01M Equivalent Circuit

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 43

Prepared by

Dr. Mohammad Abdul Mannan


Associate Professor, Department of EEE
American International University – Bangladesh (AIUB)
Equivalent Circuit of Synchronous
Generator(Alternator)/Motor
Eg: Generated emf at no load due to the field excitation
Xar: Reactance due to the armature reaction known as fictitious reactance.
Xl: Reactance due to the leakage flux known as leakage reactance or potier
reactance.
Ra: Resistance due to armature winding known as armature resistance.
Vt: Terminal voltage of generator

Vs: Supply voltage of generator


Em: Back emf I: Current

Synchronous Generator/Alternator Synchronous Motor


Dr. Mohammad Abdul Mannan 2
Xs: Summation of Xar and Xl known as synchronous reactance.
Xs:= Xar + Xl

Synchronous Impedance: Zs=Ra+jXs

Impedance Diagram Reactance Diagram


Dr. Mohammad Abdul Mannan 3
Transformer
Definition: The transformer is a static device which transfers
electrical energy from one circuit to another circuit without
changing of frequency.

Features of a Transformer
‰ Transfer electrical energy from one circuit to another circuit
by changing voltage and current
‰ Frequency cannot be changed
‰ Energy transformation is accomplished by electromagnetic
induction
‰ Electrical circuits are magnetically coupled no direct electric
connection
‰ Efficiency is high and mantainance is simpler since there has
no rotating parts

Dr. Mohammad Abdul Mannan 4


Main Components of a Transformer
™ The magnetic core
™ Primary and secondary windings
™ Insulation of windings
™ Lead and tapping for coils with their supports, terminals and
terminal insulator
™ Tank, oil, cooling arrangement etc.

Application of Transformer
9 Stepping-up of voltage
9 Stepping-down of voltage
9 Electrical Isolation
9 Impedance matching
9 Link between AC and DC systems
9 Instrument extension

Dr. Mohammad Abdul Mannan 5


Classification of Transformer
Transformer can be classified according to the following ways:
Based on Number of Phases
™ Single-phase transformer
™ Three phase transformer
Based on Relative Position (Construction) of Winding and
Core
‰ Core type transformer
‰ Shell type transformer
Based on Number of Winding Per Phase
¾ One winding per phase
¾ Two winding per phase
¾ Three winding per phase
Based on Volt-Ampere and Voltage Ratings
o Low voltage transformer [VHV < 1.1 kV]
o Medium voltage transformer [1.1 kV ≤VHV < 11 kV]
o High voltage transformer [VHV ≥ 11 kV]
Dr. Mohammad Abdul Mannan 6
Based on Service Conditions
ƒ Power transformer
ƒ Distribution transformer
Instrument Transformer
9 Current transformer
9 Potential transformer
Based on Method of Cooling
• Air Natural
• Air Blast
• Oil Natural
• Oil Blast
• Forced Oil Cooling
• Oil and Water Cooled
• Forced Oil and Water Cooled
Dr. Mohammad Abdul Mannan 7
Current (or Series) Transformer (CT)
¾ Used to measure current in high-current ac circuit with
low-range ammeters
¾ Step up the voltage
¾ Step down the current
¾ Has a primary coil with one or more turns of thick wire
connected in series with the line whose current is to be
measured
¾ Has a secondary coil with a large number of turns of fine
wire and connected across the ammeter terminals.
¾ If the current transformer has primary to secondary
current ratio (I1/I2) of 100:5, then it steps up the voltage 20
times whereas it steps down the current to (1/20) th of its
actual value.

Dr. Mohammad Abdul Mannan 8


¾ One of the most commonly used current transformer is the one
known clamp-type or clip-on type.
¾ Since the ammeter resistance is very low, the current
transformer normally works short circuited.

