Safety information
WARNING
The instructions in this manual are not intended as a substitute for
proper training or adequate experience in the safe operation of the Before installing, operating, maintaining, or testing this equipment,
equipment described. Only competent technicians who are carefully read and understand the contents of this manual. Improper
familiar with this equipment should install, operate, and service it. operation, handling or maintenance can result in death, severe personal
injury, and equipment amage.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high- and low-voltage safe
operating practices and procedures. WARNING
• Is trained and authorized to energize, de-energize, clear, and
This equipment is not intended to protect human life. Follow all locally
ground power distribution equipment.
approved procedures and safety practices when installing or operating
• Is trained in the care and use of protective equipment such as this equipment. Failure to comply can result in death, severe personal
flash clothing, safety glasses, face shield, hard hat, rubber
injury and equipment damage.
gloves, hotstick, etc.
Following is important safety information. For safe installation and
operation of this equipment, be sure to read and understand all
cautions and warnings. WARNING
Power distribution and transmission equipment must be properly
Hazard statement definitions selected for the intended application. It must be installed and serviced by
This manual may contain four types of hazard statements: competent personnel who have been trained and understand proper
safety procedures. These instructions are written for such personnel and
are not a substitute for adequate training and experience in safety
DANGER: Indicates an imminently hazardous situation procedures. Failure to properly select, install, or maintain power
which, if not avoided, will result in death or serious distribution and transmission equipment can result in death, severe
injury.
personal injury, and equipment damage.
1
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
Product information
Introduction Handling and storage
Service Information S280-43-1 provides installation, operation, and Be careful during handling and storage of the recloser to minimize
maintenance instructions for the NOVA i three-phase, micropro- the possibility of damage. Refer to the Moving the Recloser and
cessor-controlled recloser. Before installing and operating this Lifting the Recloser sections. If the recloser is to be stored for any
recloser, carefully read and understand the contents of this length of time prior to installation, provide a clean, dry storage
manual. area.
2
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
Table 1
Voltage ratings (kV)
Description 15 kV 27 kV 38 kV
Table 2
Current ratings (A)
Description 15 kV 27 kV 38 kV
Table 3
Mechanical ratings
Description 15 kV 27 kV 38 kV
Table 4
Duty cycle*
Percentage of Number of Minimum
Type Interrupting Rating Unit Operations Circuit X/R Value
NOVA i 15-20 44 4
45-55 56 8
90-100 16 17
Total 116
*Compliant with IEC 62271-111 2005
*Compliant with IEEE Standard C37.60-2012 ™
3
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
E
394 394
Terminal
connectors
A A
Terminal C
connectors
298
1000
285
Figure 2.
NOVA i Three-phase recloser dimensions.
Terminal options A B C D E
Eyebolt, 1/0-500mcm
89 NOVA 15i 809 528 400.5 260
Cable range (630 a max.)
Eyebolt, 4/0 - 1000 mcm
111 NOVA 27i 908 627 400.5 260
Cable range (800 a max.)
Flat Pad, 2-hole
119 NOVA 38i 1007 676 441.1 298.6
(630 a max.)
Flat Pad, 4-hole
121
(800 a max.)
Creepage distances
Description Creepage distance (mm) Creep (mm/kV)
4
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
Terminal
connectors
Terminal
connectors
Integrated
voltage
sensor
Figure 3.
NOVA 15i recloser dimensions with 3 integrated voltage sensor option in load side.
5
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
Control-powered interface
The NOVA i recloser mechanism (see Figures 4 and 5) with the
control-powered interface is fully operational with a Form 6/FXD
microprocessor-based control equipped with the required dc-to-dc
converter, interface circuit, and a fully shielded 19-pin cable. The
control-powered interface includes a 19-pin receptacle on the
recloser and an internal heater (for humidity control) powered from
the control input power supply.
The dc-to-dc converter board converts the control’s 24 V dc battery
supply to 53 V dc to charge the trip/close capacitors in the NOVA i
mechanism. The dc-to-dc converter board also houses voltage
monitoring and conditioning circuits that protect the battery from
failure and provide trip/close operations without ac power. In the
absence of ac power to the electronic control, the control battery
will provide the trip and close operations. A complete four-trip
sequence with minimal reclose intervals as configured for each
control is obtainable without ac power. The recloser and control
system is capable of exceeding over one thousand operations on
battery power only.
4-Pin IVS Cable
Figure 5.
