Hydrological Analysis: Bed Slope/Longitudinal Slope/ Stream
Hydrological Analysis: Bed Slope/Longitudinal Slope/ Stream
HYDROLOGICAL ANALYSIS
[C] Methodology
Long Section of River/Nala along Lowest Bed
Slope = 0.005
CONSTRUCTION OF BRIDGE AT CH 3245
HYDROLOGICAL ANALYSIS
CASE 2: Chainage at 0 m
R e d u c e d le v e l o f B e d
HFL = 437.89 m
Distance
Point Level (m) HFL
(m)
1 -13.00 437.89 m 437.89 m
2 -10.00 437.45 m 437.89 m
3 -5.00 435.90 m 437.89 m 439.00 m
438.00 m
4 0.00 434.69 m 437.89 m
437.00 m
5 5.00 435.80 m 437.89 m 436.00 m
435.00 m
6 10.00 437.50 m 437.89 m 434.00 m
7 13.00 437.80 m 437.89 m
-15.00 -10.00
433.00 m
-5.00 0.00 5.00 10.00 15.00
Distance
HFL = 437.64 m
HYDROLOGICAL ANALYSIS
CALCULATION OF DISCHARGE BY AREA VELOCITY METHOD
CASE 1: Chainage at 100m U/S
High Flood Level 439.240 m
Avg. Water
Segment Watted
REF. POINT DIST. FROM LEVEL Level Difference Length L Depth below Perimeter, P Area of Cross section, A
No. DATUM (m) (in m) with HFL (m) HFL , hi (in meters) (in sq meters)
(in meters)
CASE 2: Chainage at 0m
High Flood Level 437.890 m
Avg. Water
Segment Watted
REF. POINT DIST. FROM LEVEL Level Difference Length L Depth below Perimeter, P Area of Cross section, A
No. DATUM (m) (in m) with HFL HFL , hi (in sq meters)
(m) (in meters) (in meters)
HYDROLOGICAL ANALYSIS
CALCULATION OF DISCHARGE
1 Computation of discharge by different methods
a) Discharge from Catchment Area
By Dicken's Formula
Discharge Q = C*M^3/4
Where C = 16
The Catchment Area 'M' = 2.889 Sq. Km
Q = 35.46 Cum/Sec
b) Area velocity method
Discharge (Q) = AV
(Assumed as per Table : 5.1 of IRC: SP -13)
Nature of Surface Assumed - Widening, Some Pools and shoals, Clean, Lower Stages More
Ineffective Slope and some weeds and stony Section
AFFUX CALCULATION :
Average velocity of flow (V) = 1.490 m/sec.
Unobstructed area of flow (A) = 39.855 Sqm (Area of flow at proposed bridge location)
Obstructed area of flow (a) = 116.206 Sqm
Since the water way provided is more than the desired waterway afflux calculation is not necessary
Recommendation
Design Discharge = 61.50 m3/Sec
Design HFL = 437.890 m
Required Vertical clearance = 1.000 m
Provided Soffit Level = 438.890 m