KU HOSPITAL

SUPPLY HVAC SYSTEM - MICROBIOLOGY LAB


HVAC Requirements

Room Room Pressure


Air Exchange Height(m Volume, Relationship
No: Use Rates, ACH RoomArea,(m2) ) (m3) Exhaust % Supply % (+/-) Recirculated%
1 Sample reception 6 15.3 2.7 41.31 120 100 (-)ve All Air Exhaust to Outdoor
2 Cultivate room 6 20.3 2.7 54.81 120 100 (-)ve All Air Exhaust to Outdoor
3 Sterile Room 6 10.2 2.7 27.54 120 100 (-)ve All Air Exhaust to Outdoor
4 Bacteria Identifications 6 27.6 2.7 74.52 120 100 (-)ve All Air Exhaust to Outdoor
5 Tuberclosis Lab 6 17.3 2.7 46.71 120 100 (-)ve All Air Exhaust to Outdoor
6 PCR analysis 6 19.4 2.7 52.38 120 100 (-)ve All Air Exhaust to Outdoor
7 Speciment Preparation 6 19.2 2.7 51.84 120 100 (-)ve All Air Exhaust to Outdoor
8 Reagent Preparation 6 20.4 2.7 55.08 120 100 (-)ve All Air Exhaust to Outdoor
9 Accessories 6 15.9 2.7 42.93 120 100 (-)ve All Air Exhaust to Outdoor
10 Clean Room 2 6 15.2 2.7 41.04 120 100 (-)ve All Air Exhaust to Outdoor
11 Half contaminated area 6 18.5 2.7 49.95 120 100 (-)ve All Air Exhaust to Outdoor
12 Serum bank 6 14.9 2.7 40.23 120 100 (-)ve All Air Exhaust to Outdoor
13 HIV Reference 6 47.5 2.7 128.25 120 100 (-)ve All Air Exhaust to Outdoor
!4 Clean Room 1 6 16.8 2.7 45.36 120 100 (-)ve All Air Exhaust to Outdoor
15 Corridor 6 45.1 2.7 121.77 120 100 (-)ve All Air Exhaust to Outdoor
323.6

ROOM LOCATION: MICROBIOLOGY LAB CLEAN ROOM 1


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 16.8 Room Volume (m3): 45.36 Flow rate (Q) m3/h: 181.44
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.05

Number of grilles: 1 Flow rate (Q) m3/s: 0.05 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 A 0.05 150 150 150 0.023 2.24


KU HOSPITAL
SUPPLY HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB CORRIDOR


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 45.1 Room Volume (m3): 121.77 Flow rate (Q) m3/h: 487.08
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.14

Number of grilles: 2 Flow rate (Q) m3/s: 0.07 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 B 0.07 175 150 150 0.023 3.01

2 C 0.12 200 200 175 0.035 3.37

ROOM LOCATION: MICROBIOLOGY LAB HIV REF. CENTER (HISTOLOGY)


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 47.5 Room Volume (m3): 128.25 Flow rate (Q) m3/h: 513
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.14

Number of grilles: 2 Flow rate (Q) m3/s: 0.07 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 D 0.07 175 150 150 0.023 3.17

2 E 0.19 240 225 225 0.051 3.74

3 F 0.26 275 250 250 0.063 4.17


KU HOSPITAL
SUPPLY HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB SERUM BANK


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 14.9 Room Volume (m3): 40.23 Flow rate (Q) m3/h: 160.92
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.04

Number of grilles: 1 Flow rate (Q) m3/s: 0.04 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 G 0.04 125 150 150 0.023 1.99

2 H 0.31 275 250 250 0.063 4.88

ROOM LOCATION: MICROBIOLOGY LAB ACCESSORIES ROOM


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 15.9 Room Volume (m3): 42.93 Flow rate (Q) m3/h: 171.72
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.05

Number of grilles: 1 Flow rate (Q) m3/s: 0.05 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 I 0.05 130 150 150 0.023 2.12

