Professional Documents
Culture Documents
Current Rating Considerations in Designi
Current Rating Considerations in Designi
Abstract—Ampacity calculations for high voltage direct current Tcab , T4 Internal and external thermal resistances of the
(HVDC) cables are more difficult than those for the ac cables be- cable, (K·m/W).
cause of the absence of suitable analytical formulas. The current U0 Maximum operating voltage or, alternatively, as
carrying capability of such cables is not only limited by the op-
erating temperature, but also by the electrical stress within the impulse level of the cable installation (kV).
insulation. The IEC60287 standard only considers the thermal lim- Wc Conductor losses, (W/m).
itations of the conductor current and, therefore, cannot be used for κ Electrical conductivity of the insulation material,
some HVDC applications because it fails to include the analytical (S/m).
derivations of the stress-limited rating equations. However, appli- α Field temperature dependency coefficient, (1/K).
cations of the HVDC cables are becoming more common and so
there is a need to extend the IEC standard methodology so that am- αc Conductor coefficient of electrical resistance,
pacity calculations can be performed for such installations. This (1/K).
paper considers various aspects of the HVDC cable design and how γ Field dependency coefficient, (mm/kV).
they influence cable rating. It focuses on the temperature difference ρi , ρj Thermal resistivity of the insulation and the
across the electrical insulation and the entire cable as a means of jacket, respectively, (K·m/W).
representing the maximum dielectric stress as the current limiting
factor when calculating ratings for HVDC cables. ρ1 , ρ2 Thermal resistivity of the wet and dry soil, re-
spectively, (K·m/W).
Index Terms—High-voltage power cables, direct current, Δθcab Temperature difference across the cable, (°C).
ampacity.
Δθcab,m ax Maximum temperature difference across the ca-
NOMENCLATURE ble, (°C).
dc Conductor diameter, (mm). ΔθF Temperature rise (drop) caused by the neighbour-
E(r) Electric field strength at the distance r from the ing heat (cooling) sources, (°C).
cable centre, (kV/mm). ΔθI Temperature difference across the insulation,
IT D Field limited current, (A). (°C).
IT D ,20 Field limited current corresponding to the con- ΔθI ,m ax Maximum temperature difference across the in-
ductor resistance of 20 °C, (A). sulation, (°C).
Itherm Thermally limited current, (A). Δθx Critical cable surface temperature rise at which
n Number of cable conductors. the drying out occurs, (°C).
ri , ro Inner and outer radii of the insulation, (mm). θam b Soil ambient temperature, (°C).
R DC resistance of the conductor, (Ω/m). θc. m ax Thermal temperature limit on the conductor tem-
R20 DC resistance of the conductor at 20 °C, (Ω/m). perature, (°C).
s Thickness of the insulation, (mm). θe Temperature of the cable surface, (°C).
T1 , T2j , Thermal resistances of the insulation, jacket θ0 Temperature reference value for field calcula-
T2 and T3 around each core, armour bedding and armour tions, (°C).
serving, respectively, (K·m/W).
TI Thermal resistance of the insulation (it is different I. INTRODUCTION
from T1 because the latter includes the conductor HE application of HVDC cables is increasing as the inter-
and insulation shields), (K·m/W). T connector and long submarine applications become more
common. Apart from the installation cost, DC cables have sev-
Manuscript received July 27, 2017; revised October 16, 2017 and November eral advantages over their alternating current counterparts. How-
30, 2017; accepted January 5, 2018. Date of publication February 7, 2018;
date of current version September 25, 2018. Paper no. TPWRD-00982-2017. ever, rating of such cables is more difficult due to an absence
(Corresponding author: George J. Anders.) of suitable analytical formulas. The standardized rating calcula-
H. Brakelmann is with the BCC Câble Consulting, Rheinberg 47495, tions of IEC60287 [1] are only thermally limited, meaning that
Germany (e-mail: heinrich.brakelmann@uni-due.de).
G. J. Anders is with the Department of Microelectronics and Computer Sci- the standard cannot be directly used for the rating of HVDC
ence of the Technical University of Lodz, 90-924 Poland, and Anders Consulting cable systems where the limits of the electric field stress over
Ltd., Toronto, ON, Canada (e-mail: george.anders@bell.net). the insulation might become an issue.