Control-powered NOVA i recloser configuration with potential
transformer input power.
Open/close
Aluminum mechanism contact position Control cable Ground connector
housing (standard) indicator Actuator board Ct protection board receptacle #10 - #2 stranded
Figure 4.
NOVA i recloser mechanism with control-powered interface (view from bottom of recloser with bottom cover removed).
6
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
Installation procedure
WARNING CAUTION
This equipment is not intended to protect human life. Follow all locally Personal injury. Bushings have sharp edges. Wear protective gloves
approved procedures and safety practices when installing or operating when handling the unit. Failure to do so can result in cuts and abrasions.
this equipment. Failure to comply can result in death, severe personal
injury, and equipment damage.
3. Install the recloser. Install the recloser in the appropriate
Cooper Power Systems pole- or substation-mounting frame. See
Figure 7 for moving and lifting instructions.
WARNING CAUTION
Hazardous voltage. Always use a hotstick when working with this Follow all locally approved safety practices when lifting and mounting
equipment. Failure to do so could result in contact with high voltage, the equipment. Use the lifting lugs provided. Lift the unit smoothly and do
which will cause death or severe personal injury. not allow the unit to shift. Improper lifting can result in equipment
damage.
When installing the recloser, refer to the applicable reclos-
er-mounting frame instructions. Installation instructions are
included with the mounting frame. Moving the recloser
1. Check the nameplate ratings. Make sure the ratings, settings, NOVA i reclosers are shipped in an enclosed crate and palletized.
and interface options on the recloser nameplate (see Figures 6 When moving with a fork truck/lift, the recloser must remain
and 13) are correct for the planned installation. bolted to the pallet to avoid damage to the OPEN/CLOSE contact
position indicator.
CAUTION
Tip-over Hazard. High center of gravity. Use a 4-point hitch to prevent
switchgear from overturning during lifting operations. Improper lifting
can result in personal injury or equipment damage.
Figure 6.
Nameplate.
Figure 7.
Moving and lifting the NOVA i recloser.
7
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
WARNING Bypass
switch
Hazardous voltage. Solidly ground all equipment. Failure to comply can
result in death, severe personal injury, and equipment damage.
CAUTION Figure 8.
Equipment Damage. Do not adjust or rotate bushing terminals. The ushing Connection diagram shows complete surge protection
terminals are factory-calibrated to meet the continuous current require- and illustrates bypass and disconnect switches.
ment of the switchgear. Adjusting or rotating the bushing terminals can
damage the encapsulated interrupter resulting in equipment damage or
personal injury.
IMPORTANT 5 3 1
The default connections use the horizontal bushing as the source side and the
vertical bushing as the load side. Also, the horizontal bushing may be used as the
load side and the vertical bushing as the source side. Note that reversing the
source and load bushings has no effect on overcurrent protection but may require
setting or wiring changes to the control for correct metering.
If equipped with internal voltage sensors, the horizontal bushings (1, 3, 5) must be
connected to the source. The internal voltage sensors cannot monitor source-side
voltage when the NOVA i recloser is in the OPEN position if the horizontal
bushings are connected to the load.
8
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
7. Remove control cables, power cables, and ground leads from IMPORTANT
recloser.
Note: Disconnecting the control cable on an energized Any external voltage sensor installed with the NOVA i recloser must have its
recloser will not damage the integrated CTs. ground referenced to the recloser ground.
8. Follow standard utility procedures regarding removal of
recloser from service.
3-wire ungrounded and impedance grounded systems
The use of a grounding mat may be required depending upon the
local safety regulations defining the permissible step and touch
potential levels. Consult local regulations for proper grounding
procedures.
9
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
Grounding with a local supply voltage trans- Grounding with a remote supply voltage trans-
former: 4-wire multi-grounded, 3-wire former: 4-wire multi-grounded, 3-wire
ungrounded, or impedance-grounded ungrounded, or impedance-grounded
Installation with a local supply voltage transformer must include Installation with a remote supply voltage transformer must include
the following (refer to Figure 10): the following (refer to Figure 11):
• Protection of the recloser bushings and the supplying • Protection of the recloser bushings and the supplying
transformer with lightning arresters. transformer with lightning arresters.
• Grounding of the recloser head and tank. • Grounding of the recloser head and tank.
• Grounding of the transformer tank. • Grounding of the transformer tank.
• Grounding of the control cabinet. • Grounding of the control cabinet.