2 J 0.12 200 200 175 0.035 3.30


KU HOSPITAL
SUPPLY HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB CLEAN ROOM 2


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 15.2 Room Volume (m3): 41.04 Flow rate (Q) m3/h: 164.16
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.05

Number of grilles: 1 Flow rate (Q) m3/s: 0.05 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 K 0.05 130 150 150 0.023 2.03

2 L 0.16 230 225 200 0.045 3.58

ROOM LOCATION: MICROBIOLOGY LAB HALF-CONTAMINATED AREA


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 18.5 Room Volume (m3): 49.95 Flow rate (Q) m3/h: 199.8
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.06

Number of grilles: 1 Flow rate (Q) m3/s: 0.06 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 M 0.06 140 150 150 0.023 2.47

2 N 0.22 250 225 225 0.051 4.28

3 0 0.52 340 300 300 0.090 5.80


KU HOSPITAL
SUPPLY HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB SAMPLE RECEPTION


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 15.3 Room Volume (m3): 41.31 Flow rate (Q) m3/h: 165.24
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.05

Number of grilles: 1 Flow rate (Q) m3/s: 0.05 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 P 0.05 135 150 150 0.023 2.04

ROOM LOCATION: MICROBIOLOGY LAB CULTIVATE ROOM


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 20.3 Room Volume (m3): 54.81 Flow rate (Q) m3/h: 219.24
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.06

Number of grilles: 1 Flow rate (Q) m3/s: 0.06 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 Q 0.06 140 150 150 0.023 2.71

2 R 0.11 190 175 175 0.031 3.49


KU HOSPITAL
SUPPLY HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB STELILE ROOM


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 10.2 Room Volume (m3): 27.54 Flow rate (Q) m3/h: 110.16
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.03

Number of grilles: 1 Flow rate (Q) m3/s: 0.03 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 S 0.03 125 150 150 0.023 1.36

2 T 0.14 220 200 200 0.040 3.44

ROOM LOCATION: MICROBIOLOGY LAB BACTERIA IDENTIFICATION


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 27.6 Room Volume (m3): 74.52 Flow rate (Q) m3/h: 298.08
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.08

Number of grilles: 1 Flow rate (Q) m3/s: 0.08 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 U 0.08 165 150 150 0.023 3.68

2 V 0.22 250 225 225 0.051 4.35


KU HOSPITAL
SUPPLY HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB TUBERCLOSIS LAB


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 17.3 Room Volume (m3): 46.71 Flow rate (Q) m3/h: 186.84
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.05

Number of grilles: 1 Flow rate (Q) m3/s: 0.05 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 W 0.05 135 150 150 0.023 2.31

2 X 0.27 270 250 250 0.063 4.35

ROOM LOCATION: MICROBIOLOGY LAB REAGENT PREPARATION


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 20.4 Room Volume (m3): 55.08 Flow rate (Q) m3/h: 220.32
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.06

Number of grilles: 1 Flow rate (Q) m3/s: 0.06 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 Y 0.06 135 150 150 0.023 2.72


KU HOSPITAL
SUPPLY HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB SPECIMENT PREPARATION


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 19.2 Room Volume (m3): 51.84 Flow rate (Q) m3/h: 207.36
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.06

Number of grilles: 1 Flow rate (Q) m3/s: 0.06 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 Z 0.06 135 150 150 0.023 2.56

1 A1 0.12 200 200 175 0.035 3.39

ROOM LOCATION: MICROBIOLOGY LAB PCR ANAYLSIS AREA


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 19.4 Room Volume (m3): 52.38 Flow rate (Q) m3/h: 209.52
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.06

Number of grilles: 1 Flow rate (Q) m3/s: 0.06 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 B1 0.06 135 150 150 0.023 2.59

