Professional Documents
Culture Documents
GP 44-70 - Overpressure Protection Systems
GP 44-70 - Overpressure Protection Systems
GP 44-70
Applicability Group
Date 24 February 2010
GP 44-70
Group Practice
BP GROUP
ENGINEERING TECHNICAL PRACTICES
24 February 2010 GP 44-70
Overpressure Protection Systems
Foreword
This revision issue of Engineering Technical Practice (ETP) Group Practice (GP) GP 44-70 has been
revised to remove references to Strategic Performance Units (SPU). The changes are indicated by a
bar in the margin.
The previous revision (10 December 2009) consistsed of only one addition as 9.5.1.1.e. and is
indicated by a bar in the margin. Thisat revision recommendsed periodic revalidation of the relief
system design and was inadvertently omitted in the 26 October 2009 revision. Revisions to the
3 April 2006 version were more extensive and were not indicated by a bar in the margin but included
the following:
In the event of a conflict between this document and a relevant law or regulation, the
relevant law or regulation shall be followed. If the document creates a higher obligation, it
shall be followed as long as this also achieves full compliance with the law or regulation.
Page 2 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Table of Contents
Page
Foreword.......................................................................................................................................... 2
1. Scope...................................................................................................................................... 6
2. Normative references.............................................................................................................. 7
3. Terms and definitions.............................................................................................................. 8
4. Symbols and abbreviations...................................................................................................10
5. Philosophy............................................................................................................................. 12
5.1. Review of overpressure scenarios.............................................................................12
5.2. Safety instrumented systems (SIS)............................................................................12
5.3. Pressure settings.......................................................................................................13
5.4. Closed relief system...................................................................................................13
6. Design practice..................................................................................................................... 13
6.1. General...................................................................................................................... 13
6.2. Causes of overpressure.............................................................................................15
6.3. Relief limitation by design...........................................................................................18
6.4. Assessment of overpressure scenarios......................................................................19
6.5. Pressure limiting and safety instrumented systems (SIS)...........................................22
6.6. Reverse flow..............................................................................................................23
6.7. Vacuum relief............................................................................................................. 25
6.8. Cold service...............................................................................................................25
6.9. External fire condition.................................................................................................26
6.10. Multiphase vapour/liquid relief....................................................................................29
6.11. Thermal relief............................................................................................................. 29
7. Letdown stations................................................................................................................... 30
7.1. General...................................................................................................................... 31
7.2. Design for gas breakthrough (blowby)........................................................................31
7.3. Design for liquid overfill..............................................................................................32
7.4. Control valve size.......................................................................................................32
7.5. Credit for open outlets................................................................................................33
7.6. Credit for operator intervention...................................................................................33
7.7. Credit for instrumentation...........................................................................................33
7.8. Bypass valves and restriction orifices.........................................................................34
7.9. Temperature effects...................................................................................................36
7.10. Interconnecting pipework...........................................................................................36
8. Equipment, tankage, and piping............................................................................................36
8.1. Shell and tube heat exchangers.................................................................................36
8.2. Air cooled heat exchangers........................................................................................40
8.3. Double pipe heat exchangers.....................................................................................40
Page 3 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Page 4 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
A.12. Piping equivalent lengths and header pressure profiles - flare system simulation review
output (Flarenet or Visual Flare)............................................................................................83
A.13. HP/LP interfaces................................................................................................................... 84
A.14. Disposal system.................................................................................................................... 84
A.15. Test reports........................................................................................................................... 84
Annex B (Informative) Relief and overpressure dossier..................................................................85
Bibliography................................................................................................................................... 89
List of Tables
List of Figures
Page 5 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
1. Scope
a. This GP provides practice for selection, design, and installation of overpressure protection
systems and protection against overpressure of pressurised systems (up to the relief device
discharge flange), in new plants and facilities in the list provided below:
1. Hydrocarbon processing plants, including refineries, natural gas installations, and
chemical plants.
2. Steam and/or power generating plants and ancillary equipment.
3. Terminals, including jetty and loading facilities.
4. Offshore installations, including floating production systems.
5. Petroleum production facilities, including well pads and crude oil and gas gathering
centres.
6. Main transmission pipelines, flowlines, and associated equipment.
7. Storage installations.
8. Vacuum systems and systems relieving at pressure less than 1 barg (14,5 psig).
9. Utility systems.
10. Components of drilling systems on BP operated platforms in which the drilling rig is
an integral part of the facility or mobile drilling rigs that are owned or operated by
BP.
11. Ships, vessels such as a floating production storage offload (FPSO) and road/rail
tanks where the system is a special purpose-built facility that would normally be
considered a processing plant. This GP does not apply to other ships, vessels or
road/rail tanks.
b. This GP may also be used for assessment and modification of existing plants and facilities
in the list above.
c. This GP applies the general requirements, as outlined in GP 48-03, for the use of layer of
protection analysis (LOPA) to define applicable safety instrumented systems (SIS) for
overpressure protection or avoidance of overpressure. For the analysis of overpressure
systems, these requirements are based on:
1. Use of pressure relief devices, if practical, as the main method of overpressure
protection.
2. SIS, if used, which may be an additional method of overpressure protection in most
cases, and as the sole method in a limited number of cases.
d. This GP is to be used in conjunction with the following:
1. GP 44-80, which specifies the overall relief, vent, and depressurisation system design
of which the overpressure protection is a part.
2. ISO 4126, API Std 520, Part I, API RP 520, Part II, and API Std 521/ISO 23251,
interpreting and supplementing them as necessary to provide BP requirements.
e. This GP does not cover mobile drilling rigs or other equipment that is owned by others and
assembled as required on the facility.
f. This GP does not apply to pressure relief for systems in ships or road/rail tanks, unless the
system is for a special purpose built facility that would normally be considered a
processing plant (e.g., floating production storage offload [FPSO] facility).
Page 6 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
2. Normative references
The following referenced documents may, to the extent specified in subsequent clauses and normative
annexes, be required for full compliance with this GP:
BP
GN 44-001 Relief System Design Guide.
GN 44-005 Assessment of Acoustic Induced Vibrations.
GP 30-80 Safety Instrumented Systems (SIS) - Specification and Implementation.
GP 30-81 Safety Instrumented Systems (SIS) - Operations and Maintenance.
GP 32-47 In Service Inspection and Testing of Mechanical Protective Devices.
GP 42-10 Piping Systems (ASME B31.3).
GP 44-40 Isolation of Equipment for Maintenance and Emergency.
GP 44-80 Relief Disposal and Depressurisation Systems.
GP 48-02 Hazard and Operability (HAZOP) Study.
GP 48-03 Layer of Protection Analysis (LOPA).
GP 48-04 Inherently Safer Design (ISD).
Page 7 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
The technical terms used in this GP have the meanings defined in API Std 521/ISO 23251. For the
purposes of this GP, the following terms and definitions also apply:
Disposal system
A system that conducts the relieved fluid to a location where it can be safely discharged. Disposal
systems may terminate in an atmospheric vent, a combustion device, such as a flare tip, or other
specialised treating equipment.
Page 8 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Joule-Thomson effect
The temperature change of a gas or liquid that is forced through a valve or restriction while kept
insulated such that no heat is exchanged with the environment.
Letdown station
A flow restriction in which the upstream operating pressure is greater than the downstream design
pressure. Letdown stations normally consist of an arrangement of control valves, manual valves,
and/or orifice plates. Choke valves in Exploration and Production (E&P) operations are letdown
stations. Letdown stations can be permanent (e.g., fixed piping) or temporary (e.g., hoses).
Pressure vessel
Vessel used for an integrated operation in petrochemical facilities, refineries, gas plants, oil and gas
production facilities, and other facilities.
Reliability analysis
Mathematical technique for assessing, in probabilistic terms, performance of a component, system, or
plant.
Relief device
Any device (mechanical or instrumentation) that acts automatically and reliably to relieve material
upon pressure rise. “Relief device” normally refers to pressure relief valves and bursting discs, but
explosion hatches, water seals, buckling pin devices, and pressure/vacuum breather valves are other
devices that meet this definition.
Page 9 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
For the purpose of this GP, the following symbols and abbreviations apply:
CSC/CSO Car sealed closed/car sealed open (normally applies to isolation valves).
CV Control valve.
EA Engineering authority.
FB Full bore.
HP High pressure.
I/O Input/output.
IM Integrity management.
Page 10 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
LP Low pressure.
