Professional Documents
Culture Documents
Calculation Report
Calculation Report
Calculation Report
1.1Introduction
The design of plumbing systems shall adopt the concepts of value optimization to ensure
providing the project with high quality services with optimal cost.
The plumbing calculation should be read in conjunction with the project drawings, design reports
and project specifications.
1.2Scope
The proposed plumping schematic report with primarily calculation involving Domestic Water
System including cold and hot water System. The calculations are based on specific codes and
local regulations.
1.3Reference Documents
All plumbing systems are designed in accordance with the Qatar construction specification
guidelines and the requirements of governmental agencies/authorities having jurisdiction over
work at the project.
Additionally, all plumbing systems are designed based on the codes and standards in Table1
Table 1
1.4Abbreviations and Units
Refer to table 2
1.5Design Parameter
Refer to table 3
1.6System description:
Main water storage tank (RCC) will be proposed externally beside external fence with filling point outside
the fence (for tanker filling to be transferred –by transfer pump set-to the internal ground water tanks for the
building, then lift to the roof water tanks which Booster to each Fixture’s Unit. The design criteria
implemented in this study is based on the above design standards with the following design criteria for the
domestic water system.
1.6.1 Ground and roof water tanks
The ground water tanks for the building will be R.C.C , roof water tanks for the building will be Roto Mould
type
capacity of the ground/roof tanks are as per the following:
o Daily water consumption shall be as per kahramaa regulation (refer to appendix –A)
o Assume numbers of staff =650 staff (as per Furniture).
o No of customer = 25% of staff = 165
o Total No of people = 813
o daily water consumption per staff=70 liter
o daily domestic water demand for all staff=70x815=57050 liters= 15070gallon
o Two-day storage (as per kahramaa regulation) = 30140 gallon
o selected ground domestic water tank will be 2.0 tanks 72m3 with each
o selected Roof water tank will be 4.0 tanks with 4000 gallon each
The lift and booster pump have been proposed to transfer the
domestic water to the roof tank and to deliver the water to the
fixture, pumps data calculation is as per the following:
o The formula below for calculate these losses over a given length of pipe.
o hL = 10.67 * L * Q1.852 / C1.852 / d4.87 (SI Units)
Where,
o hL represents friction head loss (meters of H2O),
o L represents length of pipe (meters),
o d represents internal pipe diameter (meters),
o Q represents flow rate through the pipe (cubic meters per second), and
o C represents the Hazen-Williams coefficient.
- The domestic lift pump set hydraulic loss calculation is done based on the most critical path from the
transfer pump set which locate 1st basement of the building until the high level of the Roof tank of
building, with counting the pipe size length within the site, all valves and fittings to determine the
hydraulic pressure loss. (Contractor shall recalculate and verify the required head as per site
condition)
- The selected pipe dia at 1.0m/s = 160mm from the chart
- The length of the pipe = 65m
- The equivalent length for fitting and valves =50% of total length of the pipe = 33
- The total pipe length = 95m
- The friction losses = 2.208m
The pump head is equal to = (vertical head + friction losses + residual pressure) 10%
So, the lift pump set which located outside the building will be triplex single speed transfer pumps set with
100gpm flow and 62 m head (each) is designed to lift the domestic water from ground tank to roof tank,
three pumps will operate with one stand by pump.
Table for Estimating Demand from IPC (refer to Appendix B&C) demand water flow needed will be
165.6 GPM +20% safety factor =200 gpm (Approximately)
Pump Head calculation
o The formula below for calculate these losses over a given length of pipe.
o hL = 10.67 * L * Q1.852 / C1.852 / d4.87 (SI Units)
Where,
o hL represents friction head loss (meters of H2O),
o L represents length of pipe (meters),
o d represents internal pipe diameter (meters),
o Q represents flow rate through the pipe (cubic meters per second), and
o C represents the Hazen-Williams coefficient.
- The domestic booster pump set hydraulic loss calculation is done based on the most critical path from the
booster pump set which locate at the roof of the building until the last fixture at the 4 th basement-floor
toilet With counting the pipe size length within the site, all valves and fittings to determine the hydraulic
pressure loss. (Contractor shall recalculate and verify the required head as per site condition)
- The selected pipe dia at 1.0m/s = mm from the chart
- The selected pipe dia at 1.0m/s = 160mm from the chart
- The length of the pipe = 180m
- The equivalent length for fitting and valves =50% of total length of the pipe = 90
- The total pipe length = 270m
- The friction losses = 6.083m
The pump head is equal to = (vertical head + friction losses +filter loss+ residual pressure) 10%
Vertical head = -2.0 m
Friction losses = 6.083m
Residual pressure (max flow pressure required at water closet) = 20 psi =14 m.
Multimedia filter = 10m
The pump head = (-2+6.083+14+10) x1.1=31 m
So, the booster pump set which located above the roof of the buildings will be triplex variable speed with
100gpm flow and 31m head (each) is designed to serve the building with the domestic water needs and to
cover the peak load. Variable frequency drive controller is selected for proper pump operation and to cover
the building demand curve within the day. Three pumps will operate with one stand by pump.
Refer to ASHRAE Applications Handbook, 2003, Chapter 45, Table 9) refer to Appendix D the possible
maximum demand for the respective fixtures shall be as per table 7a,
Table 7a
Hot Water Demand per Fixture at a final temperature of toilet (60°C), GPH
Numbe
Fixture type GPH r of Total GPH
Fixture
1 WB 6 193 1158
2 KS 20 10 200
Total GPH 1358
Demand factor 0.3
Storage capacity factor 2
Required Heater Capacity (gallons) 815
Selected Heater Capacity (litter) 3085
Table 7a
2.1. Surface Rainwater system
2.1.1. Introduction
- The system shall be designed to safely remove and dispose of surface water build up from roofs to
prevent the ingress of water into the development in accordance with the recommendation of rainfall
data applicable to Doha.