• Grounding of the SCADA equipment. • Grounding of the SCADA equipment.
CONTROLLER
CONTROLLER
Figure 11.
Recommended grounding method for NOVA i reclosers
with microprocessor-based control and remote supply
Figure 10. voltage transformer.
Recommended grounding method for NOVA i recloser
with microprocessor-based control and local supply
voltage transformer.
10
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
CONTROLLER
Figure 12.
Recommended grounding method for NOVA i reclosers with microprocessor-based control on a 3-wire uni-grounded system.
11
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
WARNING
Hazardous voltage. Never rely on the open position of the operating
handle or the contact position indicator; it does not ensure that the line is
Nameplate
de-energized. Follow all locally approved safety practices. Failure to
comply can result in contact with high voltage, which will cause death or
severe personal injury.
Manual
The OPEN/CLOSE contact position indicator consists of a red OPEN/CLOSE Contact OPEN Handle
CLOSED and a green OPEN indicator located on the bottom of the Position Indicator
mechanism housing (see Figure 13).
Figure 13.
NOVA i recloser OPEN/CLOSE contact position indicator,
nameplate, and manual OPEN handle.
12
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
Voltage sensing option Refer to the Installation section of this manual for information on
the NOVA i recloser installation procedure. Refer to Service
Information S280-70-18 for further information on installing the
3 Internal voltage sensor in source side busing Form 6/FXD Pole-Mount control.
of recloser Verify the correct load-side and source-side terminal connections.
The internal voltage sensor is located internal to the NOVA i This is required for correct operation of the internal voltage sensor.
module and connected to the horizontal bushing. The internal Verify correct grounding of the NOVA i recloser and control prior to
voltage sensor is used to provide low voltage input to the Form making any high-voltage connections and before high-potential
6/FXD recloser control for metering and/or protective functionality. testing. A proper ground connection consists of a good electrical
The sensing option, cable, and control support a magnitude ground connection to the surge ground connector located on the
accuracy of 2% or better and a phase degree accuracy of ±1.5° mechanism housing. Provide a good electrical ground connection
throughout the temperature range of -40°C to +65°C. to the control cabinet ground.
Note: Painted surfaces of the mechanism housing may prevent a
3 Integrated voltage sensor in load side bushing ground connection to the recloser housing. Always provide a
good electrical connection to the recloser surge ground
of recloser connector.
The NOVAi recloser is available with 3 additional integrated voltage Poor grounding of the recloser housing may result in the
sensors in load side, which are behind the module and connected presence of high voltage on the housing associated with the
to the vertical bushings. The integrated voltage sensor is also used high-voltage resistor connections used with internal voltage
to provide low voltage input to the Form 6/FXD recloser control for sensing.
metering and/or protective functionality.
The sensing option, cable, and control support a magnitude CAUTION
accuracy of 2% or better and a phase degree accuracy of ±1.5°
throughout the temperature range of -40°C to +65°C. Hazardous voltage. Do not touch the female receptacle connections of the
voltage sensing cable. If the recloser is energized and the voltage
sensing cable is disconnected from the recloser or the control, a voltage
Installation clamped at 250 V ac will be present at the female receptacle. Contact
with this voltage can result in personal injury.
WARNING
This equipment is not intended to protect human life. Follow all locally The recloser is equipped with a 4-pin / 12-pin female receptacle
approved procedures and safety practices when installing or operating (see Figure 14) that connects to the control with a shielded, 4-pin /
this equipment. Failure to comply can result in death, severe personal 12-pin conductor cable. The control accessory includes a 4-pin /
injury, and equipment damage. 12-pin male receptacle on the control and appropriate circuitry;
refer to Figure 15.
WARNING
Hazardous voltage. Solidly ground all equipment. Failure to comply can
result in death, severe personal injury, and equipment damage.
IMPORTANT
Optional Auxiliary
Disconnect switches for ac control power are necessary to isolate the control for Switch Receptacle
testing and servicing. Voltage Sensor Label
Figure 14.
NOVA i recloser cable receptacles with voltage sensing option.
(NOVA i recloser with 19-pin control interface shown.)
13
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
CAUTION
Equipment misoperation. Verify all connector pins and both mating
interface surfaces are clean and dry before connecting cables. Voltage
sensing errors can result from contamination. Failure to comply can
result in control and recloser misoperation. Voltage Sensor
Receptacle
CAUTION
Equipment Misoperation. Do not connect this control to an energized
recloser until all control settings have been properly programmed and
verified. Refer to the programming information for this control. Failure to
comply can result in control and recloser misoperation, equipment Figure 15.
damage, and personal injury. Form 6/FXD control voltage sensor receptacle..