LR Long radius.
MP Major projects.
RO Restriction orifice.
SR Short radius.
TA Technical authority.
Page 11 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
5. Philosophy
Page 12 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
6. Design practice
6.1. General
a. A systematic examination of all modes of operation, including startup, shutdown, trip, and
maintenance, shall be made to identify failures capable of creating overpressure.
b. Apart from their normal operating mode, process units can have a range of other operating
conditions that are either necessary for maintenance or occur as a result of upsets.
Operating conditions (as applicable) to be considered shall include the following:
1. Normal and emergency shutdown.
2. Pressure and tightness testing.
3. Prestartup and startup.
4. Manual operation as a result of automatic control system failure or deactivation.
5. Alternate operating modes from original design (e.g., change in controller set point,
turndown, or turnup).
6. Catalyst conditioning.
7. Catalyst regeneration/passivation, etc.
8. Depressuring.
9. Removal of inventory from unit.
10. Gas freeing.
c. Establishment of relieving loads shall include consideration of common modes of failure,
such as electrical, instrument control system, mechanical, human, and procedural.
d. Relief rates, together with the relieving temperature and composition, should be calculated
by performing heat and mass balance calculations for relieving conditions. This should
include such factors as:
1. Reflux drum emptying or flooding.
2. Dryout of column sections, causing loss of circulating reflux.
3. Change of duty in air cooled exchangers due to different temperature differentials.
4. Change in latent heat and boiling temperature due to increased pressure and change in
composition.
5. Initial gas flow during startup of shut in oil wells.
e. Methods of calculation shall be defined at an early stage of the design.
f. A specialist in relief sizing for runaway reaction kinetics should be consulted to assist in
overpressure protection analysis of reaction systems. This analysis should include:
1. Too much reactant, wrong composition.
2. Too much catalyst and/or promoter.
3. Overfilling, insufficient ullage for expansion.
4. Loss of agitation.
5. Loss of cooling.
6. Failure to terminate the reaction.
7. Loss of control.
Page 13 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
g. Relief devices that only protect piping systems may be set above the design rating of the
piping in accordance with GP 42-10.
h. For internal explosion or runaway chemical reactions, if an ISD is not practical and if
pressure relieving devices cannot protect against the situation, special requirements for
emergency depressuring, halting reactions, or otherwise preventing/controlling these
situations shall be provided by SIS in accordance with GP 48-03, GP 30-80, and GP 30-81.
Page 14 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
b) If a single check valve is used on the discharge stream, full backflow shall be
considered, and the settle out pressure should be appropriately defined.
c) Typically, a dynamic analysis of the process system is required to be performed
to evaluate the “settle out” case.
11. Partial utility failure and/or interaction between utilities.
12. Changes in feedstock or other process condition changes.
13. Properties of process fluids under relief conditions that are different from normal
operation.
14. Effect of a very large capacity source (such as a wellhead or long pipeline)
a) The HP/LP interface shall be considered between a large high pressure inventory
that feeds a system of smaller capacity designed for lower pressure (e.g., a
subsea flowline or interfield pipeline feeding a topsides production manifold and
separator).
b) In these circumstances, it may not be feasible to provide a relief system of
sufficient capacity to accommodate the case in which the high pressure system is
suddenly deisolated (e.g., through failure open of the main ESDV).
c) In this case, it may be necessary to provide mechanisms for safely depressuring
the upstream source to a low enough pressure prior to startup with appropriate
SIS and procedural controls.
d) If SIS is used in lieu of mechanical devices, a detailed dynamic analysis should
be performed to ensure that the downstream system will be protected, given that
there is a delay between high pressure switch activation and closure of the
isolation valve.
Page 15 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
a. Design, selection, and protection of control equipment and other service systems to
minimise the potential for simultaneous failure of otherwise independent systems.
b. Use of auxiliary sources of power, such as diesel engines or steam turbines, to provide
cooling water, instrument air, electrical power, etc., under emergency conditions.
c. Provision of automatic reacceleration schemes for electric motor drivers, the loss of which
may give rise to overpressure conditions. These schemes may reaccelerate motors
simultaneously or sequentially, depending on the capability of the power supply.
d. Use of the same utility for cooling as for heat supply (e.g., steam or steam/hydraulic
drivers for air cooled exchangers and reflux pumps) in which steam driven feed pumps and
reboiler pumps or steam heated reboilers are used.
e. Consideration of the effect on relief systems in selecting process and auxiliary drivers.
f. Provision of cooling water standby tanks to ensure a period of water supply, normally
30 min.
Page 16 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
2. If manual block valves are located in a normally flowing process line and if they are
only used for equipment isolation and maintenance, the flow path between the
equipment and its protective device shall be maintained open by:
a) Locking or sealing open the intervening block valve(s).
b) Identifying the valves in relief and overpressure system design documentation.
c) Closing the valves by permit or procedure only and including the isolation
procedure in plant operating instructions.
d) If manual block valves are installed around an exchanger for maintenance, the
exchanger shall be vented and drained immediately after it has been isolated. If
this is not practical, a relief device should be installed to protect the exchanger.
e) If the option of venting and draining is adopted, a warning notice should be
installed which states that the exchanger shall be vented and drained
immediately after being isolated.
3. If closure of the valve (due to mechanical failure or human error) can result in
pressures exceeding the corrected test pressure, either of the two following shall
occur:
a) The block valve(s) shall be eliminated.
b) A pressure relief device shall be installed that protects the equipment from
overpressure due to closure of the valve(s).
h. Credit shall not be taken for automatic controls acting to prevent an overpressure situation,
unless they meet the requirements required for SIS (see 6.5).
i. To address the issues of I/O card failure and inadvertent operation of control devices that
have multiple inputs, a process control loop failure assessment shall be performed as
follows:
1. For any system with more than one output, an analysis should be performed to
determine all reasonably foreseeable failure modes or common cause component
failures that may result in more than one output going to the nonfailsafe state and
potentially producing unacceptable process relief loads.
2. Relief loads that could arise from these failures should be determined. If relief loads
exceed design capability, it may be possible to reassign system outputs to reduce the
relief load.
j. Credit shall only be taken for an operator intervention in accordance with GP 48-03 to
determine if the operator, in conjunction with other layers of protection, can be relied upon
to address the overpressure scenario (e.g., liquid overfill).
k. Since piping and equipment design takes into account both temperature and pressure, the
possibility that departures from the normally expected operating temperature range may
occur during emergencies should be recognised.
l. Overpressure protection design shall be based on the maximum expected throughput for an
individual process component or process system. Consideration should be given to
variations in normal operating flow rates while avoiding significant oversizing of pressure
relief devices.
m. Relief devices protecting unfired process boilers (waste heat boilers) that are designed in
accordance with ASME Boiler and Pressure Vessel Code Section VIII (or another pressure
vessel design code) shall be consistent with that design code.
n. Dynamic simulation
1. Calculation of the quantity to be discharged under relief conditions normally assumes
a steady state condition.
Page 17 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Page 18 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
g. API Std 520, Part I, should be consulted for typical set point tolerances and the spread
required between operating and set pressure of relief devices.
h. Sufficient design margin, taking account of control system response and process dynamics,
shall be applied in selecting a set point. Design margin shall be defined to allow for:
1. Tolerance of set pressure of the relief device under actual working conditions.
2. Setting of any trip switch or amplifier and its switching differential.
3. Setting of the prealarm and its switching differential.
4. Maximum operating pressure under normal process conditions.
5. Time required for the SIS to fully complete its protective function in relation to
process dynamics.
Page 19 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
readily identifiable in the field, and the requirement for isolation shall be clearly
identified in operating procedures.
b) System design shall ensure that it is safe for field personnel to make required
manual isolations. The rate of pressurisation of the low pressure system shall be
sufficiently slow such that a dangerous level of pressure is not reached within
the timescale for effective isolation.
c) Assessment of the timescale for isolation shall take into account the likely
circumstances of the initiating event (e.g., a total power failure) and the alarm
loading and work load on field personnel at the time. The human factor aspects
of the situation shall be considered, including the potential for the isolation step
to be omitted.
d) Any manual isolation valve that is required to supplement the check valves shall
be maintained in good working order. An actuated isolation valve should be
used, unless the manual valve is located in an area that is protected against
effects of fire or blast overpressure and potential escalation.
e) Any manual isolation valve shall be accessible in all foreseeable situations (e.g.,
if the cause of reverse flow was a fire that could lead to a pump being shut
down, the isolating valve would need to be accessible), unless the consequences
of any reverse flow were judged to be far less than the initiating event.
f) Consideration of the potential consequences of failure (either the failure of the
isolation valve to open or close) should be made. While catastrophic failure of a
vessel is always a very serious event, if the consequences are particularly severe,
a higher standard may be warranted.
g) Consideration should be given to the implications of assumed leakage rates on
the inspection regime of check valves and whether simple visual inspection is
sufficient or a higher standard of testing (e.g., periodic leak testing) is required.