The rainwater is collected from the building roofs through separate network, the following criteria is
applying for the rainwater calculation:
- Where possible, all rainwater pipes will be in accessible positions to assist future maintenance. All
horizontal pipe work located in voids or ceilings will be kept to a minimum and will be installed to
take the shortest practical route. Running rainwater pipes above the office rooms shall be avoided.
- All rainwater pipes passing through compartment floors and walls will be fitted with fire sleeves and
sealed as necessary.
- The Roof floor is divided to Multiple Areas with slope 1 %-0.67% toward the roof drain points, with
taken into consideration the location of outdoor AC units, Split Outdoor Units and building shafts on
roof, which effect on the Rainwater collection Area, location of Roof Drains and Number of provided
roof drains.
Table 12
-selected riser sizes refer to Appendix F
The irrigation water tank capacity is 3330gallon (12.6m3) and time to considered to fill the tank
120min
So the capacity of pump flow rate = 28gpm
o The formula below for calculate these losses over a given length of pipe.
o hL = 10.67 * L * Q1.852 / C1.852 / d4.87 (SI Units)
Where,
o hL represents friction head loss (meters of H2O),
o L represents length of pipe (meters),
o d represents internal pipe diameter (meters),
o Q represents flow rate through the pipe (cubic meters per second), and
o C represents the Hazen-Williams coefficient.
- The domestic booster pump set hydraulic loss calculation is done based on the most critical path from the
booster pump set with counting the pipe size length within the site, all valves and fittings to determine the
hydraulic pressure loss. (Contractor shall recalculate and verify the required head as per site condition)
- The selected pipe dia at 1.0m/s = 50mm from the chart
- The length of the pipe = 50m
- The equivalent length for fitting and valves =50% of total length of the pipe = 25
- The total pipe length = 75m
- The friction losses = 1.467m
The pump head is equal to = (vertical head + friction losses + residual pressure) 10%
Vertical head = 12.0 m
Friction losses = 1.467m
Residual pressure (assume 3.0 m) =3 m.
Filtration section loss = 10m
The pump head = (12+1.467+3+10) x1.1=30 m
o The formula below for calculate these losses over a given length of pipe.
o hL = 10.67 * L * Q1.852 / C1.852 / d4.87 (SI Units)
Where,
o hL represents friction head loss (meters of H2O),
o L represents length of pipe (meters),
o d represents internal pipe diameter (meters),
o Q represents flow rate through the pipe (cubic meters per second), and
o C represents the Hazen-Williams coefficient.
- The domestic booster pump set hydraulic loss calculation is done based on the most critical path from the
booster pump set with counting the pipe size length within the site, all valves and fittings to determine the
hydraulic pressure loss. (Contractor shall recalculate and verify the required head as per site condition)
- The selected pipe dia at 1.0m/s = 40mm from the chart
- The length of the pipe = 200m
- The equivalent length for fitting and valves =50% of total length of the pipe = 100
- The total pipe length = 300m
- The friction losses = 11.844m
The pump head is equal to = (vertical head + friction losses + residual pressure) 10%
Vertical head = 10.0 m
Friction losses = 11.844m
Residual pressure (assume 3.0 m) =3 m.
Multimedia filter = 10m
The pump head = (10+11.844+3+10) x1.1=38 m
3. Drainage system
3.1. Introduction
The design of plumbing systems shall adopt the concepts of value optimization to ensure
providing the project with high quality services with optimal cost.
The plumbing calculation should be read in conjunction with the project drawings, design reports
and project specifications.
3.2. Scope
The proposed plumping schematic report with primarily calculation involving drainage System
including sewage and rain water System. The calculations are based on specific codes and local
regulations.
BRITISH Gravity drainage systems inside buildings - Part2: Sanitary pipe work layout and
STANDAR calculation
D
IPC International Plumbing Code 2015 Edition. - Drainage and Vent System.
- Storm water system.
Table 6
3.4. Abbreviations and Units
Refer to table 7
Table 8
- Two Sanitary System (Soil and Waste), One Waste Pipe collects the waste from lavatories,
Shower, Pantry Sink, Janitor Sink, and Floor Drains, Another Soil Pipe collect the Drainage
from the WCs, The two pipes will discharged by gravity to the Sewage chambers/Manholes
which will be collected to the proposed main septic tank.
- Waste stack to be connected to sewage chamber via gully traps.
- Vent system to be provided for the waste & soil system. Vent piped exiting at roof level.
- Some toilet has not been provided with vent stack, A drainage stack shall serve as a single stack
vent system where the following condition are meet as per the IPC standard clause 917.2-2015
edition
1- stack size :
o as per Table 917.2 (IPC -2015 edition ) the maximum proposed drainage fixture units are 3.0 for soil
stack and 5.0 for waste stack which is complied with 4’’ stack
2- Branch size.
o All branch sizes have been complied as mentioned.
3- Length of horizontal branches
o Water closet connections are not greater than 1219 mm in length measured horizontally from the soil
stack.
o Fixture connections are not located greater than (3657 mm) in length, measured horizontally from the
waste stack.
4- Minimum vertical piping size from fixture. Complied
5- Sizing building drains and sewers are compiled as per IPC code
- Manholes and chambers at the head of each system shall include min 75mm or (1/2 x d) piped
vents fixed to adjacent walls and exiting at roof level
- Peak flow Rates will be calculated following Fixture load units, which will be converted to
Flow Rates for the Building.
- The design criteria implemented in this study is based on the above design standards with the
following design criteria for the foul sewage system.
Corrugated Metal 60
Fiber 140
Glass 130
Steel, corrugated 60