2 C1 0.18 240 225 225 0.051 3.50

3 D1 0.97 450 400 400 0.160 6.07


KU HOSPITAL
EXTRACT HVAC SYSTEM - MICROBIOLOGY LAB
Exhaust Requirements

Room Room Pressure


Air Exchange Height(m Volume, Relationship
No: Use Rates, ACH RoomArea,(m2) ) (m3) Exhaust % Supply % (+/-) Recirculated%
1 Sample reception 6 15.3 2.7 41.31 120 100 (-)ve All Air Exhaust to Outdoor
2 Cultivate room 6 20.3 2.7 54.81 120 100 (-)ve All Air Exhaust to Outdoor
3 Sterile Room 6 10.2 2.7 27.54 120 100 (-)ve All Air Exhaust to Outdoor
4 Bacteria Identifications 6 27.6 2.7 74.52 120 100 (-)ve All Air Exhaust to Outdoor
5 Tuberclosis Lab 6 17.3 2.7 46.71 120 100 (-)ve All Air Exhaust to Outdoor
6 PCR analysis 6 19.4 2.7 52.38 120 100 (-)ve All Air Exhaust to Outdoor
7 Speciment Preparation 6 19.2 2.7 51.84 120 100 (-)ve All Air Exhaust to Outdoor
8 Reagent Preparation 6 20.4 2.7 55.08 120 100 (-)ve All Air Exhaust to Outdoor
9 Accessories 6 15.9 2.7 42.93 120 100 (-)ve All Air Exhaust to Outdoor
10 Clean Room 2 6 15.2 2.7 41.04 120 100 (-)ve All Air Exhaust to Outdoor
11 Half contaminated area 6 18.5 2.7 49.95 120 100 (-)ve All Air Exhaust to Outdoor
12 Serum bank 6 14.9 2.7 40.23 120 100 (-)ve All Air Exhaust to Outdoor
13 HIV Reference 6 47.5 2.7 128.25 120 100 (-)ve All Air Exhaust to Outdoor
!4 Clean Room 1 6 16.8 2.7 45.36 120 100 (-)ve All Air Exhaust to Outdoor
15 Corridor 6 45.1 2.7 121.77 120 100 (-)ve All Air Exhaust to Outdoor
323.6

ROOM LOCATION: MICROBIOLOGY LAB CLEAN ROOM 1


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 16.8 Room Volume (m3): 45.36 Flow rate (Q) m3/h: 272.16
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.08

Number of grilles: 1 Flow rate (Q) m3/s: 0.08 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 A 0.08 190 175 175 0.031 2.47

ROOM LOCATION: MICROBIOLOGY LAB HIV REF. CENTER (HISTOLOGY)


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
KU HOSPITAL
EXTRACT HVAC SYSTEM - MICROBIOLOGY LAB
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 47.5 Room Volume (m3): 128.25 Flow rate (Q) m3/h: 769.5
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.21

Number of grilles: 2 Flow rate (Q) m3/s: 0.11 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 B 0.11 200 175 175 0.031 3.49

2 C 0.18 240 225 225 0.051 3.60

3 D 0.29 275 250 250 0.063 4.63

ROOM LOCATION: MICROBIOLOGY LAB ACCESSORIES ROOM


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 15.9 Room Volume (m3): 42.93 Flow rate (Q) m3/h: 257.58
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.07

Number of grilles: 1 Flow rate (Q) m3/s: 0.07 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 E 0.07 175 175 175 0.031 2.34


KU HOSPITAL
EXTRACT HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB CLEAN ROOM 2


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 15.2 Room Volume (m3): 41.04 Flow rate (Q) m3/h: 246.24
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.07

Number of grilles: 1 Flow rate (Q) m3/s: 0.07 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 F 0.07 175 175 175 0.031 2.23

2 G 0.14 225 200 200 0.040 3.50

ROOM LOCATION: MICROBIOLOGY LAB HALF-CONTAMINATED AREA


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 18.5 Room Volume (m3): 49.95 Flow rate (Q) m3/h: 299.7
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.08

Number of grilles: 1 Flow rate (Q) m3/s: 0.08 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 H 0.08 180 175 175 0.031 2.72