Page 20 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Page 21 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
h. Fire relief
1. Pressure relief devices that protect vessels during an external fire (including liquid
full vessels) should be sized assuming all vapour venting (i.e., adequate
disengagement of the liquid and vapour occurs).
2. However, fire relief design for vessels containing reactive or foamy fluids and/or
vessels in which the pressure relief device inlet is connected below liquid level shall
size the relief device based upon incomplete vapour/liquid disengagement (i.e., two
phase or flashing flow).
3. The relief rate should be determined on the basis that the equipment is isolated. It
may be acceptable to take credit for open outlets but only if it is possible to ensure
that the outlets will remain open and have adequate capacity during a fire (e.g., it is
normal practice for emergency responders to isolate lines and equipment).
i. Vessel failure
1. Vessels may fail due to sustained exposure to high temperature from the flame/fire
plume and/or thermal radiation for the following cases:
a) Gas or vapour filled vessels.
b) Vessels in which the fluid can reach or exceed thermodynamic critical
conditions (dense phase fluid).
2. In these cases, vessel will fail due to overtemperature rather than overpressure, so a
pressure relief device is generally ineffective.
3. Deluge, fireproofing, emergency depressurisation, or other system mitigation should
be provided to protect against vessel rupture due to overtemperature for large
equipment that is subject to external fire.
j. All bunded areas (curbed or diked) with storage tanks or equipment storing combustible
liquids shall be considered potential fire zones (refer to NFPA 30).
k. A closed system for the fire relief case shall be sized to handle simultaneous discharge
from all pressure relief devices that are judged to be affected. Refer to GN 44-001 for
additional guidance on fire zones as follows:
1. Fire zone shall be determined by reference to the plot plan, making allowance for
adjacent roads, bund (dike) walls, curbed areas, firewalls, and drainage conditions.
2. Areas considered shall be consistent with design of the surface water drainage system
such that it is not possible for fire to be spread further as a result of burning
hydrocarbons being carried on top of draining fire water.
3. If evaluating drainage credit, consideration should be given to the amount of firewater
that might be applied in the fire area (can be several hundred cubic metres per hour or
thousands of gallons per minute).
4. For offshore platforms, account shall be taken of plant above and below the plot area.
l. The pool fire case need not be considered for equipment if all the following conditions are
met:
1. Equipment itself does not contain flammable/combustible liquids.
2. Equipment is located greater than 15 m (50 ft) from any vessel, pipe, tank, or other
equipment containing flammable/combustible liquids.
3. Flammable/combustible liquid spills will not drain within 15 m (50 ft) of the
equipment.
Page 22 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
m. External pool fire need not be considered a credible cause of overpressure for equipment
that is below the ASME Boiler and Pressure Vessel Section VIII Division 1 size
limitations (i.e., diameter of 150 mm [6 in] or less).
n. For each fire relief zone, the following shall be taken as the basis for calculation:
1. No process heat input or removal.
2. Fire heat input load on all equipment.
o. For any particular plot area for which fire conditions require relief capacity in excess of
that required for any other emergency conditions, fireproofing of selected equipment
should be applied to reduce the discharge rate and the size of any closed relief system as
follows:
1. If the pressure relief device is sized on this basis, fireproofing shall be specifically
designed and installed to resist the forces of fire hose streams and maintain its
insulation properties for an extended period (900°C [1 652°F] for 2 hr in accordance
with API Std 521/ISO 23251).
2. Details of fire resistant insulation shall be included in the relief and overpressure
design basis (see A.10.).
p. No credit for firewater or a fire protection system reducing fire heat input shall be taken
unless specifically allowed by the code (e.g., NFPA 30 for flammable/combustible storage
tanks) and approved by the project EA.
q. For above grade, nonearth covered vessels, the environment factor, F, in the API equation
(as referenced in API Std 521) should be assumed to equal 1,0, thereby allowing no credit
for insulation.
r. Requirements for shell and tube and air cooled heat exchangers during external fire
conditions are covered in 8.1.3 and 8.2, respectively.
Page 23 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
increase in fluid pressure will increase pressures beyond those permitted by the relevant
piping design code (see 8.1.3 and GN 44-001). The following shall also be considered:
1. Expansion of trapped fluid shall be calculated and pressure relief device sized
accordingly.
2. For most systems, a DN 20 by DN 25 (NPS 3/4 by NPS 1) relief valve can be used,
even though it will commonly be oversized.
b. Equipment shall have thermal relief if fluid can be trapped between inlet and outlet valves
and if sufficient heat can be supplied to the fluid to increase pressure above equipment
design pressure. Such equipment shall include heat exchangers, vessels, and pumps as
follows:
1. This shall not apply if valves are locked open during operation and closed only under
permit or procedure (see 6.4.1.1.g).
2. If relief is to the process, thermal relief valves shall discharge to a location that is
always capable of absorbing relieved material. Location of other valves and their
possible positions at the time of discharge of the thermal relief valve shall be taken
into account.
c. To reduce the likelihood of demand on thermal relief valves, operating procedures should
be in place to ensure that blocked in piping and equipment is drained if equipment is to be
out of service for a prolonged period of time.
d. If the cold side can be blocked in between inlet and outlet valves with flow on the hot side,
heat exchanger shall have a pressure relief device for thermal expansion. However, note
the requirements outlined in 6.4.1.1.g.
e. Sizing of thermal relief shall assume that:
1. Fluid is initially at the most severe operating conditions.
2. Pumps and compressors on process fluid continue to operate, unless there is an
automatic shutdown initiated by blocking in, for example, on low flow.
3. Relief devices on pumps and compressors and kickback systems operate.
4. Heat input continues at design operating rate. If temperature sensors are located such
that blocking of the process flow gives a low temperature at the sensor, the maximum
possible heat input should be used in sizing thermal relief.
5. Potential for multiphase relief sizing should be considered if the fluid boils at relief
device opening pressure.
f. Sizing of thermal relief shall be based on maximum flow of fuel to fired heaters or of
heating medium to other equipment. Control valves on heater fuel or heating fluids shall be
assumed to be fully open.
g. If thermal relief valves discharge into a closed system, effects of backpressure shall be
considered for selection of relief valve type and its set pressure.
h. If thermal relief devices are present to protect piping, relief requirement should be
determined based on solar radiation flux at the site and half the area of piping (portion
exposed to sun).
7. Letdown stations
7.1. General
a. In considering process systems in which fluids pass from a high pressure system to a low
pressure system, the low pressure system shall be protected from overpressure.
Page 24 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
b. Relief devices shall be sized to take into account the fluid conditions and all undesirable
circumstances in operation of the letdown station.
Page 25 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Page 26 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
d. No credit shall be taken for automatic controls operating to open gas outlet routes that are
normally closed (e.g., flare spilloff valves).
e. If credit is to be taken for an open outlet, it shall be demonstrated that the open outlet and
downstream equipment are able to accommodate fluid composition and possible phase
change under gas blowby conditions.
