciÓn Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.37 HP
Fan Input: 85% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.95 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in December.
Outdoor Conditions: 91° DB, 70° WB, 75.81 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 7pm is
different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 19,748.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.980 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 19,748 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 930 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 20,678 Btuh
Cooling Supply Air: 20,678 / (.980 X 1.1 X 19) = 1,009 CFM
Summer Vent Outside Air (17.2% of supply) = 174 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 3,368 Btuh 174 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 3,368 Btuh
Total sensible gain on air handling system: 24,045 Btuh
Zone space latent gain: 1,050 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,954 Btuh
Total latent gain on air handling system: 3,004 Btuh
Total system sensible and latent gain: 27,050 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,009 CFM
Total Air Handler Vent. Air (17.19% of Supply): 174 CFM
Total Conditioned Air Space: 260 Sq.ft
Supply Air Per Unit Area: 3.8779 CFM/Sq.ft
Area Per Cooling Capacity: 115.4538 Sq.ft/Ton
Cooling Capacity Per Area: 0.0087 Tons/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.25 Tons

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 14

Zone Detailed Loads (At Group Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Sala De Partos - Air Handler 1 (Uma- Sala De Partos), Group 0 peaks (sensible) in December at
8pm.
Roof-1-9-Susp.C-L 324 0.50 27.0 0.320 2,802 0.000 0
Wall-1-SSE-D-M 199 0.83 32.2 0.329 2,110 0.000 0
Wall-2-WSW-D-M 276 0.83 38.9 0.329 3,525 0.000 0
Partition-3-1 594.1 10/0 0.329 1,955 0.000 0
Lights-Prof=2 324 1.000 1,107
Equipment-Prof=2 1,000 1.000 3,412 0
People-Prof=2 3.2 1.000 811 649
Sub-total 15,722 649 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 16,508 681 0

Zone 2-Lab Hematologia - Air Handler 2 (Uma- Laboratorio), Group 0 peaks (sensible) in December at
4pm.
Roof-1-9-Susp.C-L 117 0.50 25.0 0.320 933 0.000 0
Wall-1-SSE-D-M 126 0.83 29.8 0.329 1,228 0.000 0
Partition-2-1 425.1 10/0 0.329 1,399 0.000 0
Gls-SSE-1-90-Tran 13.6 1.000 23 1.000 313 0.000 0
0%S-0-WS-Solar 13.6 0.700 156 0.300 446
Lights-Prof=1 117 1.000 398
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 2.0 1.000 500 400
Sub-total 10,335 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 10,852 420 0

Zone 3-Laboratorio MicrobiologÍa - Air Handler 2 (Uma- Laboratorio), Group 0 peaks (sensible) in
December at 4pm.
Roof-1-9-Susp.C-L 228 0.50 25.0 0.320 1,824 0.000 0
Wall-1-SSE-D-M 205 0.83 29.8 0.329 2,006 0.000 0
Partition-2-1 630.5 10/0 0.329 2,074 0.000 0
Gls-SSE-1-90-Tran 26.4 1.000 23 1.000 607 0.000 0
0%S-0-WS-Solar 26.4 0.700 156 0.300 866
Lights-Prof=1 228 1.000 778
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 3.0 1.000 750 600
Sub-total 14,024 600 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 14,726 630 0

Zone 4-Vestibulo - Air Handler 2 (Uma- Laboratorio), Group 0 peaks (sensible) in December at 4pm.
Roof-1-9-Susp.C-L 46 0.50 25.0 0.320 368 0.000 0
Partition-1-1 383.5 10/0 0.329 1,262 0.000 0
Lights-Prof=1 46 1.000 157

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 15

Zone Detailed Loads (At Group Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Equipment-Prof=1 46 1.000 157 0
People-Prof=1 1.0 1.000 250 200
Sub-total 2,194 200 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 2,303 210 0

Zone 5-Prep Y Empaque Ester - Air Handler 3 (Uma-esterlizaciÓn), Group 0 peaks (sensible) in
December at 7pm.
Roof-1-9-Susp.C-L 64 0.50 27.0 0.320 549 0.000 0
Partition-1-1 165.1 10/0 0.329 543 0.000 0
Partition-2-1 65 10/0 0.329 214 0.000 0
Lights-Prof=1 64 1.000 217
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 2.0 1.000 500 400
Sub-total 7,141 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 7,498 420 0

Zone 6-DesinfecciÓn Y EsterelizaciÓn - Air Handler 3 (Uma-esterlizaciÓn), Group 0 peaks (sensible) in


December at 7pm.
Roof-1-9-Susp.C-L 103 0.50 27.0 0.320 890 0.000 0
Partition-1-1 273 10/0 0.329 898 0.000 0
Lights-Prof=1 103 1.000 351
Equipment-Prof=1 750 1.000 2,559 0
People-Prof=1 2.0 1.000 500 400
Sub-total 5,198 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 5,458 420 0