2 I 0.22 250 225 225 0.051 4.41

ROOM LOCATION: MICROBIOLOGY LAB SERUM BANK


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services
KU HOSPITAL
EXTRACT HVAC SYSTEM - MICROBIOLOGY LAB

Room Area (m2): 14.9 Room Volume (m3): 40.23 Flow rate (Q) m3/h: 241.38
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.07

Number of grilles: 1 Flow rate (Q) m3/s: 0.07 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 J 0.07 175 175 175 0.031 2.19

2 K 0.29 280 250 250 0.063 4.64

3 L 0.58 370 350 300 0.105 5.52

ROOM LOCATION: MICROBIOLOGY LAB CORRIDOR


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 45.1 Room Volume (m3): 121.77 Flow rate (Q) m3/h: 730.62
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.20

Number of grilles: 2 Flow rate (Q) m3/s: 0.10 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 M 0.10 190 175 175 0.031 3.31

2 N 0.78 410 400 350 0.140 5.59


KU HOSPITAL
EXTRACT HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB SAMPLE RECEPTION


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 15.3 Room Volume (m3): 41.31 Flow rate (Q) m3/h: 247.86
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.07

Number of grilles: 1 Flow rate (Q) m3/s: 0.07 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 O 0.07 175 175 175 0.031 2.25

ROOM LOCATION: MICROBIOLOGY LAB CULTIVATE ROOM


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 20.3 Room Volume (m3): 54.81 Flow rate (Q) m3/h: 328.86
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.09

Number of grilles: 1 Flow rate (Q) m3/s: 0.09 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 P 0.09 180 175 175 0.031 2.98

2 Q 0.16 230 200 200 0.040 4.01


KU HOSPITAL
EXTRACT HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB STELILE ROOM


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 10.2 Room Volume (m3): 27.54 Flow rate (Q) m3/h: 165.24
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.05

Number of grilles: 1 Flow rate (Q) m3/s: 0.05 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 S 0.05 125 150 150 0.023 2.04

2 T 0.21 220 200 200 0.040 5.15

ROOM LOCATION: MICROBIOLOGY LAB BACTERIA IDENTIFICATION


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 27.6 Room Volume (m3): 74.52 Flow rate (Q) m3/h: 447.12
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.12

Number of grilles: 1 Flow rate (Q) m3/s: 0.12 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 U 0.12 165 150 150 0.023 5.52

2 V 0.33 250 225 225 0.051 6.52


KU HOSPITAL
EXTRACT HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB TUBERCLOSIS LAB


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 17.3 Room Volume (m3): 46.71 Flow rate (Q) m3/h: 280.26
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.08

Number of grilles: 1 Flow rate (Q) m3/s: 0.08 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 W 0.08 135 150 150 0.023 3.46

2 X 0.41 270 250 250 0.063 6.53

ROOM LOCATION: MICROBIOLOGY LAB REAGENT PREPARATION


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 20.4 Room Volume (m3): 55.08 Flow rate (Q) m3/h: 330.48
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.09

Number of grilles: 1 Flow rate (Q) m3/s: 0.09 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 Y 0.09 135 150 150 0.023 4.08


KU HOSPITAL
EXTRACT HVAC SYSTEM - MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB SPECIMENT PREPARATION


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 19.2 Room Volume (m3): 51.84 Flow rate (Q) m3/h: 311.04
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.09

Number of grilles: 1 Flow rate (Q) m3/s: 0.09 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 Z 0.09 135 150 150 0.023 3.84

1 A1 0.18 200 200 175 0.035 5.09

ROOM LOCATION: MICROBIOLOGY LAB PCR ANAYLSIS AREA


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: EXTRACT DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 19.4 Room Volume (m3): 52.38 Flow rate (Q) m3/h: 314.28
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.09

Number of grilles: 1 Flow rate (Q) m3/s: 0.09 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 B1 0.09 135 150 150 0.023 3.88