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. Construction of the HVDC cables is quite similar to that
Digital Object Identifier 10.1109/TPWRD.2018.2803279 of the HVAC counterparts. Apart from the insulation material,
0885-8977 © 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
2316 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 5, OCTOBER 2018
are illustrated with a practical numerical example. Section III ad- After some transformations [5], [8], [10], (4) takes the form:
dresses ampacity calculations when the temperature difference δ −1
δ · U0 r
across the insulation or the whole cable is an input parameter. E(r) = (6)
The effects of the soil dryout in the vicinity of the loaded cable ri (ro /ri )δ − 1 ri
as well as the presence of artificial or natural cooling of the
cable surface is also discussed in this Section. Section IV talks β+ε ρi
δ= β=αWc (7)
about the effect of the cable laying depth on its current rating. ε+1 2π
It includes a real-life numerical example. The effect of other In the field equations, α is used as a temperature coefficient
heat sources in the vicinity of the loaded cables on the HVDC of the electrical insulation. Later, αc is used as the temperature
cable rating is discussed in Section V. Section VI considers coefficient of the conductor material resistance (= 0.0039 1/ K
the question whether it is reasonable to cool the HVDC cable for copper).
circuits. The next section examines the effect of the selected Note, that in (7) – except for a geometric factor – the term
value of the permissible temperature drop across the cable on (β/α) describes the temperature difference across the electri-
the cable rating. The final section contains the discussion and cal insulation, through which it is directly correlated with the
conclusions. maximum electrical field strength.
We will illustrate the calculations with the data given in the
II. LIMITING ELECTRICAL FIELD STRENGTHS OF HVDC following numerical example.
CABLES
Whenever the electrical insulation of an HVDC cable is under A. Numerical Example
a capacitive control, that is, is dependent only on the geometry, Let us consider a 525-kV-HVDC cable with the XLPE
similarly to the case of the HVAC cables, the resulting field insulation, 2500 mm2 copper conductor (stranded; diameter
strength (“Laplace field strength”) E(r) is given, as a function dc = 61.2 mm; temperature coefficient αc = 0.0039/K). The
of the radial distance r from the cable center: insulation thickness is s = 26.0 mm, and the thicknesses of
U0 the inner and outer semiconducting shields are 1.9 mm and
E(r) = (1) 2.0 mm, respectively. (thermal resistivity of the insulation is
r ln (ro /ri )
ρi = 3.5 K m/W ). Thus, the inner and outer radii of the elec-
with the maximum field strength at the inner border of the
trical insulation become ri = 32.5 mm and ro = 58.5 mm, re-
insulation (r = ri ; surface of the inner conductive layer) and
spectively. The cable jacket has an outer diameter of 135.0 mm
where ro is the outer radius of the insulation. For a given design
and a thickness of 5.0 mm (ρj = 5.0 K m/W ). The maximum
limit Em ax of the field strength – either for the operating voltages
permissible conductor temperature is θc. m ax = 70 ◦ C . The con-
or for the impulse voltages – the minimal wall thickness sm in
ductor resistance at 20 °C is R20 = 7.2 · 10−6 Ω/m (measured at
of the electrical insulation is obtained from (1) as:
the completed cable).
sm in = ri eU 0 /(r i E m a x ) − 1 (2) To use (6), we need the material constants, which are equal
to: α = 0.115 /K; γ = 0.030 mm/kV and can be found, for ex-
Two values of Em ax at the conductor shield, one for the ample, in [6] and [8].
stationary voltage U0 and another value for the impulse voltage Switching the operating voltage onto the still cold cables
level will provide two minimum insulation thicknesses, where results (by capacitive control) in the Laplace field strengths at
the greater one will be selected. the inner and outer surfaces of the electrical insulation equal to:
The value of Em ax at U0 may, but does not have to be, the
E (ri ) = 27.5 kV/mm E (ro ) = 15.3 kV/mm
same for the maximum field strength at the outer shield (in our
example, later in the text, it is the same). These values are lower than a limit design of 30 kV/mm,
Thereafter, this design thickness must be compared with the which is chosen for this case (this is a typical value but may
limit values for the electrical field distribution, which will result differ for different cable designs).
from the critical operation conditions of the warmed-up cable.