Zone 7-Almacén Material Esteril - Air Handler 3 (Uma-esterlizaciÓn), Group 0 peaks (sensible) in
December at 7pm.
Roof-1-9-Susp.C-L 94 0.50 27.0 0.320 810 0.000 0
Partition-1-1 146.9 10/0 0.329 483 0.000 0
Partition-2-1 107.9 10/0 0.329 355 0.000 0
Partition-3-1 254.8 10/0 0.329 838 0.000 0
Lights-Prof=1 94 1.000 320
Equipment-Prof=1 1,000 1.000 3,412 0
People-Prof=1 1.0 1.000 250 200
Sub-total 6,469 200 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 6,793 210 0

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 16

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Sala De Partos peaks (sensible) in December at 8pm, Air Handler 1 (Uma- Sala De Partos),
Group 0, 21.2 x 15.3, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 324 0.50 27.0 0.320 2,802 0.000 0
Wall-1-SSE-D-M 199 0.83 32.2 0.329 2,110 0.000 0
Wall-2-WSW-D-M 276 0.83 38.9 0.329 3,525 0.000 0
Partition-3-1 594.1 10/0 0.329 1,955 0.000 0
Lights-Prof=2 324 1.000 1,107
Equipment-Prof=2 1,000 1.000 3,412 0
People-Prof=2 3.2 1.000 811 649
Sub-total 15,722 649 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 16,508 681 0

Zone 2-Lab Hematologia peaks (sensible) in December at 4pm, Air Handler 2 (Uma- Laboratorio), Group
0, 10.7 x 10.9, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 117 0.50 25.0 0.320 933 0.000 0
Wall-1-SSE-D-M 126 0.83 29.8 0.329 1,228 0.000 0
Partition-2-1 425.1 10/0 0.329 1,399 0.000 0
Gls-SSE-1-90-Tran 13.6 1.000 23 1.000 313 0.000 0
0%S-0-WS-Solar 13.6 0.700 156 0.300 446
Lights-Prof=1 117 1.000 398
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 2.0 1.000 500 400
Sub-total 10,335 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 10,852 420 0

Zone 3-Laboratorio MicrobiologÍa peaks (sensible) in December at 4pm, Air Handler 2 (Uma- Laboratorio),
Group 0, 15.1 x 15.1, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 228 0.50 25.0 0.320 1,824 0.000 0
Wall-1-SSE-D-M 205 0.83 29.8 0.329 2,006 0.000 0
Partition-2-1 630.5 10/0 0.329 2,074 0.000 0
Gls-SSE-1-90-Tran 26.4 1.000 23 1.000 607 0.000 0
0%S-0-WS-Solar 26.4 0.700 156 0.300 866
Lights-Prof=1 228 1.000 778
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 3.0 1.000 750 600
Sub-total 14,024 600 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 14,726 630 0

Zone 4-Vestibulo peaks (sensible) in December at 7pm, Air Handler 2 (Uma- Laboratorio), Group 0, 4.6 x
10.0, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 46 0.50 27.0 0.320 397 0.000 0
Partition-1-1 383.5 10/0 0.329 1,262 0.000 0

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 17

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Lights-Prof=1 46 1.000 157
Equipment-Prof=1 46 1.000 157 0
People-Prof=1 1.0 1.000 250 200
Sub-total 2,223 200 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 2,334 210 0

Zone 5-Prep Y Empaque Ester peaks (sensible) in December at 7pm, Air Handler 3 (Uma-esterlizaciÓn),
Group 0, 12.7 x 5.0, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 64 0.50 27.0 0.320 549 0.000 0
Partition-1-1 165.1 10/0 0.329 543 0.000 0
Partition-2-1 65 10/0 0.329 214 0.000 0
Lights-Prof=1 64 1.000 217
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 2.0 1.000 500 400
Sub-total 7,141 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 7,498 420 0

Zone 6-DesinfecciÓn Y EsterelizaciÓn peaks (sensible) in December at 7pm, Air Handler 3 (Uma-
esterlizaciÓn), Group 0, 13.2 x 7.8, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 103 0.50 27.0 0.320 890 0.000 0
Partition-1-1 273 10/0 0.329 898 0.000 0
Lights-Prof=1 103 1.000 351
Equipment-Prof=1 750 1.000 2,559 0
People-Prof=1 2.0 1.000 500 400
Sub-total 5,198 400 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 5,458 420 0