14
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
When programming the Form 6/FXD, the PT connection must be 3.05 m N/A
set for a Wye connection. Also, the Phantom Phase feature must 6.10 m N/A
be disabled. Refer to Service Information S280-70-4 for more 9.15 m N/A
information on programming the Form 6/FXD control. Phase Shift, NOVA 27i
3.05 m N/A
Table 5 6.10 m N/A
Form 6 adjusted PT ratio 9.15 m N/A
Description PT Ratio Phase Shift, NOVA 38i
Description PT Ratio
Figure 16.
Form 6/FXD control system configuration screen.
15
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
Accessories Terminals
The standard terminal is a 2-hole flat-pad terminal rated 630 A. An
Auxiliary switch eyebolt, 1/0–500 mcm (630 A), eyebolt 4/0–1000 mcm (800 A), and
A three-stage auxiliary switch can be provided as an accessory. 4-hole flat-pad terminals, are available as an accessory (see Figure
Each stage has two independent contacts that permit any desired 17).
combination of “a” (follow state of recloser contacts) and “b”
The eyebolt and fixed-pad terminals are made of copper alloys.
(opposite recloser contacts) positions. The switch contacts are
Cooper Power Systems recommends terminal connection to
insulated for 600 V and have a continuous current rating of 10 A.
copper wires to optimize the electrical connection.
Their interrupting ratings are shown in Table 7.
Anti-oxide coatings for temporary protection of wire-brushed
Table 7 aluminum cable connections to flat-pad terminals must be
Auxiliary switch interrupting ratings maintained at intervals determined by the customer based on load
current, climate, and other installation conditions.
Inductive Non-Inductive Inductive Non-Inductive
ac ac dc dc Eyebolt terminals are recommended for copper conductors only.
Volts (A) (A) (A) (A)
24 – – 15.0 20.0
48 – – 7.5 10.0
Pole-mounting hanger
120 60 80 – –
125 – – 1.5 2.0 A pole-mounting hanger (see Figure 17), which bolts directly to the
recloser frame, is available for pole-mounting installation.
240 30 60 – –
250 – – 0.45 0.5
Terminal options A
Eyebolt, 1/0 - 500 mcm
89
Cable range (630 A max.)
Eyebolt, 4/0 - 1000 mcm
111
Cable range (800 A max.)
Flat Pad, 2-hole 119
(630 A max.)
Flat Pad, 4-hole 121
(800 A max.)
POLE
1085
637 B
290
POLE
Figure 17.
Dimensions of NOVA i recloser with pole-mounting hanger accessory.
16
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
Arrester-mounting brackets
The arrester-mounting bracket accessory (see Figure 18) can be bolted to the recloser frame and pole-mounting hanger for the addition
of inboard and outboard arresters. The arresters are not included with the brackets.
Figure 18.
Dimensions of NOVA i recloser with pole-mounting hanger and arrester-mounting bracket accessories.
17
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
Substation-mounting frame
A substation-mounting frame accessory (see Figure 19) is available for substation-mounting applications.
Terminal options A B C
Eyebolt, 1/0 - 500 mcm NOVA 15i
89 809 528
Cable range (630 A maximum) 110 kV BIL
Eyebolt, 4/0 - 1000 mcm NOVA 27i
111 908 627
Cable range (800 A maximum) 150 kV BIL
Flat Pad, 2-hole NOVA 38i
119 1007 676
(630 A maximum) 170 kV BIL
Flat Pad, 4-hole
121
(800 A maximum)
Figure 19.
Dimensions of NOVA i recloser with substation-mounting frame accessory.
18
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
Service information 1. Check the nameplate ratings. Make sure the ratings, settings,
and interface options on the recloser nameplate (see Figure 6)
Service requirements are correct for the planned testing.
The NOVA i recloser has been designed with a minimum mechani- 2. Test electrical open and close operation. Close and open the
cal life of 10,000 operations. The NOVA i recloser requires routine recloser contacts using the microprocessor control. Confirm that
inspection to check for physical damage and verify proper opera- the contacts have closed and opened by:
tion.