For this, let us consider an electrical insulation made of a B. Ampacity Limit
synthetic material, for which the electrical conductivity κ is
We start with a given temperature θe of the cable surface (this
dependent on the field strength and temperature represented by
may correspond, for example, to the case of a surface cooling
the coefficients γandα in the following relation [7]–[11]:
of the cable). Considering the thermal aspects only, the current
κ(E, θ) = k · eα ·(θ −θ 0 ) · eγ ·E (3) rating is obtained from a standard equation [1]:
which can be approximated by (e.g., [8]): θc,m ax − θe θc,m ax − θe
ε Itherm = =
α ·(θ −θ 0 ) E R · (T1 + T2j + nT2 + nT3 ) R · Tcab
κ(E, θ) = k · e · (4)
E0 (8)
where R is the DC conductor resistance at the maximum operat-
where
ing temperature, n is the number of conductors and T1 , T2j , T2
ε = γU0 /(ro − ri ) (5) and T3 represent thermal resistances of the insulation, jacket
2318 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 5, OCTOBER 2018
Fig. 6. Two 525 kV-HVDC cable systems (with lossless return conductors)
in a common trench.
In this example, we can observe that for all laying depths the
thermal limited ampacity remains lower than the field limited
rating. With the required rating of 1905 A, the thermal limit
remains adequate, but falling below this value for greater laying
depths. For a laying depth of, say, 5.0 m the thermally limited
current is reduced to 1729 A. But in urban areas, such laying
depths may be quite normal when the existing infrastructures
must be crossed below.
The dotted lines in Fig. 7 are valid for ΔθF = −20.0◦ K,
that is, they correspond to a cooling of the cable surrounding
by 20 K. It becomes clear, that this additional cooling would
compensate the rating reduction for depths of up 10.0 m.
Fig. 7. Thermal and field limited currents as functions of the laying depth
h for Δθc a b , m a x = 20 K, θa m b =15 °C. The continuous lines represent no V. THERMAL BOTTLENECKS CAUSED BY OTHER HEAT
cooling and the dotted lines correspond to ΔθF = −20 °C. SOURCES
Most HVDC projects are large scale (320 kV or above) to
and justify their economic aspect, thus, a special cable corridor is
normally designed to minimize interference with other utili-
θc,m ax − θam b − ΔθF − θx ties. However, this most likely will not be the case in the fu-
Itherm =
R20 [1 + αc (θc,m ax − 20)] (Tcab + νx nT4 ) ture. For example, in Germany there are now three 320 kV or
(20) 525 kV “power highways” are planned, with 2000 MW each,
with lengths of more than 500 km. From this, we can expect a
high probability that thermal hot spots will occur. For one of
IV. THERMAL BOTTLENECKS CAUSED BY LARGER LAYING these “power highways” an initial host spot will arise with the
DEPTHS
crossing of the river Elbe, where a duct or a small tunnel with
It is a well-known fact that increasing the laying depth of the a length of about 2 km must be built – containing more than
cables reduces their ratings. In this section, we will examine the one cable system (probably 2, 4 or more systems during future
effect of the laying depth on the HVDC cable ampacity. upgrading or extensions). Similar groupings of cables may arise
Let us consider a system of two 525-kV-HVDC circuits ar- for other crossings of rivers, highways and so on. As a result,
ranged in flat formation at a depth h in a common trench 2.20 m such situations are of interest and some examples are discussed
wide as shown in Fig. 6. The required ampacity of each cable is below.
1905 A, which results in a transmission power of 2000 MW per In this section, the current rating reductions of underground
circuit. HVDC cables, caused by the adjacent heat sources, will be
Application of the rating equations defined above results in discussed. The first example, frequently occurring in cities, is
the current ratings shown in Fig. 7. The blue straight line in a 110-kV-XLPE cable system at the same depth as the HVDC
Fig. 7 shows the thermally limited current Itherm as a function circuits (2500 Al-conductors, 1774 A/338.0 MVA; daily load
of the laying depth h without outside thermal interferences. The factor equal 0.80).
straight red line, obtained with (15), shows the corresponding We will also consider a district heat pipe in the vicinity of the
field limited current IT D for a maximum permissible tempera- HVDC cables with the inner temperature of 140 °C.
