LEGEND:

NO. PART DESCRIPTION DWG RATING


POSITION

125VDC 6U SUBRACK 1 MAINS AC INPUT 2P MCB CB1 50A 2P

I/O 2 BATTERY MCB 2P MCB CB2 50A 2P

MONITOR 3 LOAD MCB 2P MCB CB3 50A 2P

4 AC SURGE ARRESTOR SPD 230VAC


CAN-4 5 DC SHUNT(BATTERY) SHB 100A 60mV

6 TERMINAL BLOCKS X1-X4 -

MASTER
DISPLAY

CAN-3 CONTROLLER
DISPLAY

A V
BASIC
CONTROLLER

DC LOAD O/P(125V DC)


SPD
230VAC 1PH 2W 50HZ

CAN-2
AC MAINS INPUT

10sq.mm
CB1 CB3
10sq.mm 50A 2P 10sq.mm 2.5sq.mm COPPER 25sq.mm 50A 2P WITH AUX
X1 X2 X4
COPPER
RECTIFIER SYSTEM ALARM CONFIGURATION:
2 X 241115.805
1. AC Mains Fail
SHB 2. Rectifier Fail
100A
3. Battery/Load MCB Trip
COPPER
4. High Temp Alarm
5. DC Earth Fault
6. Common
K1
(100A)

CB2 Cable Colour code:


50A 2P WITH AUX AC:
L1 - Red
16sq.mm N - White OR Blue
PE - Yellow/Green
X3 Signal Cable: White/Black

DC:
TO BATTERY
+ve - Red
(BY OTHERS) -ve - Blue

TITLE:
GOD
IS

SINGLE LINE DIAGRAM OF


GOOD

A Delta Group Company


125VDC 6U SUBRACK - 4KW
ELTEK POWER PTE LTD
INPUT 1 X 230VAC +N+PE - OUTPUT 125VDC NO.3 TEBAN GARDENS CRESCENT, TEL: 6773 2326
SINGAPORE - 608920 FAX: 6775 3602

DESIGNED BY: DRAWN BY: APPROVED BY: START DATE: SCALE FORMAT UNIT MATERIAL THICKNESS FINISHING
SRIPEDSG SRIPEDSG GOSUSG 25.05.2018 1:1 A3 mm N/A N/A N/A
A ISSUED FOR APPROVAL 28.05.2018 SRIPEDSG FRCASG GOSUSG DRAWING NO. PART NO. PROJECTION PAGE

REV DESCRIPTION DATE PREPARED CHECKED APPROVED


PE-1

PE
C
SPD TO I/O MONITOR
NC CONFIG INPUT-1
230VAC 1PH 2W 50/60HZ

CB1 L N
X1 50A 2P MCB
AC MAINS INPUT

L 1 1 2 3

N 2 3 4 4
X2
E PE

PE-2

4 3 2 1

CAN-1

TO SHEET-3
COPPER

COPPER

TITLE:
GOD
IS

SCHEMATIC DIAGRAM OF
GOOD

A Delta Group Company


125VDC 6U SUBRACK - 4KW
ELTEK POWER PTE LTD
INPUT 1 X 230VAC +N+PE - OUTPUT 125VDC NO.3 TEBAN GARDENS CRESCENT, TEL: 6773 2326
SINGAPORE - 608920 FAX: 6775 3602

DESIGNED BY: DRAWN BY: APPROVED BY: START DATE: SCALE FORMAT UNIT MATERIAL THICKNESS FINISHING
SRIPEDSG SRIPEDSG GOSUSG 25.05.2018 1:1 A3 mm N/A N/A N/A
A ISSUED FOR APPROVAL 28.05.2018 SRIPEDSG FRCASG GOSUSG DRAWING NO. PART NO. PROJECTION PAGE

REV DESCRIPTION DATE PREPARED CHECKED APPROVED


FROM SHEET-2
CAN-2 CAN-3 CAN-4

PORT

PORT
CAN

CAN
PORT

PORT
CAN

CAN
SMARTPACK 2

PORT

PORT
IO

CAN

CAN
IO MONITOR 1
BASIC

Digital Input 1

Digital Input 2

Digital Input 3

Digital Input 4

Digital Input 6
Digital Input 5
CONTROLLER

Relay 1

Relay 2

Relay 3

Relay 4

Relay 5

Relay 6
SMARTPACK 2
MASTER
System Connections (DISPLAY)