A. The OPEN/CLOSE contact position indicator, or
B. By a continuity check between the recloser terminals.
Frequency of inspection
Because these reclosers are applied under widely varying operat- 3. Test manual open. Pull the yellow manual open handle (see
ing and climatic conditions, service intervals are best determined Figure 13) down to open the recloser contacts. Confirm that the
by the user based on actual operating experience. contacts have opened by:
A. The OPEN/CLOSE contact position indicator, or
Testing operation
This recloser is used with the Form 6/FXD microprocessor-based B. By a continuity check between the recloser terminals.
recloser controls. Refer to the control operation manual. 4. To close the recloser contacts:
A. First, push the yellow manual open handle up.
WARNING
B. Close the recloser using the microprocessor-based control.
This equipment is not intended to protect human life. Follow all locally
approved procedures and safety practices when installing or operating
this equipment. Failure to comply can result in death, severe personal
injury and equipment damage.
19
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
WARNING
Radiation. At voltages up to the specified test voltages, the radiation
emitted by the vacuum interrupter is negligible. However, above these
voltages, radiation injurious to personnel can be emitted. See Service
Information S280-90-1, Vacuum Interrupter Withstand Test Voltage
Ratings Information for further information.
TEST 3
Use the following procedures to perform high-potential withstand Open contact Open contact
tests at 75% of the rated low-frequency withstand voltage for 60
seconds. See Table 8 for test voltages and Figure 20 for test
5 6 5 6
connection diagrams.
ac ac
Test results for NOVA i reclosers equipped with the internal 3 4 3 4
voltage sensing option will be influenced by the source-to-ground
connected sensing resistor, especially if dc high-potential testing is 1 2 1 2
performed.
Table 8
NOVA i Recloser withstand test voltage ratings information.
TEST 2
1. Close the recloser contacts.
2. Ground the recloser.
3. Ground Phase A (terminal 2) and Phase C (terminal 6).
4. Apply proper test voltage to Phase B (terminal 3).
5. The recloser should withstand the test voltage for 60 seconds.
20
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)
If the recloser does not pass Tests 1, 2, or 3, contact an authorized • Check all cables for proper connection.
service center or your Cooper Power Systems representative. • Verify that the control has power.
Test results for NOVA i reclosers equipped with the internal • Upon loss of ac power, check recloser control battery level.
voltage sensing option will be influenced by the source-to-ground
connected sensing resistor, especially if dc high-potential testing is • Check the fusing on the dc-to-dc converter board located in the
performed. control cabinet.
21
NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective January 2017
instructions (S280-43-1)
5 R3-G
B R1-H b
BØ CT 6
X1 R3-H
K R1-K
7 R3-E
C R1-J a
CØ CT 8 R3-F
X1
"CTP"
9 R3-L
CURRENT TRANSFORME R b
10 R3-M
11 R3-J
a
1 12 R3-K
2 –
"C1" "AS"
"CC " +
3 +
"AB" 4
ACTUATOR 5
CIRCUIT BO ARD 6
7 + – "C2"
+
"TC" LEGEND
8
53Vdc SYMBOL DESCRIPTIO N
9 R1-T
53Vdc AB Actuator Circuit Board
10 R1-S
AS Auxiliary Switch - 3 Stage
53Vdc
11 R1-R C1 Close Capacitor
Common C2 Trip Capacitor
"P1" 12 R1-P
CC Close Coil
13 Common
R1-N TC Trip Coil
Common MS1 Micro Switch, Contact Position Indicator
14 R1-L
MS2 Micro Switch, Contact Position Indicator
15 MS3 Micro Switch, Open Handle - Disables
16 Closing Circuit
COM 52a or a Contact - Open When Unit is Open
17 "MS3" 52b or b Contact - Closed When Unit is Open
N.O.
18 R1 Receptacle, Control - 19-Pin Male
R3 Receptacle, Auxiliary Switch - 14-Pin Male
19 H1 Resistive Heater
COM N.C. Open H2 Resistive Heater
20 R1-C
"MS1" 52a VTC Pull Up 2 CTP Current Transformer Protector
21 R1-A CT Current Transformer
COM N.O. Close
22 R1-E
"MS2" 52b VTC Pull Up 1
23 R1-B
R1-M
R1-U
"H2" "H1"
R1-V
Figure 21.
Wiring diagram for NOVA i recloser with control-powered interface (19-pin receptacle).
22
Instructional Literature IL0104001E NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective January 2017 microprocessor-controlled; installation and operation
instructions (S280-43-1)