SCHEDULE OF LOADS
C C
5W PL 5W PL C1 5W PL
5W PL 5W PL 5W CL
12W CL 12W CL CIRCUIT LIGHT CONV. CIRCUIT
NO. DESCRIPTION WATTS VOLTS AMPS WIRE SIZE CONDUIT SIZE
5W CL 12W CL 1
S S
1 12W CL 1
S OUTLET OUTLET PROTECTION
12W CL
1
3S
S
3S 12W CL 1 11 LED LIGHTING FIXTURES 83 230 0.36 15 2-2.0MM2 THHN 1/2'' Ø PVC PIPE
1
S
B B
1 C2 5W PL 2 8 LED LIGHTING FIXTURES 54 230 0.23 15 2-2.0MM2 THHN 1/2'' Ø PVC PIPE
5W PL 5W PL S
5W PL 5W PL 5W PL
A A
3 7 CONVENIENCE OUTLET 1400 230 6.09 20 2-3.5MM2 THHN 3/4'' Ø PVC PIPE

4 5 CONVENIENCE OUTLET 1000 230 4.35 20 2-3.5MM2 THHN 3/4'' Ø PVC PIPE
8 7 6 5 4 3 2 1

5 1 1 REFRIGERATOR OUTLET 300 230 1.30 20 2-3.5MM2 THHN 3/4'' Ø PVC PIPE

6 1 1 CONVENIENCE OUTLET 1000 230 4.35 30 2-5.5MM2 THHN 3/4'' Ø PVC PIPE

7 SPARE
1 GROUND FLOOR LIGHTING PLAN 8 SPARE
E-1 SCALE: 1:1OO

TOTAL 19 14 3837 230 16.68 100 2-30MM2 THW 1 1/4''Ø RSC

8 7 6 5 4 3 2 1

C C

C4

C5

C3
B C6 B

A A

SINGLE LINE DIAGRAM


8 7 6 5 4 3 2 1 FROM NORECO
ELECTRICAL SYMBOLS
M 2-30MM2 THW IN 1 1/4''Ø RSC
2 GROUND FLOOR POWER PLAN
E-1 SCALE: 1:1OO
PINLIGHT CICRCUIT HOMERUN

CIRCULAR LAMP M KILOWATTHOUR METER


ELECTRICAL SPECIFICATIONS SINGLE RECEPTACLE CONVENIENCE OUTLET PANEL BOARD
100A, MAIN
CIRCUIT LINE
15A 15A DOUBLE RECEPTACLE CONVENIENCE OUTLET
1.ALL ELECTRICAL WORKS AND INSTALLATIONS HEREIN SHALL BE IN ACCORDANCE TO R.A. 7920 OTHERWISE KNOW AS THE NEW SWITCH LINE
ELECTRICAL ENGINEERING LAW AND CONFORM WITH THE LATEST APPROVED EDITION OF THE ELECTRICAL CODE, RULES, AND 1 2 S
1 ONE GANG SWITCH
REGULATIONS OF THE LOCAL AND NATIONAL AUTHORITIES CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCE. S
20A 20A 2 TWO GANG SWITCH

2.ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE FOR BOTH PURPOSE AND LOCATION INTENDED. 3 4 S
3 THREE GANG SWITCH
20A 30A
3.NO BRANCH OF CIRCUIT WILL HAVE A LOAD OF MORE THAN 80% OF ITS RATING .
5 6
4.ADEQUATE AND EFFECTIVE GROUNDING SHALL BE PROVIDED FOR ALL METALIC CONDUIT CABINETS.

5.ALL ELECTRICAL WORKS AND INSTALLATION WHEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY ELECTRICAL SPARE 7 8 SPARE
ENGINEER.

6.NO REVISION IN THE DESIGN SHALL BE DONE WITHOUT THE PRIOR KNOWLEDGE AND APPROVAL OF THE DESIGNER AND THE OWNER,
ANY SUCH REVISION DONE WITHOUT THE APPROVAL SHALL CAUSE THE RESPONSiBILITY OF THE DESIGNER TO CEASE AS A WHOLE. GROUND ROD

PEE CONSULTANT SEAL PROJECT OWNER REVISION DATE SHEET CONTENTS SHEET NO.

LIGHTING LAYOUT
POWER LAYOUT
A PROPOSED SINGLE DETACHED RESIDENTIAL BUILDING MS. VIRGINIA T. MORTE
ELECTRICAL SPECIFICATIONS E-1
PTR NO. PRC REG. No.
SCHEDULE OF LOADS
SINGLE LINE DIAGRAM
DATE ISSUED TIN ELECTRICAL SYMBOLS
PLACE ISSUED IAPOA NO. LOCATION: MAAYONG TUBIG, DAUIN, NEG. OR. ADDRESS: DONGGA MALAUNAY, VALENCIA, NEG. OR.