Pressure = P1
Pressure = P2
Page 27 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Opening of
bypass
increases flow
Operating to downstream Relief device Bypass controls and/or
Case Bypass use pressure equipment? sizing basis hydraulic turbines
1 Normally open P2A < P1 < P2T No Consider transient None required
or maintenance conditions on initial
only opening of bypass
2 Normally open P2A < P1 < P2T Yes Flow through None required
control valve plus
flow through
bypass
3 Maintenance P2A < P1 < P2T Yes Flow through Bypass flow restricted to ≤
only control valve or maximum flow through control
flow through valve and bypass
bypass (whichever administrative controls to lock
is larger) in closed position
4 Maintenance P1 > P2T > P2A Yes Flow through Consider removal of bypass or
only control valve plus bypass flow restricted to ≤
flow through maximum flow through control
bypass valve and bypass
administrative controls to lock
in closed position
c. Cases summarised in Table 1 consider that upstream pressure exceeds maximum allowable
accumulated pressure (i.e., relieving pressure) in downstream equipment when bypass
valve is opened.
d. The following overpressure scenarios shall be considered for overpressure protection of
downstream equipment, with due reference to 7.5:
1. Normal flow through letdown station with a closed outlet on vessel.
2. Maximum flow through letdown station minus normal flow rate entering vessel.
3. Maximum flow through letdown station for cases in which a closed vessel outlet can
occur in conjunction with maximum flow through letdown station due to a credible
common failure mode.
e. Flow through the letdown station shall be calculated on the basis given in Table 1.
f. Pressure relief device shall be sized for the largest of credible scenarios.
g. In developing relief load, pressure drop through the lines at higher flow rates should be
considered to avoid overestimating relief load. Options to further reduce relief load
contribution from the bypass line include:
1. Removal of bypass line.
2. Installation of a smaller bypass valve.
3. Installation of a restriction orifice in bypass line.
Page 28 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
8.1.1. General
a. In exchanger systems consisting of more than one shell, both shell or tube sides
interconnected without intermediate isolating valves may be considered as single systems
for the purpose of overpressure protection design, unless severe fouling could occur or
transient overpressures as a result of tube rupture, validated by dynamic analysis, require
treatment as separate units.
b. Overpressure conditions to be considered shall include possibilities set forth in
API Std 521/ISO 23251 and as follows:
1. Blocked in and burst tube conditions shall be designed for, together with any
implications of more gradual tube leakage.
2. Overpressure conditions should be met by designing for pressure containment (see
GN 44-001).
Page 29 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Page 30 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
the largest relief load in the hot oil system, assuming that fluid is heated to normal hot
oil operating temperature.
k. Each case for possible design of pressure relief devices for this condition should be
considered individually. For example, if pressure differential and potential leakage are
significant, such as with high pressure gas coolers, or in any other case in which high
pressure can rapidly build up on low pressure side with a tube failure during normal
operation, a relief device should be installed. However, if a pressure leak can be
accommodated in normal flow, a relief device should not be automatically provided.
Accordingly, pressure relief for tube failure may be omitted if both of the following are
true (however, possible need for thermal relief should not be overlooked in any case):
1. Low pressure side can absorb tube rupture flow without causing other problems
upstream or downstream of tube break.
2. Volumetric flow from tube rupture (expanded to low pressure side relieving pressure)
is less than normal volumetric flow through low pressure side.
l. In offshore systems, a burst tube or spurious opening of the relief device(s) can result in
significant quantities of liquid and gas being relieved via the relief device(s) into the flare
system or to atmosphere (e.g., if direct seawater cooling is used and a caisson is provided
for disposal to sea). For this reason, emergency isolation valves should be installed on inlet
to and outlet from low pressure side of exchanger to limit quantities of liquid or gas
released. If emergency isolation valves are installed on cooling water stream, exchanger
should be considered to be blocked in for assessment of burst tube condition.
m. A burst tube condition shall be considered for a heating or cooling coil in a vessel, unless
process piping is used, in which case a small leak is frequently considered.
n. Provision of overpressure protection for heat exchanger and associated pipework does not
eliminate the need for process hazard analysis (i.e., HAZOP) to consider wider process
implications of any interstream leakage.
Page 31 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Page 32 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
c. Thermal relief requirements shall be considered for PCHEs and appropriate protection
provided.
Page 33 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
block valve to a safe location. However, this is normally a more expensive design and shall
not be used for highly viscous or coking liquids.
e. Pump pressure relief devices should discharge to a feed drum, tank, vessel, or pump
suction. If discharging into the pump suction, consideration shall be given to guard against
eventual overheating of fluid from mechanical heating (e.g., trip systems and
administrative controls are commonly used).
f. To mitigate a potential blocked discharge scenario, discharge piping and equipment shall
be designed for one of the following pressure ratings:
1. The sum of suction vessel design pressure plus static head pressure from the suction
vessel normal liquid level to the pump suction flange, plus pump shut-in pressure
with design impeller diameter.
2. The greater of:
a) The sum of suction vessel design pressure, plus static head pressure from the
suction vessel normal liquid level to pump suction flange, plus pump normal
differential pressure.
b) The sum of the suction vessel maximum operating pressure, plus static head
pressure from suction vessel normal operating pressure to pump suction flange,
plus pump shut-in pressure.
Page 34 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
3. The provisions in 1 and 2. should also apply to condensing turbines with intermediate
takeoff connections.
c. In checking manufacturer rating for exhaust side of the casing and also maximum pressure
rating for the exhaust line, it is permissible, depending upon local codes, to add 33% to
ratings for maximum allowable nonshock working pressure given in ASME B16.5 for
flanges (including casing exhaust flange) and fittings or to add 33% to maximum allowable
stress for other components as follows:
1. The 33% allowance may be applied only if it lasts less than 10 hr at any one time or
less than 100 hr per yr in accordance with GP 42-10 and ASME B31.3 and shall not
be used for cast iron or similar nonductile materials.
2. Other local codes and standards may govern temporary overpressure allowance for
piping in other worldwide locations.
d. Condensing turbines shall have a pressure relief device to protect against overpressure
resulting from loss of cooling water or other operational failure.
e. Noncondensing turbines shall have a pressure relief device on the low pressure side
upstream of the first block valve. Sentinel valves shall not be considered pressure relief
devices.
8.11. Boilers
a. Safety valves for ASME Boiler and Pressure Vessel Code Section I boilers should be set
such that the first valve to open is downstream of the superheater.
b. Pilot operated relief valves shall not be used on ASME Boiler and Pressure Vessel Code
Section I boilers.
c. Safety valve(s) on steam drum should be set to open over as wide a range of pressure as
permissible, with the first safety valve to open being the smallest size used. Subsequent
safety valves should be progressively larger.
d. Safety valve protecting economiser/preheater (e.g., safety valve on the steam disengaging
drum) should be set to open after all drum valves have opened.
Page 35 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
8.12. Compressors
a. Reciprocating and centrifugal compressors in which pressure during surge or closed
discharge can exceed MAWP of piping, equipment, or casing shall have a pressure relief
device. An SIS shall not be used as a substitute for a pressure relief device to provide
overpressure protection in this instance.
b. Compressor pressure relief valves shall discharge to a safe location, such as a closed flare,
if compressing hydrocarbons or toxic materials. Consideration shall be given to Joule-
Thompson cooling across the pressure relief valve and downstream system.
c. If the pressure relief valve discharges back to suction of the compressor, an analysis should
be performed to verify that temperature and pressure of compressor suction and process
fluid do not exceed their maximum safe operating limits.
d. Operation of a pressure relief valve shall not cause or intensify compressor surge or create
a system malfunction.
e. If reciprocating compressor suction piping can be overpressured due to internal back
leakage through compressor discharge valves of discharge gas when the machine is shut
down, the suction piping shall have a pressure relief device or the compressor inlet flange
and suction piping back to the first block valve shall be rated for the higher pressure.
f. Reciprocating compressors shall have a pressure relief device on the discharge side that is
upstream of the first isolation valve.
g. Multistage reciprocating compressors shall have pressure relief devices for each stage.
Consideration should also be given to multistage centrifugal compressors, especially
multibody compressors to ensure that adequate overpressure protection is supplied for each
compressor stage.
h. Compressor suction systems, including suction drum and piping downstream of suction
side shutdown isolation valve, shall be designed to accommodate calculated settle out
pressure following a compressor shutdown, assuming that discharge is at the high pressure
trip setting. Design pressure of the suction system should be set at least 10% higher than
maximum settle out pressure.
D
i. Check valves should be provided between upstream low pressure systems and compressor
suction system to minimise reverse flow of high pressure gas from compressor discharge
during the time it takes for compressor to spin down and shutdown valves to isolate the
system following compressor shutdown.
8.13.1. General
a. For the purposes of this GP, flowline and transmission pipelines and associated equipment
shall be defined as follows:
1. Oil or gas transmission pipelines both on land and offshore but excluding processing
plant.
2. Departure and arrival terminals immediately associated with transmission pipelines,
plus any intermediate stations, as required. This includes pig launchers/receivers and
slug catchers but not processing facilities associated with a terminal.
3. Flowlines transporting oil, gas, or water that connect wellheads to production
facilities. These can be used for production or injection/disposal purposes.