ture difference Δθcab,m ax = 20 K. The surrounding soil is as- The computed temperature rise of a HVDC cable in a hor-
sumed to be homogeneous (thermal resistivity equal 1.0 K m/W) izontal distance x is shown as a black line in Fig. 8 for the
with an ambient temperature of 15 °C. 110 kV cable heating and by the red line for the heat source. The
BRAKELMANN AND ANDERS: CURRENT RATING CONSIDERATIONS 2321
in somewhat uncharted waters, and many questions are “under It is shown in the numerical example involving two 525-kV-
consideration”. Perhaps, there should be more frank discussion HVDC cable circuits in a typical arrangement that their current
and information sharing about such parameters. rating may easily fall below the required transmission capacity,
The rating equations are derived with a given maximum per- especially for greater laying depths and/or in the presence of
missible temperature difference Δθcab,m ax across the cable. adjacent heat sources.
This temperature difference is derived from the prequalification Contrary to the general opinion that an additional forced cool-
tests. The current rating of the HVDC cables are derived here ing of HVDC cables will not be reasonable because of the in-
taking into account different laying arrangements and thermal creased electrical field strengths, the paper shows that in case
parameters. of the thermal hot-spots, an area-to-area cooling of the cables
It is shown that, in addition to the thermally limited current, a may result in an increase of the current rating and compensation
field limited rating must be considered. The field limited rating is for the thermal bottlenecks. Different cooling techniques can be
achieved by using the maximum permissible temperature differ- considered to execute the cooling function.
ence Δθcab,m ax , which is translated into the maximum permissi- When the field limited ampacity should be computed in ad-
ble electrical field strength for the stationary DC-operation. The dition to the standard thermal rating analysis is a question that
limit value for the electrical field strength for the same insulation may be asked. A review of the published literature suggests that
material may have different values specified by different man- such analysis should always be performed for the EHV (above
ufacturers. The 30 kV/mm used in this paper for the numerical 300 kV) cable installations. The authors believe that it might
studies is only one example, but which is close to the real values be prudent (but perhaps not always necessary) to computed the
encountered in practice. With our data of the XLPE insulation, field limited current for all HVDC cables, especially because
30 kV/mm corresponds to a maximum temperature difference the calculations are very simple as demonstrated in the paper.
across the cable of about 15 K, which, again, corresponds to At medium and low voltage levels, the insulation thickness is
the limiting value specified by some cable manufacturers. But much smaller than at higher voltages and, therefore, no signif-
the situation may be somewhat more complicated: sometimes icant temperature gradient of the electric field. Of course, this
different limit values are defined for the inner and the outer sur- temperature gradient will depend on the type of insulating ma-
faces of the insulation, other values again for joints and sealing terial and will be greater for the paper cables in comparison with
ends, and also for the radial and longitudinal field strengths, and an extruded construction.
so on. Thus, a maximum temperature difference is a nice (man-
ageable) simplification as a result of all these research aspects REFERENCES
of the HVDC cables. As mentioned before, this value has to be [1] IEC, Calculation of the continuous current rating of cables (100% load
established by a discussion with the manufacturer and it ranges factor), Parts 1 and 2, IEC-Publ. 60287, 2012–2016.
from 10 to 15 °C for the MIND cables and can be higher, up to [2] CIGRE WG B1.40, Offshore Generation Cable Connections, CIGRE TB
610. Paris, France, 2015.
20 °C for the XLPE construction. [3] B. M. Weedy and D. Chu, “HVDC extruded cables – parameters for
The derived equations have the same form as the rating equa- determination of stress,” IEEE Trans. Power App. Syst., vol. PAS-103,
tions in the IEC-publication 60287 [1] and can be used in the no. 3, pp. 662–667, Mar. 1984.
[4] Z. Y. Huang et al., “Thermal-electric rating method for mass impregnated
same way. The computational procedure can be summarized by paper insulated HVDC cable circuits,” IEEE Trans. Power Del., vol. 30,
the following steps. no. 1, pp. 437–444, Feb. 2015.