2 C1 0.27 240 225 225 0.051 5.24

3 D1 #REF! 450 400 400 0.160 #REF!


KU HOSPITAL
MICROBIOLOGY LAB
Exhaust/ Supply Requirements

Room Room Pressure


Air Exchange Height(m Volume, Relationship
No: Use Rates, ACH RoomArea,(m2) ) (m3) Exhaust % Supply % (+/-) Recirculated%
1 Sample reception 6 15.3 2.7 41.31 120 100 (-)ve All Air Exhaust to Outdoor
2 Cultivate room 6 20.3 2.7 54.81 120 100 (-)ve All Air Exhaust to Outdoor
3 Sterile Room 6 10.2 2.7 27.54 120 100 (-)ve All Air Exhaust to Outdoor
4 Bacteria Identifications 6 27.6 2.7 74.52 120 100 (-)ve All Air Exhaust to Outdoor
5 Tuberclosis Lab 6 17.3 2.7 46.71 120 100 (-)ve All Air Exhaust to Outdoor
6 PCR analysis 6 19.4 2.7 52.38 120 100 (-)ve All Air Exhaust to Outdoor
7 Speciment Preparation 6 19.2 2.7 51.84 120 100 (-)ve All Air Exhaust to Outdoor
8 Reagent Preparation 6 20.4 2.7 55.08 120 100 (-)ve All Air Exhaust to Outdoor
9 Accessories 6 15.9 2.7 42.93 120 100 (-)ve All Air Exhaust to Outdoor
10 Clean Room 1 6 15.2 2.7 41.04 120 100 (-)ve All Air Exhaust to Outdoor
11 Half contaminated area 6 18.5 2.7 49.95 120 100 (-)ve All Air Exhaust to Outdoor
12 Serum bank 6 14.9 2.7 40.23 120 100 (-)ve All Air Exhaust to Outdoor
13 HIV Reference 6 47.5 2.7 128.25 120 100 (-)ve All Air Exhaust to Outdoor
!4 Clean Room 2 6 16.8 2.7 45.36 120 100 (-)ve All Air Exhaust to Outdoor
15 Corridor 6 45.1 2.7 121.77 120 100 (-)ve All Air Exhaust to Outdoor
323.6

ROOM LOCATION: MICROBIOLOGY LAB CLEAN ROOM


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 16.8 Room Volume (m3): 45.36 Flow rate (Q) m3/h: 181.44
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.05

Number of grilles: 1 Flow rate (Q) m3/s: 0.05 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITYDUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 A 0.05 150 150 150 0.023 2.24


KU HOSPITAL
MICROBIOLOGY LAB

ROOM LOCATION: MICROBIOLOGY LAB HIV REFERENCE (HISTOLOGY)


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 47.5 Room Volume (m3): 128.25 Flow rate (Q) m3/h: 513
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.14

Number of grilles: 2 Flow rate (Q) m3/s: 0.07 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITYDUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 B 0.07 175 150 150 0.023 3.17

2 C 0.12 200 200 175 0.035 3.48

3 K 0.19 240 225 225 0.051 3.81

ROOM LOCATION: MICROBIOLOGY LAB ACCESSORIES ROOM


REQUIRED CONDITIONS:
1. Pressurization - Negative
2. Minimum outdoor ACH - 2
3. Minimum Total ACH - 6

TYPE OF SYSTEM: SUPPLY DUCT


Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 15.9 Room Volume (m3): 42.93 Flow rate (Q) m3/h: 171.72
Room Height (m): Room Height (m): 2.7 Air Changes per hour : 4 Flow rate (Q) m3/s: 0.05

Number of grilles: 2 Flow rate (Q) m /s:


3
0.02 GRILLE

CROSS
ITEM SECTIONAL
NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITYDUCT LENGTH TOTAL AREA
Q (m3/s) DIAMETER EQUIVALENT RECTANGUL (m2) (m/s) (m) (m2)