Page 36 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
8.13.2. Surge
a. Maximum pressure in the system that can arise as the result of operating conditions plus
any surge pressure shall be evaluated and taken into consideration in design, after allowing
for the effect of all practical methods for surge protection (e.g., expansion vessels, slow
closing valves).
b. If operating pressure plus resultant surge pressure exceeds that permitted, then either
pressure relief devices or a suitably SIL rated SIS shall be installed.
c. Manufacturer should be consulted for data regarding specific valve types, and response
times of the valves shall be considered in hydraulic surge analyses.
d. Surge pressures that are likely to be significant shall be determined by dynamic simulation
and provided for in design, either by reducing level of permitted operating pressure or by
provision of protective devices to keep maximum pressure within that permissible.
Page 37 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
8.15.1. General
Pressure relieving arrangements for storage tanks that operate at or near atmospheric pressure
shall comply with API Std 2000/ISO 28300.
Page 38 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
e. If air is not to be tolerated within the tank, consideration should be given to designing the
tank to withstand full vacuum or providing an inert gas blanketing system to prevent
vacuum during normal and emergency conditions.
f. Liquid storage tanks should be designed in accordance with ISO 28300.
Page 39 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
9.1. General
a. This clause provides requirements for design documentation for new and modified facility
projects.
b. Documentation requirements are defined in accordance with the CVP as used on major
projects.
c. Requirements and recommendations should be followed by smaller projects. However,
they can be modified commensurate with the complexity and magnitude of the
overpressure hazards involved.
d. During project design, documentation for overpressure and relief systems shall be
generated in three phases. Each phase is further clarified as follows:
1. Early design concept (“appraise/select” project stages), with a conceptual design
philosophy.
2. Complete relief and overpressure design basis (“define” and “execute” project
stages), with supporting calculations and system details.
3. A comprehensive relief and overpressure dossier for incorporation into the plant
operating procedures (during the project “execute” stage for use in the “operate”
stage).
e. A typical example of how the documentation requirements in this GP can be met for a
major project is provided in Figure 2.
f. Preliminary design of an overpressure protection system shall be reviewed independently
in detail as specified by the MP EA (as applicable).
g. The subsequent design for overpressure protection shall then be developed, agreed, and
finalised as specified by the MP EA (as applicable).
h. Development of the overpressure protection systems through the remaining design stages
shall be fully documented to enable the design basis and any operating restrictions to be
understood and applied during the operate stage.
9.2. Appraise and select stages - early design of relief and overpressure protection
systems
a. At the appraise/select stage, overpressure scenarios shall be identified, and relief
requirements shall be studied in sufficient depth to establish the basic design philosophy.
Page 40 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Page 41 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Page 42 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
14. Flare system details, including flare header, knockout drum and appurtenances, flare
stack, flare tip, ignitor system, etc.
15. Header pressure profiles.
16. Maximum tailpipe and header velocities.
17. LO/LC valve register.
18. HP/LP interface schedule.
19. Size and type of disposal system used.
20. Relief device inlet/outlet piping hydraulics.
21. Mechanical design basis of process piping and equipment.
10.1. General
a. Equipment, vessels, or process systems protected with more than one relief device for the
same overpressure contingency should have staggered set pressures for these relief devices
as follows:
1. A smaller relief valve with a lower set pressure for smaller and more frequent upset
loads should be considered in addition to the larger valve for the less frequent, larger
Page 43 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
relief loads. Typically, a relief valve may be considered oversized if inlet flow is less
than approximately 25% of capacity.
2. One pressure relief device shall be set at or below design pressure or MAWP of
protected equipment.
3. Additional devices may be set at higher pressure (if allowed by local codes) but in no
case, except for fire, shall the setting be more than 105% of design pressure or
MAWP.
4. Only under fire conditions or other expected external heat input could a supplemental
device be set as high as 110% of design pressure or MAWP, if this is permitted under
equipment design code.
b. Attention shall be given to relief situations that result in a wide range of relieving flow
rates under different upset conditions as follows:
1. In this case, consideration shall be given to selection of two valves: a smaller pressure
relief valve set at the equipment design pressure to handle upset conditions resulting
in lower relieving rates and a larger valve set at 105% of equipment design pressure
for the largest relieving case or otherwise set as permitted by code.
2. Alternatively, modulating pilot operated relief valves may be used under certain
constraints (see 10.2.4).
c. Use of multiple pressure relief devices shall comply with the following:
1. Multiple pressure relief devices should be used if sufficient relief area cannot
practically be supplied by one relief device.
2. If a large valve is being considered (e.g., Q, R, or T size), consideration should be
given to using multiple smaller pressure relief devices.
3. A LOPA of the multiple relief device protective function shall be performed in
accordance with GP 48-03 and any further measures implemented to ensure that the
relief device complies with the reliability requirement.
d. Similar considerations shall apply if a single large rupture disk is required for the
controlling scenario as follows:
1. A parallel pressure relief valve set to open at lower pressure should be considered to
handle smaller upsets that do not require full rupture disk area but could occur more
frequently.
2. Depending on service, the pressure relief valve may require a rupture disk beneath it.
e. After hydraulic analysis of the disposal system has been performed, size and selection of
the relief device shall be revalidated based on calculated backpressure.
f. Total backpressure on a pressure relief device shall not reduce capacity of the pressure
relief device to less than that required for all overpressure contingencies.
g. Relief valve set pressure corrections for temperature may be necessary for high
temperature systems as follows:
1. Correction applied should be based on temperature at the valve when it is in the
closed position.
2. This temperature may not be the flowing process temperature, even if the valve is
mounted directly on protected equipment but uninsulated.
3. Distance from process and effects of any thermal tracing shall be taken into account
in applying a thermal correction factor.
4. After temperature is determined, manufacturer specific temperature correction factor
shall be applied.
Page 44 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
5. Correction factor should be multiplied by set pressure to determine cold set pressure.
h. Use of pressure relief devices other than pressure relief valves and rupture disks is not
excluded but shall be subject to approval by the appropriate EA (operations or site).
10.2.1. General
a. Selection of pressure relief valve type is unique to each individual application. However,
general guidelines and experience can be given in b and c.
b. Relief valve material shall be suitable for inlet and outlet temperatures that result from
extremes of operating and emergency conditions. This includes effect of cooling as a result
of reducing pressure through the valve during relief. However, this temperature does not
include extreme conditions, such as external fire or explosion, in which relief valves would
subsequently be replaced.
c. Relief valves shall comply with API Std 520, Part I, or ISO 4126 guidelines and local or
national design standards, if applicable, such as PED and ASME.
Page 45 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
e. Bellows type valves should not be used in fouling conditions, unless precautions are taken
to avoid or minimise bellows fouling or deposit buildup during relieving and normal
operation (e.g., due to leakage across valve seat).
f. Auxiliary balancing piston type relief device should be used for critical and fouling
service.
g. For those few cases in which a pressure relief valve discharge is routed to atmosphere and
yet is fitted with a bellows seal to protect the spring, guides, and top works from
atmospheric corrosion or fouling, failure of the bellows does not affect pressure at which
the valve commences to lift. However, consideration should be given to the potential for
corrosion or fouling affecting discharge capacity by restricting lift of the disc.
h. Backpressure
1. Maximum backpressure that a balanced type valve may be subjected to shall be based
on manufacturer recommendations (backpressure correction factor and pressure rating
of the bellows).
2. For total backpressure exceeding 50% of valve set pressure, performance data of the
specific valve at expected set pressure shall be obtained from manufacturer.
3. For preliminary sizing, backpressure should not exceed either of the following:
a) 50% (normally) or 60% (in consultation with valve manufacturer) of valve set
pressure.
b) Maximum pressure rating on the outlet side of the balanced valve (refer to
API Std 526).
i. Maximum pressure to which relief valve will be exposed shall be calculated based on
hydraulics of the disposal system for all relief scenarios, including those in which relief
valve is not operating.
Page 46 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
h. If PORVs have the potential for downstream pressure being higher than upstream pressure,
these valves shall have a backflow preventer.
i. Blowdown shall be set such that the valve reseats if required (i.e., blowdown pressure does
not fall within normal operating pressure range).
j. Pilot valves should not be used in high temperature service (200°C to 260°C [400°F to
500°F]) due to elastomers used in pilot valve and/or main valve seat.