The secondary of a current transformer should never be left open


under any circumstances. If this not done, then due to the absence
of counter amp-turns of the secondary, the unopposed primary
mmf will set up an abnormally high flux in the core which will
produce excessive core loss with subsequent heating and a high
voltage across the secondary terminals.
Dr. Mohammad Abdul Mannan 9
Potential (or Voltage) Transformer (PT)
¾ Used to measure high voltage in high-voltage ac circuit with
low-range voltmeter
¾ Step down the voltage
¾ Step up the current

For safety, the secondary should be completely insulated from


the high-voltage primary and should be, in addition, grounded
for affording protection to the operator.

Dr. Mohammad Abdul Mannan 10


Equivalent Circuit of Transformer

R1, Xl1, I1, V1, E1: primary side resistance, leakage reactance,
current, voltage, and counter (or self induced) emf, respectively.
R2, Xl2, I2, V2, E2: secondary side resistance, leakage reactance,
current, voltage, and counter (or self induced) emf, respectively.
Rc (or R0 or Rm), Xm (or X0): core loss resistance, mutual
inductance, respectively.
I0, Iµ (or Ic) Iw: no-load current, magnetizing current, and
working or core loss current, respectively.

Dr. Mohammad Abdul Mannan 11


Voltage Transformation Ratio: K=N2/N1=E2/E1=V2/V1
Secondary quantities referred to primary:
V2′= V2/K; Xl2′=Xl2/K2; R2′=R2/K2

Impedance Diagram

Neglect Core Loss


i.e. Rc is very large

Dr. Mohammad Abdul Mannan 12


Assuming, Xm is very large

Simplified Impedance Diagram Reactance Diagram


Dr. Mohammad Abdul Mannan 13
High-voltage (HV) or high tension (HT) side impedance
referred to low-voltage (LV) or low-tension (LT) side

⎛ ⎞2 ⎛ ⎞2
V ⎜ ⎟ ⎜ N ⎟
Z =Z HV

⎜ ⎟ =Z
⎟ ⎜

HV ⎟

HV LV V ⎟⎟
⎜⎜ LV⎜⎜ N
LV ⎠
⎝ ⎝ LV ⎟⎟⎠

Low-voltage (LV) or low tension (LT) side impedance


referred to high-voltage (HV) or high-tension (HT) side

⎛ 2 ⎞2
V ⎞⎟


⎜ N ⎟
Z =Z LV

⎜ ⎟ =Z
⎟ ⎜

LV ⎟

LV HV V ⎜⎜⎟⎟ HV⎜⎜ N
HV ⎠
⎝ ⎝ HV ⎟⎟⎠

Dr. Mohammad Abdul Mannan 14


Calculation of Three Phase Rating of a
Transformer from the Given Single Phase Rating
In a power system, the Y-connection of a three-phase transformer
always considered as high voltage side. The given voltage rating
of a three-phase transformer is always line voltage rating.
If the single phase ratings are: 11 kV/6.6 kV, 100 MVA
The rating for three-phase transformer are:
For Y-Y connected transformer are:
(√3×11)kV/(√3×6.6)kV or 19.053kV/11.432kV and 3×100 MVA

For Y-Δ or Δ -Y connected transformer are:


(√3×11)kV/6.6kV or 19.053kV/6.6kV and 3×100 MVA

For Δ -Δ or Δ -Y connected transformer are:


11kV/6.6kV and 3×100 MVA
Dr. Mohammad Abdul Mannan 15
Parameters of Transmission (TX) Line
The basic transmission-line parameters are:
1. Series resistance
2. Series inductance (or inductive reactance)
3. Shunt capacitance (or capacitive reactance)
4. Shunt conductance (or admittance)

Series Resistance (R)


Series resistance accounts for copper (or ohmic or I2R) losses.
The resistance of a conductor at a specified temperature is
Rdc=ρl/A
Resistance of a conductor depends of the following factors:
• Spiraling
• Temperature
• Frequency (due o skin effect)
• Current magnitude – magnetic conductor
Dr. Mohammad Abdul Mannan 16
Series inductance (or inductive reactance) (XL)
Series inductive reactance gives rise to series voltage drops along the
line.
The inductance of a magnetic circuit that has a constant permeability µ
can be obtained by determining the following:
ƒ Magnetic field intensity H from Ampere’s Law
ƒ Magnetic flux density B (B=µH)
ƒ Flux linkage λ
ƒ Inductance from flux linkage per ampere (L=λ/I)