COM

COM

COM

COM

COM

COM
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC
+

+
+
Voltage Sense Input 1 +

-
Current Sense Input 1 +

-
Voltage Sense Input 1 -

Current Sense Input 1 -


Battery Fuse Input 1 +

11

18
10
11
12
13
14
15
16
17
10

12
1

1
Battery Fuse Input 1 -

2
3
4

6
7
8

2
3
4

6
7
9
5

9
8
PE-4

Load Fuse Input 1 +


Load Fuse Input 1 - Power

TEMP. SENSOR

Battery +/-
Battery +

Battery -
LVD1

LVD2
-

-
+

+
1

3
2
2

1
3
4

6
7
8
5

1
1

4
2

3
PE-3
51-1
52-1
NC 501
CB2-CB3 AUX 502
NC 503
504
505
506

507
508

51-2

52-2
C
CB4 AUX

TEMP

FROM SPD
C

AUX

FROM FROM
SHEET-4 SHEET-4
FROM SHEET-2

COPPER

TO SHEET-4
COPPER

TITLE:
GOD
IS

SCHEMATIC DIAGRAM OF
GOOD

A Delta Group Company


125VDC 6U SUBRACK - 4KW
ELTEK POWER PTE LTD
INPUT 1 X 230VAC +N+PE - OUTPUT 125VDC NO.3 TEBAN GARDENS CRESCENT, TEL: 6773 2326
SINGAPORE - 608920 FAX: 6775 3602

DESIGNED BY: DRAWN BY: APPROVED BY: START DATE: SCALE FORMAT UNIT MATERIAL THICKNESS FINISHING
SRIPEDSG SRIPEDSG GOSUSG 25.05.2018 1:1 A3 mm N/A N/A N/A
A ISSUED FOR APPROVAL 28.05.2018 SRIPEDSG FRCASG GOSUSG DRAWING NO. PART NO. PROJECTION PAGE

REV DESCRIPTION DATE PREPARED CHECKED APPROVED


CB3 50A 2P MCB

125VDC OUTPUT
FROM SHEET-3
WITH AUX
58
59
X4
TO SHEET-3 TO SHEET-3

SHB
100A

53

K1
100A

54 55

CB2
50A 2P MCB
WITH AUX
56 57

X3

TO BATTERY
(BY OTHERS)

TITLE:
GOD
IS

SCHEMATIC DIAGRAM OF
GOOD

A Delta Group Company


125VDC 6U SUBRACK - 4KW
ELTEK POWER PTE LTD
INPUT 1 X 230VAC +N+PE - OUTPUT 125VDC NO.3 TEBAN GARDENS CRESCENT, TEL: 6773 2326
SINGAPORE - 608920 FAX: 6775 3602

DESIGNED BY: DRAWN BY: APPROVED BY: START DATE: SCALE FORMAT UNIT MATERIAL THICKNESS FINISHING
SRIPEDSG SRIPEDSG GOSUSG 25.05.2018 1:1 A3 mm N/A N/A N/A
A ISSUED FOR APPROVAL 28.05.2018 SRIPEDSG FRCASG GOSUSG DRAWING NO. PART NO. PROJECTION PAGE

REV DESCRIPTION DATE PREPARED CHECKED APPROVED


CB2 WITH AUX CB3 WITH AUX X3 X4 CB2 WITH AUX CB3 WITH AUX X3 X4 Note:
1. Cabinet Front Access
2. 120° Door Opening (Approx)
3. Ventilation = Top and Side
4. Type/Protection = Indoor/IP20
BASIC 5. Cable Entry = Rear
6. Mounting = 19 inch Railing
SHT

418
418

K1

I/O

MASTER

INTERNAL TOP VIEW


EXTERNAL TOP VIEW

465 418

Controller Display
SMART PACK2

DONGYA SH-F1 100A60mV

5 Nos. of FP2 110VDC FLATPACK 2 FLATPACK 2

2000W HE Modules
ELTEK 24V ELTEK 24V ELTEK ELTEK

EXTERNAL FRONT VIEW INTERNAL SIDE VIEW

TITLE:
GOD
IS

GENERAL ARRANGEMENT DIAGRAM OF


GOOD

A Delta Group Company


125VDC 6U SUBRACK - 4KW
ELTEK POWER PTE LTD
INPUT 1 X 230VAC +N+PE - OUTPUT 125VDC NO.3 TEBAN GARDENS CRESCENT, TEL: 6773 2326
SINGAPORE - 608920 FAX: 6775 3602

DESIGNED BY: DRAWN BY: APPROVED BY: START DATE: SCALE FORMAT UNIT MATERIAL THICKNESS FINISHING
SRIPEDSG SRIPEDSG GOSUSG 25.05.2018 1:1 A3 mm GI 2MM BLACK
A ISSUED FOR APPROVAL 28.05.2018 SRIPEDSG FRCASG GOSUSG DRAWING NO. PART NO. PROJECTION PAGE

REV DESCRIPTION DATE PREPARED CHECKED APPROVED

You might also like