10.3.1. General
a. Margins between normal operating and design pressures are generally larger for rupture
disks compared to relief valves and shall be accommodated in the design. Rupture disks
are susceptible to opening due to short duration pressure transients particularly common in
liquid filled systems.
b. Rupture disks may be considered for slurry, corrosive, and erosive services or to minimise
leakage of valuable, hazardous, or toxic fluids. Use of a pressure relief valve combined
with an inlet rupture disk should be evaluated on a case by case basis if corrosive fluids
dictate material of construction of the valve.
c. API Std 520, Part I, and the manufacturer shall be consulted for sizing of rupture disks.
Design shall consider such items as discharge velocities, maximum backpressure, and
Joule-Thomson effects downstream of the device.
Page 47 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
1. For relief of pressure that is rising too fast (less than 10 ms) for normal pressure relief
valves, typically in a reaction vessel, shell and tube exchangers, in which exchanger
shell requires rapid overpressure protection against tube rupture, or for potential
explosions in a powder silo.
2. For services in which operation of a pressure relief valve may be affected by
corrosion or corrosion products or by deposition of material that may prevent the
valve from lifting in service.
3. With fluids (e.g., highly toxic) for which leakage through a pressure relief valve
cannot be tolerated. In this case, either a standalone rupture disk or a combined
rupture disk and relief valve may be considered. Discharge location needs to consider
hazards of toxic releases and comply with GP 44-80.
4. For low positive set pressures in which pressure relief valves tend to leak.
5. For slurry flow, chemically reactive, and/or extremely viscous fluids. A rupture disk
may be used to either protect a pressure relief valve located downstream or in place of
a pressure relief valve if the valve would plug during normal operation or while
relieving.
6. If it is necessary for rapid depressuring to atmospheric pressure.
b. A rupture disk venting to atmosphere does not give the high velocity required for safe
discharge of flammable or toxic vapours for complete duration of the discharge. As the
pressure falls, so does the flow and, consequently, discharge velocity. In such
circumstances, there are two options:
1. Do not use a rupture disk.
2. Use a pressure relief valve in series with and downstream of a rupture disk.
c. Selected burst temperature shall consider day/night and seasonal temperature variations,
particularly if untraced and/or uninsulated.
d. Rupture tolerance range of rupture disk does not need to be considered if determining burst
pressure.
e. Rupture disks shall not be used for pulsating flows or at working pressure close to design
bursting pressure. The following shall also be considered:
1. Normal domed rupture disks (i.e., nonscored) may be operated at working pressures
only up to 70% of bursting pressure.
2. Forward acting scored rupture disks may be operated at 80% to 90% of bursting
pressure.
3. Reverse acting scored rupture disks may be operated up to 90% of bursting pressure
in many circumstances.
4. Rupture disks shall not be subjected to operating working pressure exceeding 90%.
5. API Std 520, Part I, or ISO 4126 should be used for general guidance on maximum
suitable operating pressures for various types of bursting disks. However, in all cases,
the manufacturer information on the specific disk should be used.
f. Rupture disks shall only be used to shield inlet or outlet of pressure relief valves if:
1. A “telltale” device and pressure gage is used between rupture disk and relief valve to
identify disk leakage or failure.
2. If the rupture disk and the pressure relief valve are installed in series, the space
between the two shall be vented to prevent slight leaks from the first device causing
the second to open. If leakage is not permitted to be routed to atmosphere, the vent
Page 48 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
should be routed to a closed system operating near atmospheric pressure, even under
upset conditions.
3. Any backpressure in the closed system should be considered in the rupture disk relief
burst pressure design. Maximum design backpressure in the closed system shall also
be considered if selecting the rupture disk assembly to ensure that maximum
backpressure can be tolerated.
4. A leaking rupture disk beneath a pressure relief valve should be replaced in a timely
manner.
5. If a rupture disk is used upstream of a pressure relief valve such that a lesser
metallurgy relief valve can be used (e.g., use of a titanium rupture disk with a
stainless steel pressure relief valve instead of a titanium pressure relief valve), and if
pressure relief valve vents into a common header, design should consider any
corrosive or fouling products from other locations that can degrade the pressure relief
valve from the outlet side.
g. Rupture disk layout and installation design shall be such that disks can be replaced
conveniently and safely.
h. Low pressure (less than 1,0 barg [15 psig]) rupture disk designs that do not allow affixing a
tag should only be used if tag is firmly secured to installed disk assembly and special
provisions are made to ensure correct installation.
i. For slurry or any other service in which material could build up, consideration should be
given to providing a small gas or clean liquid purge flow across process side of disk to
prevent possible obstruction in front of disk.
j. Rupture disks should preferably be prescored forward acting design and prescored reverse
acting design.
k. Reverse acting rupture disks that rely on a cutting assembly shall not be used.
l. If rupture disks are used to protect the low pressure liquid filled side of a shell and tube
exchanger, initial discharge through the disk could be a high velocity liquid slug. The
following shall be considered:
1. Downstream piping shall be designed to accommodate shock loads and two phase
flow from this event.
2. Surge analysis of the cooling medium system should be performed to ensure that
rupture disks will not routinely burst. Alternatively, mitigation measures can be
implemented to avoid spurious failures during nonroutine conditions (e.g.,
temporarily blocking inlet to the rupture disk if a cooling water pump is brought
online or if switching cooling water valves).
m. Inconel 600 rupture disks shall be heat treated by manufacturer to maximum operating
temperature that the disk is expected to see in service.
Page 49 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
10.3.6. Rupture disk specification in accordance with ASME or ISO and performance criteria
a. Rupture disks (bursting discs) with a burst pressure greater than 1,0 barg (15,0 psig) shall
be manufactured, marked, and certified and shall comply with performance criteria (e.g.,
rated flow capacity, rupture tolerance) in accordance with the following, as a minimum:
1. ASME Boiler and Pressure Vessel Code Section VIII Division 1 (with ASME PTC 25
testing protocol) or ISO 4126-2 and ISO 4126-6 (with ASME PTC 25 testing
protocol).
2. Any additional requirements mandated by local codes and regulations.
Page 50 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
b. Rupture disks (bursting discs) with a burst pressure of 1,0 barg (15,0 psig) or less shall be
manufactured, marked, certified, and comply with performance criteria (e.g., rated flow
capacity, rupture tolerance) in accordance with the following as a minimum:
1. ISO 4126-2 and ISO 4126-6 (with ASME PTC 25 testing protocol).
2. Any additional requirements mandated by local codes and regulations.
c. Each rupture disk shall be packaged separately.
Page 51 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
1. Compressible fluids that are not choked at the throat of the pressure relief valve may
use the effective discharge coefficient for nonflashing liquid flow.
2. Compressible fluids that are choked at the throat of the pressure relief valve may use
the effective discharge coefficient for vapour flow.
e. Capacity of an installation involving only rupture disks should be based on hydraulic
calculations of the piping system between pressurised equipment at relief conditions and
reservoir into which effluent is transferred as follows:
1. Hydraulic calculations of the piping system should be derated by a factor of 0,9 in
accordance with ASME Boiler and Pressure Vessel Code Section VIII Division 1.
2. If equivalent velocity head resistance factor (Kr) of rupture disk is not known or has
not been tested, a default value of 2,4 may be used.
f. For sizing relief devices, set pressure and accumulation pressure shall comply with
applicable pressure vessel design code.
g. Design of pressure relief devices discharging to a closed relief system shall take into
account maximum backpressure arising at discharge of the device for the particular
overpressure case under consideration. Additionally, mechanical design shall be suitable
for maximum backpressure to which a device can be exposed as a result of other devices
relieving.
10.6.1. General
a. Pressure relief devices shall be configured in accordance with ISO 4126 or API RP 520,
Part II, as amplified and amended in this clause and 10.7, as well as other applicable codes
and standards, such as:
1. ASME Boiler and Pressure Vessel Code Section I.
2. ASME Boiler and Pressure Vessel Code Section VIII.
3. BSI PD 5500.
4. PED.
b. Relief devices intended to relieve vapour should be connected to the highest point of
equipment to be protected, if possible. If this is not possible and there is the potential for
liquid above the relief device inlet line, relief device shall be sized for an equivalent
volumetric rate of liquid and also designed to minimise slugging.
c. If thermal cycling is an issue, to minimise thermal cycling, pressure relief valves should be
located such that fluid temperature at the valve during normal plant operation is near
ambient conditions, when the valve is inactive. If ambient conditions affect performance,
valve should be heat traced.
d. Pressure relief devices shall be isolated before hydrotest of piping or vessels but included
in system tightness testing.
