DIAC/DIFC/DSFC Single Phase Digital O/C
Range/ 1A 5A
step Rated Rated
TOC range 0.1 to 3.18 0.5 to 15.9 52 DIAC
step 0.02 A 0.1 A DIFC
IOC range 0.2 to 31.8 1 to 159 DSFC
step 0.2 A 1A
IOC delay 50 to 400 ms
step 25 ms
Time Dial 0.5 to 9.9 0.5 to 9.9
51 AUXILIARY
2 www.GEindustrial.com/Multilin
DIAC/DIFC/DSFC Single Phase Digital O/C
Features
IOC target, provides latched
TOC target, provides latched indication of operation
indication of operation
TIME Power Management INST
Model DIFCA5A
Rated Current 5 Amperes
Instruction Book GEK-105570
Test lever for manually
tripping IOC outputs
Test lever for manually
tripping TOC outputs Pull Pull
and 0 IAC51 8 IEC Inverse
and
lift
to
1
2
3
IAC53
55-ST
57-MT
9
10
11
IEC Very Inv.
IEC Ext. Inv.
IEEE Inverse FREQ RESET
lift
to Dials for setting IOC
Test 4
5
6
66-LT
75-ST
AC77
12
13
14
IEEE Very Inv.
IEEE Ext. Inv.
DefiniteTime
0
1
2
50HZ
50HZ
60HZ
TIME
INST
TIME
Test
pickup current
3 60HZ
Curve Select
8 5 6 80 8
pickup current
6 5 6 8 5 6
4 4 4 4
10
6
10
10
10
40 60
2
6
4 6
0
7 8
7 8
7 8
2 3
2 3
120 14
2 3
12
12
12 14
4
4
8
2
14
14
3
2
9
0
9
2
9
20
0
1 1 1
0 0 0 0 0 0 0 0
TOC Time Pickup IOC IOC
Pickup-Amps Dial Pickup-Amps Delay Time dial for IOC delay
Typical Wiring
USE HEAVY
5 6 USE HEAVY
5 6
GAUGE WIRE SURGE GAUGE WIRE SURGE
4 GROUND 4 GROUND
CURRENT CURRENT
INPUT INPUT
SWITCHGEAR 2 NO SWITCHGEAR 2 NO
GROUND BUS GROUND BUS
1 COM TRIP TRIP
OUTPUT RELAYS
1 COM
OUTPUT RELAYS
3 NO 3 NO
GE Power Management GE Power Management
7 NO 11 NO
8 NO DIAC or DSFC 12 NO DIFC
Overcurrent Relay Overcurrent Relay
AUX AUX
9 NO 13 NO
10 NO 14 NO
718750A4.CDR
NOTES:
1) Relay contact state shown in the non operative state
2) Terminal numbers shown for all 3 models
GUIDEFORM SPECIFICATIONS
Feeder protection shall be provid- GE, IEEE, and IEC standards LED pickup indicator shall be
ed using digital microprocessor, ■ latched targets for IOC and TOC located on the front panel.
self-powered, single phase which operate on trip circuit
All settings shall be visible
relays. Protection features shall current
through the unit’s cover. Targets
include: The reset characteristic can be may be reset without removing
■ instantaneous overcurrent selected to either emulate an the cover.
(50 or 50G) induction disk or fast reset. The
The relay shall be available as a
■ time overcurrent (51 or 51G) system frequency can be selected
complete drawout case and
■ independent TOC and IOC pickup to be 50 or 60 Hz.
cradle assembly.
and timing settings Two trip circuit test levers shall
■ 16 selectable TOC curves meeting be located on the front panel. An
www.GEindustrial.com/Multilin 3
DIAC/DIFC/DSFC Single Phase Digital O/C
Dimensions
INCHES
(mm)
CUTOUT
GLASS 4 x 0.25"Dia.
STUDS FOR (6)
1.13" SURFACE
MTG. 3.0"
6.62" (3) 5.69"
10.31" (76)
(168) (144)
(262)
7.00" 2.25"
(178) (57)
6.69"
CUTOUT (170)
GLASS 4 x 0.25"Dia.
STUDS FOR (6)
1.13" SURFACE
MTG. 3.0"
6.62" (3)
(76) 5.69"
(168) 10.31"
(144)
(262)
6.75"
6.19"
(171)
(157)
7.38"
(187)
CUTOUT
GLASS
0.88" 3.0"
6.13" (22) (76) 5.13"
(154) 10.88" 4 x 0.25"Dia.
(130)
(276) (6)
718753A3.DWG
4 www.GEindustrial.com/Multilin
DIAC/DIFC/DSFC Single Phase Digital O/C
Technical Specifications
METERING ENVIRONMENTAL
Frequency: 50 or 60 Hz Ambient Temperature Range:
Rated Current: 1 or 5 A Storage: -40°C to +85°C
Maximum Permissible Current: Operation: -40°C to +70°C
Continuous: 3 times rated Humidity: Up to 95% without condensation
I 2 t: (1 A) 1520
(5 A) 38000 TYPE TESTS
Three Sec: 50 times rated Insulation Withstand Test:
One Sec: 100 times rated Impulse Voltage: 5 kV peak, 1.2/50 µsec, 0.5 J
Per IEC255.5, Class III
INPUTS Surge Withstand Capability:
BURDEN Fast Transient: Per ANSI C37.90.1
AC Current Circuit: Input current Burden Per IEC 255.22.4, Class IV
10% of rated 0.45 VA Oscillatory: Per ANSI C37.90.1
100% of rated 2.6 VA Per IEC 255.22.1, Class IV
Radio Frequency Interference:
25 MHz - 1 GHz keyed every
OUTPUTS
1 MHz for 2 sec
OUTPUT CONTACT RATINGS Per ANSI C37.90.2 & IEC 801.3
Load Type Voltage Cont 1 Sec Make & Carry Break Max. Load Electrostatic Discharge: Per IEC 801.2
DC 125 10 A 30 A 0.5 A 60 W
Resistive 250 0.3 A APPROVALS
DC 125 0.25 A UL, CUL: UL listed for USA and Canada
Inductive 250 10 A 30 A 0.15 A 50 VA
L/R = 40 ms 370 0.05 A NOTE: Suitable for Cap-Trip Devices
Specifications subject to change without notice.
5
Burdens
Burdens for the overcurrent units are listed in table below. Burdens
decrease with increasing current above minimum setting, due to the
power supply shunting in the power supply circuit. Since the power
supply is the major portion of the burden, the burden for a given input
current will be constant, irrespective of pick-up settings on both TOC and
IOC units.
Ordering
D**** * *
I ACA IAC SI Case
I FCA IFC CI Case
S FCA SFC VI Case
1 1 A nominal current
5 5 A nominal current
B Revision level
Accessories Order online –
Test device for DIAC/DSFC, 20 point XLA12A1
Test device for DIAC/DSFC, 10 point XLA13A1
save time
Test device for DIFC, 28 point XCA28A1
Current probe for DIFC XCA11A2 www.GEindustrial.com/pm