1.

On NetAgent’s webpage, Modbus on TCP/IP’s option is under Network—Ethernet tab

2. Install Modbus Poll software


3. Click on Connection → Connect option
4: (1) Connection → TCP/IP option
(2) IP Address (Enter NetAgent IP Address)
Connection Timeout : 5000 ms
(3) OK

5: Modbus Poll receives NetAgent MODBUS ON TCP/IP 。


6: Click on Display → select Hex option
To converts NetAgent MODBUS ON TCP/IP value to 16 bit。

7: NetAgent MODBUS ON TCP/IP value in 16 bits。


8: Click on Setup → Select Read/Write Definition option

9: Click on Function → select 03 Read holding registers option


Enter: Address → Enter 1
Quantity →Enter 25
Address in Cell →Tick
PLC Address(Basic 1) →Tick
OK ,save

e
10: Refer to the ModBus Register Table, ModBus Poll has captured the data of all range of 03 Read
holding registers