Shunt Capacitance (C) (or Capacitive Reactance or susceptance,


Bc )
Shunt capacitive reactance gives rise to line-charging current.
The capacitance between conductors in a medium with constant
permittivity ε can be obtained by determining the following:
o Electric field strength E, from Gauss’s Law
o Voltage between conductors
o Capacitance from charge per unit volt (C=q/V)
Dr. Mohammad Abdul Mannan 17
Representation of Transmission Line
Transmission-line are three types:
™ Short-Transmission Line (less than 80 km)
™ Medium Transmission Line (from 80 to 250 km)
™ Long Transmission Line (more than 250 km)

Short-Transmission Line (less than 80 km)


For a short-transmission line, shunt capacitance is so small that it
can be omitted entirely with little loss of accuracy, and we need to
consider only the series resistance and the series inductance for
the total length of the line.

Dr. Mohammad Abdul Mannan 18


Shunt conductance (or admittance) (G)
Shunt conductance accounts for real power (V2G) line losses due to
leakage currents between conductors or between conductors and
ground.
Shunt conductance of overhead line is usually neglected since this
loss is very small compared to copper loss.
This power loss is due to leakage currents at insulators and to
corona.
Corona occurs when a high value of electric field strength at a
conductor surface causes the air to become electrically ionized and
to conduct.
The real power loss due to corona, called corona loss, depends on
meteorological conditions, particularly rain, and on conductor
surface irregularities.

Series impedance is including the series resistance and series


inductive reactance.
Dr. Mohammad Abdul Mannan 19
Medium Transmission Line (from 80 to 250 km)
A medium-length line can be represented sufficiently well by
series resistance, series inductance as lump parameters with half
the capacitance to neutral of the line lumped at each end of the
equivalent circuit.
R X
Z
Nominal π circuit G/2 Bc/2 G/2 Bc/2
Y/2 Y/2
R/2 X/2 R/2 X/2
Z/2 Z/2
Nominal T circuit
G Y Bc

Dr. Mohammad Abdul Mannan 20


Long Transmission Line (more than 250 km)
The exact solution of any transmission line and the one required
for a high degree of accuracy more than approximately 150 mile
long must consider the fact that the parameters are not lumped
but are distributed uniformly throughout the length of the line.

V + I Zc γx V − I Zc −γx
V= R R e − R R e Zc = z / y
2 2
V / Zc + I γx V / Zc − I −γx γ = zy =α + jβ
I= R Re − R Re
2 2
Dr. Mohammad Abdul Mannan 21
Zc : Characteristic impedance of the line
γ : propagation constant
α : attenuation constant
β : phase constant

Equivalent-π circuit of a long transmission line


Dr. Mohammad Abdul Mannan 22
One Line or Single Line Diagram
A one-line or single-line diagram is a simplified notation for
representing a three-phase power system.
A simplified diagram of an electrical system is called one-line or
single-line diagram.
The purpose of the one-line diagram is to supply in concise form
the significant information about the power system.
The one-line diagram has its largest application in power flow studies.
Electrical elements such as circuit breakers, transformers, capacitors, bus
bars, and conductors are shown by standardized schematic symbols as shown
in the following Table 1.
Instead of representing each of three phases with a separate line or terminal,
only one conductor is represented. It is a form of block diagram graphically
depicting the paths for power flow between entities of the system.
Elements on the diagram do not represent the physical size or location of the
electrical equipment, but it is a common convention to organize the diagram
with the same left-to-right, top-to-bottom sequence as the switchgear or other
apparatus represented.
Dr. Mohammad Abdul Mannan 23
Why one line diagram?
™ Power systems are extremely complicated
™ Geographically spread system
™ Three phase (3φ) System

Characteristics of One-Line Diagram


¾ Concise form of basic arrangement of Power System (PS)
¾ Not show the exact electrical connection
¾ Expressed in block diagram
¾ Diagram varies for different purposes