Page 52 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
c. Block valves and/or blinds are vital to the maintenance of items on operating units.
However, these should be kept to a minimum, identified, and a procedure shall be put in
place (generally a work permit or valve lock open procedure) for controlling their use.
d. Inlet or outlet block valves are generally not permitted for ASME Boiler and Pressure
Vessel Code Section I applications, unless special three way valves are approved by local
authorities and the appropriate EA. For ASME Boiler and Pressure Vessel Code
Section VIII applications, the PSV installation may provide in place online testing
capability to improve safety and reduce turnaround time and maintenance costs.
Restrictions to block valve use in overpressure relieving services shall be determined in
compliance with governing local codes and standards.
e. Block valves may be used to isolate pressure relief devices for inspection or maintenance,
provided that an additional relief device that supplies 100% design relieving capacity is
installed as follows:
1. Such block valves shall be installed on inlet piping to relief devices and on discharge
piping if this is to a closed system. Isolation valves shall also be acceptable
downstream of single relief valves to isolate them from a closed disposal system.
2. Such block valves shall be locked open or interlocked by a system approved by
operating management. Isolating valve should be secured by a physical means.
f. If block valves are installed on relief devices, upstream or inlet block valve shall be a full
port valve with valve inlet diameter the same as or larger than relief device inlet flange.
Downstream valve shall also be full port if required by pressure drop. With supporting
pressure drop calculations, a reduced port valve may be used (see 10.6.4.1.j).
g. A valved and blanked/plugged drain connection of minimum size DN 20 (NPS 3/4) shall
be provided between relief device and any upstream block valve. A similar vent
connection shall be provided between relief device and any downstream block valve.
h. A maintenance bypass valve or manual depressurisation valve shall only be located in
parallel to a PSV if the following conditions are met:
1. Capacity of bypass valve is limited to less than PSV capacity to avoid excessive flow
in the downstream system.
2. Bypass valve shall be locked or sealed closed and may only be opened under permit
for maintenance of the PSV or other situations if sustained flow through the bypass of
a cold fluid into a downstream system cannot occur.
3. Valve and downstream piping shall be designed for the minimum temperature
experienced under flowing conditions, taking into account autorefrigeration effects
(Joule-Thomson cooling) and the possible isentropic expansion of a closed volume of
the system that it is depressuring (see GP 44-80).
Page 53 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
2. Pressure relief valves that require inspection and/or maintenance between major plant
shutdowns.
d. Pressure relief devices discharging into a closed system shall be located such that there is
continuous elevation decline (slope) from the devices to the downstream knockout drum
such that the lines contain no liquid traps.
e. Relief valves shall be mounted in a vertical position.
Page 54 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
l. If pressure relief device discharges to atmosphere, the potential for relief discharge ignition
coincident with the presence of an operator in the vicinity shall be considered and, if
necessary, specific means for operator protection or escape shall be provided.
m. Relief device discharge line to atmosphere shall have a 10 mm (3/8 in) drain at its lowest
point. If discharge is flammable or toxic, drain shall be piped to a safe location and may
contain a locked open isolation valve in an easily accessible location.
n. The ends of atmospheric discharge tailpipes should be cut off square, not chamfered (i.e.,
45 degree bevel). However, if atmospheric discharge tailpipes are chamfered, outlet piping
shall be designed, anchored, and guided to resist forward, lateral, and upward dynamic
forces.
o. Pressure relief devices and associated piping shall be designed, anchored, and guided to
resist forward, lateral, and upward dynamic forces.
p. Relief valve discharge lines connected to a closed system shall enter the top of the header
or discharge piping system, if practical.
q. Generally, the isothermal flow method should be used to calculate pressure drop in outlet
relief piping for gas service. See API Std 521/ISO 23251 for details. If the adiabatic
method is used in high pressure gas service, the “k” value shall be calculated for gas
conditions that exist in outlet relief piping.
r. Relief valve outlet piping shall be evaluated for potential acoustic and flow induced
vibration and appropriate supports shall be provided. See GN 44-005 for guidance on
acoustical and flow induced vibration. Pipe wall thickness of Schedule 10 or lower should
not be used without completing a detailed analysis per GN 44-005.
10.7. Preinstallation
10.7.1. General
a. Before installation, pressure relief valves shall be stored in an upright position in a clean,
dry area, and rupture disks shall be stored in a clean, dry area in their original shipping
containers.
Page 55 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
b. Pressure relief device inlets and outlets shall remain covered until installation.
c. Before installation or bench testing, pressure setting engraved on pressure relief device
nameplates shall be verified as being the same as specified on data sheet and facility
pressure relief device records.
d. Inlet piping and associated equipment shall be free of foreign matter. This includes pipe
scale, welding beads, or other objects that could cause damage or prevent pressure relief
valves from reseating after operation.
Page 56 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Annex A
(Normative)
Relief and overpressure protection dossier structure
A.1. General
a. Relief and overpressure documentation should consist of a readily accessible structure such
that pertinent information relating to design of overpressure protection systems can be
readily accessed.
b. Information listed in A.2. through A.15. may be included in the dossier. However, if the
information is maintained elsewhere in the documentation system, it should be made clear
in the dossier.
c. Details on information requirements to assist in compilation of the document are included
in A.2 through A.15. Example tables for recording data are in Annex A.
The design philosophy section of the dossier contains a summary of the philosophy adopted in
process design that shall address in particular (but not be limited to) the following, as described
in 5 and 6:
a. Codes, standards, and BP practices used in the design.
b. Utility failures considered (total, unit, partial, etc.).
c. Whether multiple failure cases have been considered and, if so, where and why.
d. If SIS have been used to prevent overpressure or limit relief loads.
e. Design considerations of fire relief from vessels, shell and tube exchangers, and
condensers, especially if individual relief valves have not been provided.
f. Instances in which credit has been taken for operator intervention.
g. In developing the relief and overpressure philosophy, due consideration shall also be given
to potential vacuum conditions that can be created in process equipment.
h. Assumed position of bypass valves if control valves fail open.
i. Philosophy for sparing relief valves (see 10.6.5).
j. Maximum fire areas considered and how they relate to design of surface and firewater
drainage systems.
k. Basis for sizing discharge lines (i.e., maximum backpressure and velocity that have been
considered).
l. Values of pipe roughness used to size lines.
m. Unit capacities, feedstock, and maximum and normal design basis.
n. Flashback prevention design basis.
A.3. List of relieving devices, data sheets, and associated block valves
a. A complete set of relief valve specifications and rupture disk (i.e., bursting disk)
specifications shall be provided. In addition, the list shall include thermal relief valves,
rupture/buckling pins, conservation vents, vacuum relief valves, and other mechanical
devices used for both overpressure and underpressure protection.
Page 57 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
b. This section of the dossier shall contain an index of unit flowsheets or P&IDs that are
relevant to the stage of design or operation (i.e., IFD, IFC, or as built) and which shall be
marked up to designate and show all chain locked, CSO/CSC, or LO/LC manual block
valves that shall be locked or sealed open or closed during normal unit operation to
safeguard the integrity of the relief system as designed.
c. Reference shall be made to the valve register (LO, LC, CSO, or CSC isolation block valve
requirement), which shall consist of a tabulation, spreadsheet, and/or list of isolation block
valves in a relief or overpressure system path or process. This register is provided to ensure
that these administrative controls are implemented during construction and operation to
ensure an open relief path and/or to prevent occurrence of an overpressure situation within
the unit and assist in development of field operating procedures.
a. The relief loads section of the dossier shall contain a summary tabulation of the relief loads
generated for identified causes of overpressure, clearly indicating the case that governs
sizing of the relief device. For each device, the summary shall include:
1. Tag number.
2. Discharge location.
3. Relief loads for each credible overpressure case (included in relief device sizing
basis) as follows:
a) Each relief case shall note maximum vapour, liquid, or two phase relief rate and
may include additional data if deemed appropriate (e.g., a high temperature
relief case).
b) Fluid characteristics, such as molecular weight, specific gravity, fluid
temperatures at relieving conditions, and any other fluid properties relevant to
the relief case being reviewed. Relief device capacity shall also be included as
part of the data.
b. Conditions under which each relief load occurs shall be clearly defined. If recording power
failure, it should be stated whether this is facility wide, local (i.e., one unit or group of
units), partial (affecting part of the supply distribution within a unit or group of units [e.g.,
MCC]), or individual (single item of equipment).
c. If evaluating gas breakthrough conditions, the relief load summary should state:
1. Source of overpressure, including control valve tag number, if applicable.
2. Whether control valve bypass has been assumed open or closed, if applicable.
3. Assumed liquid level in low pressure vessel, if this has an impact on the relief case.
d. If a relief valve is provided to protect more than one item of equipment, the equipment
protected shall be clearly indicated.
e. Relief load detailed calculations shall be provided.
a. This section of the dossier shall contain process data for control valves and restriction
orifices that limit relief loads as follows:
1. Sheet shall specify manufacturer, type, size, and rated conditions (including Cv) at
normal and fully open positions.