Zone 7-Almacén Material Esteril peaks (sensible) in December at 7pm, Air Handler 3 (Uma-esterlizaciÓn),
Group 0, 11.3 x 8.3, Construction Type: 1 (Light)
Roof-1-9-Susp.C-L 94 0.50 27.0 0.320 810 0.000 0
Partition-1-1 146.9 10/0 0.329 483 0.000 0
Partition-2-1 107.9 10/0 0.329 355 0.000 0
Partition-3-1 254.8 10/0 0.329 838 0.000 0
Lights-Prof=1 94 1.000 320
Equipment-Prof=1 1,000 1.000 3,412 0
People-Prof=1 1.0 1.000 250 200
Sub-total 6,469 200 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 6,793 210 0

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 18

Air System #1 (Uma- Sala De Partos) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 60.542 54.000
Draw-Thru Fan 873 0.854 43
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 2,045 2.000 100
Zone Loads 681 1.078 16,508 16.147 806
Sensible Reserve 0 0.000 0
Zone Condition 681 61.619 19,426 73.000 948
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 948 CFM 10,681 16.899 18,403 18.000
Blow-Thru Fan 0 0.000
Entering Coil Condition 11,362 78.519 37,829 91.000 948

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.980 x 1.10 x 948 x( 91.000 - 54.000 )= 37,828 Btuh


TLH = 0.980 x 0.68 x 948 x( 78.519 - 60.542 )= 11,362 Btuh
----------
SUM = 49,190 Btuh
GTH = 0.980 x 4.50 x 948 x( 34.197 - 22.345 )= 49,568 Btuh
Total System Load = 48,344 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 49,568 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 91.00 Dry bulb temperature: .00
Wet bulb temperature: 70.00
Relative humidity: 35.40
Enthalpy: 34.20 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 54.00 Dry bulb temperature: .00
Wet bulb temperature: 53.30
Relative humidity: 95.73
Enthalpy: 22.35 Btu/lbm

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 19

Air System #2 (Uma- Laboratorio) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 60.440 54.000
Draw-Thru Fan 1,476 0.854 72
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 3,457 2.000 169
Zone Loads 1,260 1.179 27,881 16.131 1,361
Sensible Reserve 27 0.015 1
Zone Condition 1,260 61.619 32,841 73.000 1,603
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 1,603 CFM 14,615 13.679 34,568 20.000
Blow-Thru Fan 0 0.000
Entering Coil Condition 15,875 75.298 67,409 93.000 1,603

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.980 x 1.10 x 1,603 x( 93.000 - 54.000 )= 67,408 Btuh


TLH = 0.980 x 0.68 x 1,603 x( 75.298 - 60.440 )= 15,875 Btuh
----------
SUM = 83,283 Btuh
GTH = 0.980 x 4.50 x 1,603 x( 34.179 - 22.330 )= 83,785 Btuh
Total System Load = 83,283 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 83,785 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 93.00 Dry bulb temperature: .00
Wet bulb temperature: 70.00
Relative humidity: 31.92
Enthalpy: 34.18 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 54.00 Dry bulb temperature: .00
Wet bulb temperature: 53.28
Relative humidity: 95.57
Enthalpy: 22.33 Btu/lbm

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 20

Air System #3 (Uma-esterlizaciÓn) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 59.985 54.000
Draw-Thru Fan 930 0.854 45
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,050 1.561 19,748 18.146 964
Sensible Reserve 0 0.000 0
Zone Condition 1,050 61.545 20,678 73.000 1,009
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 174 CFM 1,954 2.918 3,368 3.094
Blow-Thru Fan 0 0.000
Entering Coil Condition 3,004 64.463 24,045 76.094 1,009

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.980 x 1.10 x 1,009 x( 76.094 - 54.000 )= 24,045 Btuh


TLH = 0.980 x 0.68 x 1,009 x( 64.463 - 59.985 )= 3,013 Btuh
----------
SUM = 27,058 Btuh
GTH = 0.980 x 4.50 x 1,009 x( 28.346 - 22.259 )= 27,101 Btuh
Total System Load = 27,050 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 27,101 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 76.09 Dry bulb temperature: .00
Wet bulb temperature: 62.51
Relative humidity: 47.13
Enthalpy: 28.35 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 54.00 Dry bulb temperature: .00
Wet bulb temperature: 53.16
Relative humidity: 94.88
Enthalpy: 22.26 Btu/lbm

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 21

Air System #1 (Uma- Sala De Partos) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 22

Air System #1 (Uma- Sala De Partos) Psychrometric Chart (G)


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 23

Air System #2 (Uma- Laboratorio) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 24

Air System #2 (Uma- Laboratorio) Psychrometric Chart (G)


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 25

Air System #3 (Uma-esterlizaciÓn) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Centro De Salud Nueva Requena
College Station, TX 77845 Page 26

Air System #3 (Uma-esterlizaciÓn) Psychrometric Chart (G)


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\Proyectos\Milton ERP\HOSPITAL NUEVA REQUENA\0. Anexo\0.1 Aire Acondicionado\Manejadora


domingo, 8 dede
Setiembre
Aire nuevos
de 2019,
cambios.CHV
12:28 p.m.