Why Grounding?
‰ Protect against the faulty Condition
‰ Grounded can be solid or through resistor or reactor/inductor.
This additional resistor or inductor doesn’t have any effect on
the steady-state operation
Dr. Mohammad Abdul Mannan 24
Table 1 Apparatus Symbols

Dr. Mohammad Abdul Mannan 25


Dr. Mohammad Abdul Mannan 26
Detailed Impedance Diagram

T1 TX Line

G1 M1
Eg1 Em1
Load
T1 TX Line

G1 Simplified
M1
Impedance
Eg1 Diagram Em1
Load
Dr. Mohammad Abdul Mannan 27
Reactance Diagram
If the impedance diagram is simplified by omitting
‰ All static loads
‰ All resistances
‰ The magnetizing current of each transformer
‰ All the capacitance of the transmission line
the impedance diagram reduces to the reactance diagram.

Dr. Mohammad Abdul Mannan 28


Draw the detailed Impedance Diagram, Simplified Impedance
Diagram and Reactance Diagram

T1 TX Line T2

Load
Neglecting Core Loss of Transformer
T1 TX Line T2

Dr. Mohammad Abdul Mannan 29


Neglecting Core Loss and Magnetizing Current of Transformer
TX Line

T1 T2

TX Line
T1 T2

Neglecting Core Loss, Magnetizing Current of Transformer


and Shunt Conductance (or Admittance) of Transmission Line
TX Line
T1 T2

Dr. Mohammad Abdul Mannan 30


Simplified Impedance Diagram
Neglecting Core Loss, Magnetizing Current of Transformer
and Shunt Conductance (or Admittance) of Transmission Line
TX Line
T1 T2

Reactance Diagram

T1 TX-Line T2

Dr. Mohammad Abdul Mannan 31


T1 TX-Line T2

1 2 3
Load A Load B
T1 TX-Line T2

1 2 3 T1 T2
Load A Load B
TX-Line
1 2 3

Dr. Mohammad Abdul Mannan 32


T1 TX-Line1 T2

1 2 3
Load A Load B
T3 TX-Line2 T4

Dr. Mohammad Abdul Mannan 33


T1 TX-Line1 T2

T3 TX-Line2 T4
1 2 3
Load A Load B

T1 TX-Line1 T2

1 2 T3 TX-Line2 T4 3

Dr. Mohammad Abdul Mannan 34


T1 Line 1 T2

1 2

T3 Line 2 Line 3 T4

3
Load

Dr. Mohammad Abdul Mannan 35


T1 Line 1 T2

T3 Line 2 Line 3 T4
1 2
Load
3

T1 Line 1 T2

T3 Line 2 Line 3 T4
1 2
3

Dr. Mohammad Abdul Mannan 36


Dr. Mohammad Abdul Mannan 37
T1 Line 1 T2

1 2

T3 Line 2 Line 3 T4

T5 T6

3 Load

Dr. Mohammad Abdul Mannan 38


T1 Line 1 T2

T3 Line 2 T5 T6 Line 3 T4
1 2
3
Load

T1 Line 1 T2

T3 Line 2 T5 T6 Line 3 T4
1 2
3
Load

Dr. Mohammad Abdul Mannan 39


Dr. Mohammad Abdul Mannan 40
Line 1 Line 2

T1 T4

T2 T3

2 Load 1
1 3
Line 3 Line 4

T5 T8

T6 T7

4 Load 2

Dr. Mohammad Abdul Mannan 41


T1 Line 1 T2 T3 Line 2 T4

2 T2
Load 1

T5 Line 3 T6 T7 Line 4 T8
1 3
4
Load 2

T1 Line 1 T2 T3 Line 2 T4

2
Load 1

T5 Line 3 T6 T7 Line 4 T8
1 3
4
Load 2

Dr. Mohammad Abdul Mannan 42


(a)

(b)
Draw the detailed impedance
diagram, simplified impedance
diagram, and reactance diagram.

(c)

(d) Home Work


Dr. Mohammad Abdul Mannan 43

You might also like