Page 58 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
2. A brief process sketch shall also be included or referenced, showing location of the
valve or orifice plate.
b. Control valve or restriction orifice replacement
1. If a control valve or restriction orifice is replaced, this section of relief and
overpressure design shall be reviewed to ensure that there has been no change that
can give rise to an increased relief load.
2. If an increased load can result, it is essential that capacity of the associated relief
valve and header system be checked to ensure that the system is adequately sized.
3. Relief and overpressure design basis shall either be updated or supplemented to
reflect this change.
4. Local MOC procedure shall be used to complete this change.
The pump and/or compressor data section of the dossier shall contain a list of pumps with their
shut-in heads and the corresponding impeller sizes as used in the relief design. Much of the
information should be on the original data sheet. The minimum information required for
overpressure protection reasons shall be:
a. Manufacturer.
b. Type designation.
c. Equipment tag number.
d. Shut-in head for installed impeller (for pump or centrifugal compressor).
e. Shut-in head for maximum impeller size (for pump or centrifugal compressor).
f. Fluid density (including testing/commissioning fluids).
g. Installed impeller diameter (for pump or centrifugal compressor).
h. Maximum impeller diameter (for pump or centrifugal compressor).
i. Reference to manufacturer pump or centrifugal compressor curve.
j. Cylinder data for reciprocating compressors.
k. Unloader information for reciprocating compressors.
l. Motor or driver information.
Design basis for overpressure protection of other equipment, such as compressors, heat
exchangers, and flare and vent systems, shall be specifically identified and quantified in the
detailed relief and overpressure design basis.
a. The SIS section of the dossier shall contain details of SIS with a designated SIL that has
been provided to limit overpressure as an alternative to a relieving device or reduce the
overpressure load.
b. Information should be provided for each system, including a schematic and a list of each
instrument component showing the instrument type, manufacturer, testing frequency, type
of testing, and a reference to the analysis or report defining system reliability.
Page 59 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
a. This section of the dossier shall contain a list of fire areas that have been considered for
determining relief loads, indicating which relief valves are considered as relieving
simultaneously. If there is a fire relief case to be considered, a separate breakdown shall be
included, showing loads generated within each equipment item to be protected. Tabulation
shall include:
1. Fire area considered.
2. Equipment item.
3. Vessel liquid level.
4. Tag number of relief valve through which load is discharged (may not be located on
equipment).
5. Individual loads (flow, molecular weight, temperature).
6. Total load for area (total flow, mixture molecular weight, mixture temperature).
7. Environmental factors, thermal conductivity, thickness of insulation where
fireproofing credit is taken.
b. This section of the dossier shall reference a plot plan of the unit that is marked up to show
fire areas considered.
c. This section of the dossier shall contain a list of vessel and equipment that uses fire
resistant insulation to reduce fire relief load as follows:
1. Description should include insulation type, thickness, thermal conductivity, and
details of cladding and fixing methods.
2. If fireproofing is used to reduce relief loads, a table should be provided that clearly
identifies where fireproofing is used and gives basic information such that checks can
be made that it still has adequate integrity. Table should also allow verification if such
special arrangements are needed.
Page 60 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
a. The flare loads section of the dossier shall contain a breakdown of flare load for each
major utility failure case, emergency depressurisation (blowdown), and worst fire case.
This shall include relief loads from other units not under consideration that may be
relieving at the same time due to a common event.
b. If relief valve discharges from the unit or units can be directed to more than one flare in
accordance with flare sparing philosophy, loads for each flare shall be included.
A.12. Piping equivalent lengths and header pressure profiles - flare system
simulation review output (Flarenet or Visual Flare)
a. An electronic simulation of the relief and flare network system shall be developed that
includes:
1. Hydraulic profile of the flare system for major flare load cases (including blowdown),
with backpressures at each relief or blowdown device discharge and each subsequent
node in the network. Velocities in flare headers shall be reported for each case.
2. Model shall document pressure flow relationship for the flare tip.
3. This data shall be the final as built design and shall reference the number of the
piping isometric or general arrangement drawing for the line.
b. If credit is taken for pressure drop in interconnecting pipework to reduce flow in a gas
breakthrough situation or another pressure relief scenario, pipe lengths, diameters, and
fittings shall be fully described and documented in the relief and overpressure design basis.
These sections of pipe shall be flagged in the relief and overpressure dossier to ensure that
future piping modifications affecting this pipe are carefully reviewed.
c. This section of the dossier shall contain a series of layout drawings showing flare and
backpressure at junctions and key points in the relief system pipe network for each major
utility failure and fire case. Electronic files should be provided in either Flarenet or Visual
Flare format.
a. The HP/LP interfaces section of the dossier shall either consist of or reference a schedule
of all HP/LP design pressure specification breaks in the process, including pertinent data,
such as size, type, and fully open flow coefficient of limiting valves or orifices, locked
closed valves, in every route between high and low pressure systems.
b. Consideration should be given to all manual routes to flare and/or vent that could affect
flare system design.
a. The disposal section of the dossier shall either have or reference relevant information on
design of the disposal system, including type (e.g., elevated flares, ground flares,
atmospheric vent), capacity, radiation profiles, and noise profiles. See GP 44-80 for more
details on disposal system design guidelines.
b. Relief valves connected to disposal system shall be sized or validated using established
builtup backpressure and superimposed backpressure developed in the disposal system.
See GP 44-80 for guidance on relief system modelling.
Page 61 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Test dates and reports for pressure relief valves, rupture disks, and overpressure protection SIS
at SIL 1 and higher integrity levels shall be recorded and readily accessible for inspection.
Page 62 of 69
PSV tag number
Equipment
Equipment number
Fire
Blocked outlet
NOTE:
24 February 2010
Tube rupture
Gas blowby
Reverse flow
Sizing case
Inlet (in)
been reduced in width to fit the current page size.
Orifice designation
Selected
PSV size
Outlet (in)
Type
Manufacturer
Phase
Accumulation (%)
Vapour compressibility
Page 63 of 69
GP 44-70
Multiple PSVs
Datasheet ref.
24 February 2010 GP 44-70
Overpressure Protection Systems
Pump data
Shut-in Impeller Discharge piping
Tag no. Service P&ID no. head (m) diameter pressure Final destination Protection Pump curve ref
Max Design
Installed Max Installed Max Design oper To press
(barg) (barg) (barg)
Page 64 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
SIS
SIS tag no. Equipment protected SIL rating Set point Remarks
Page 65 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Simultaneous
blowdown
Page 66 of 69
Tag no.
Equipment
Equipment number
Line
24 February 2010
Tees (run)
Tees (hard)
90° Elbows LR
90° Elbows SR
45° Elbows
Globe valves
Plug valves
Tees (run)
Tees (run)
Vessel entry
Vessel exit
Phase
Overpressure Protection Systems
Page 67 of 69
GP 44-70
Multiple PSVs
24 February 2010 GP 44-70
Overpressure Protection Systems
Bibliography
BP
[1] GIS 34-301, General Purpose Steam Turbines (API 611).
[2] GIS 34-302, Petroleum, Petrochemical and Natural Gas Industries - Steam Turbines - Special
Purpose Applications (ISO 10437).
[4] GP 06-25, Design for the Prevention of Corrosion under Insulation (CUI)) and Fireproofing (CUF).
[13] BS CP 2010, Code of practice for pipelines. Design and construction of steel pipelines in land.
[14] BS EN 14161, Petroleum and natural gas industries. Pipeline transportation systems.
[19] Model Code of Safe Practice in the Petroleum Industry: Petroleum Pipelines Safety Code Pt. 6.
Page 68 of 69
24 February 2010 GP 44-70
Overpressure Protection Systems
Other
[23] The European Pressure Equipment Directive (PED).
Page 69 of 69