1 D 0.02 110 100 100 0.010 2.39


KU HOSPITAL
HIV AND TB LAB
Exhaust/ Supply Requirements

Room Room
Air Exchange Height(m Volume, Pressure
No: Use Rates, ACH RoomArea,(m2) ) (m3) Exhaust % Supply % Relationship(+/-) Recirculated%
1 Waiting Area 6 52 2.7 140.4 120 100 Negative (-) All Air Exhaust to Outdoor
2 General Service 6 29 2.7 78.3 120 100 Negative (-) All Air Exhaust to Outdoor
3 Morphological Lab 6 11 2.7 29.7 120 100 Negative (-) All Air Exhaust to Outdoor
4 Parasite Detection Rm 6 11 2.7 29.7 120 100 Negative (-) All Air Exhaust to Outdoor
5 Ups/Pure Water Rm 6 9 2.7 24.3 120 100 Negative (-) All Air Exhaust to Outdoor
6 Precision Instrument 6 13 2.7 35.1 120 100 Negative (-) All Air Exhaust to Outdoor
7 Female Changing Rm 6 12 2.7 32.4 120 100 Negative (-) All Air Exhaust to Outdoor
8 Male Changing RM 6 12 2.7 32.4 120 100 Negative (-) All Air Exhaust to Outdoor
9 Thermostatic Rm 6 8 2.7 21.6 120 100 Negative (-) All Air Exhaust to Outdoor
10 Store RM 6 8 2.7 21.6 120 100 Negative (-) All Air Exhaust to Outdoor
11 Inpsection Centre 6 127 2.7 342.9 120 100 Negative (-) All Air Exhaust to Outdoor
12 Female Duty Rm 6 9 2.7 24.3 120 100 Negative (-) All Air Exhaust to Outdoor
13 Male Duty Rm 6 9 2.7 24.3 120 100 Negative (-) All Air Exhaust to Outdoor
!4 Corridor 6 12 2.7 32.4 120 100 Negative (-) All Air Exhaust to Outdoor

ROOM LOCATION: FIRST FLOOR (GENERAL SERVICES RM)


TYPE OF SYSTEM: Supply System
Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 29 Room Volume (m3): 87 Flow rate (Q) m3/h: 522
Room Height (m): 3 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.15
Number of grilles: 2 Flow rate (Q) m3/s: 0.07 Outlet size:

CROSS
SECTIONAL
ITEM NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH
Q (m3/s) EQUIVALENT RECTANGULAR (m2) (m/s) (m)
DIAMETER

1 A 0.07 175 200 200 0.040 1.81

2 B 0.15 220 250 250 0.063 2.32


KU HOSPITAL
HIV AND TB LAB

ROOM LOCATION: FIRST FLOOR (WAITING AREA)


TYPE OF SYSTEM: Supply System
Assume: Pressure loss per metre of 1.0 pa/m- Equal Friction Loss Method
SOURCE- TM8- CIBS---Chatered Institute of Building Services

Room Area (m2): 52 Room Volume (m3): 156 Flow rate (Q) m3/h: 936
Room Height (m): 3 Air Changes per hour : 6 Flow rate (Q) m3/s: 0.26
Number of grilles: 4 Flow rate (Q) m3/s: 0.07 Outlet size:

CROSS
SECTIONAL
ITEM NO. DUCT SECTION FLOW RATE DUCT DIMENSIONS (mm) AREA DUCT VELOCITY DUCT LENGTH
Q (m3/s) EQUIVALENT RECTANGULAR (m2) (m/s) (m)
DIAMETER

1 A 0.07 175 200 200 0.040 1.63

2 C 0.21 245 250 250 0.063 3.36

3 D 0.28 260 300 300 0.090 3.06

4 E 0.34 290 350 250 0.088 3.89

5 F 0.41 315 300 300 0.090 4.50


KU HOSPITAL
HIV AND TB LAB

TOTAL
AREA
(m2)
KU HOSPITAL
HIV AND TB LAB

#VALUE!
#VALUE!

TOTAL
AREA
(m2)