1. Calculate the thermally permissible current Itherm with (8) [5] Z. Y. Huang et al., “Current rating methodology for mass impregnated
HVDC cables,” in Proc. Elect. Insul. Conf., Ottawa, ON, Canada, Jun.
using the thermally permissible conductor temperature. 2013, pp. 513–517.
2. Calculate the temperature drop across the insulation [6] CIGRE WG B1.32, “Recommendations for testing DC extruded cable
ΔθI = Itherm RTI . systems for power transmission at a rated voltage up to 500 kV,” in Proc.
CIGRE TB 496, Paris, France, 2012.
3. If ΔθI ≤ ΔθI ,m ax , the current obtained is thermally lim- [7] T. Worzyk, Submarine Power Cables: Design, Installation, Repair, Envi-
ited by the conductor temperature and go to step 5. ronmental Aspects. New York, NY, USA: Springer-Verlag, 2009.
4. Otherwise, the rated current is limited by the ΔθI ,m ax . [8] G. Mazzanti and M. Mazinotto, Extruded Cables for High-Voltage Direct-
Current Transmission. Hoboken, NJ, USA: Wiley, 2013.
This means that the rated
current is field limited and is ob- [9] F. Buller, “Calculation of electrical stresses in dc cable insulation,” IEEE
tained from IT D = ΔθI ,m ax /RTI with the conductor Trans. Power App. Syst., vol. PAS-86, no. 10, pp. 1169–1178, Oct. 1967.
temperature rise obtained either from (10), if the max- [10] C. Eoll, “Theory of stress distribution in insulation of high-voltage dc
cables: Part I,” IEEE Trans. Elect. Insul., vol. EI-10, no. 1, pp. 27–35,
imum temperature increase across the cable is given, or Mar. 1975.
from its modification taking into account the external ther- [11] H. Brakelmann, “Optimization of HVDC-cables with natural and with
mal resistance: forced cooling (in German),” El.wirtsch, 1979, pp. 1069–1074.
[12] D. Parmar et al., “Heat pipes cool hot spots,” in Transm. Distrib. World,
Feb. 1997, pp. 53–59.
T2j + n (T2 + T3 + T4 ) [13] H. Brakelmann and G. J. Anders, “A novel cooling solution for an inter-
Δθcab,m ax = ΔθI ,m ax 1+ section of a 2 × 2 duct bank with HV cables crossed by a steam pipe,” in
T1 Proc. 9th Int. Conf. Insul. Power Cables, 2015, paper E3.6.
(21) [14] S. Cherukupalli, H. Brakelmann, and G. J. Anders, “BC hydro experience
5. Stop. to mitigate a hot spot along a 230 kV XLPE cable circuit using a novel
Note that in the above procedure the temperature increase cooling solution, ” CIGRÉ-rep. B1-106, Paris, France, Aug. 2016.
[15] H. Brakelmann and G. J. Anders, “Increasing ampacity of cables by an
across the insulation can be replaced by a similar value across application of ventilated pipes,” in Proc. 39th IEEE Ind. Appl. Conf., 2004,
the cable as explained in the paper. pp. 2288–2295.
BRAKELMANN AND ANDERS: CURRENT RATING CONSIDERATIONS 2323
Heinrich Brakelmann received the Ph.D. degree George J. Anders (F’99) authored or coauthored
from the Technical University of Aachen, Aachen, more than 100 papers in IEEE Transactions and
Germany, in 1973. For several years, he was with the wrote 3 books. He is the author of the computational
Felten & Guilleaume Energietechnik AG, Cologne, engine of CYMCAP, de facto industry standard in
Germany, as a leader of the R&D-unit. He became a cable rating calculations. His research interests in-
Professor with the University of Duisburg, in 1985. clude ampacity calculations of electric power cables.
He is the author of more than 230 technical publica- Dr. Anders is the recipient of 2016 IEEE Herman
tions and of 4 book publications in the field of cable Halperin Award in the field of Transmission and
technique as well as high-voltage and high-current Distribution and the Engineering Excellence Medal
problems. He currently leads the consulting firm BCC from the Association of Professional Engineers in the
Cable Consulting, Rheinberg, Germany. His research Province of Ontario.
interests include the power cable technologies. Prof. Brakelmann is a Member
of German VDE-working groups and of several CIGRE WGs.