SUPPLEMENT 09/2019

Table of Corrections

Description
Page
As Printed Correction
Live Parts. Energized conductive components.
Live Parts. Energized conductive components.
FPN: Examples of such locations include partially
protected locations under canopies, marquees, roofed
open porches, and like locations, and interior locations
Location, Damp. Locations protected from
subject to moderate degrees of moisture, such as some weather and not subject to saturation with water
basements, some barns, and some cold-storage or other liquids but subject to moderate degrees of
warehouses. moisture.
Location, Damp. Locations protected from FPN: Examples of such locations include partially
9 weather and not subject to saturation with water protected locations under canopies, marquees, roofed
or other liquids but subject to moderate degrees open porches, and like locations, and interior locations
subject to moderate degrees of moisture, such as some
of moisture.
basements, some barns, and some cold-storage
warehouses.
FPN: Examples of such locations include partially
protected locations under canopies, marquees, roofed
open porches, and like locations, and interior locations
subject to moderate degrees of moisture, such as some
basements, some barns, and some cold-storage
warehouses.

FPN No. 1: This analysis is not required for dwelling FPN No. 1: This arc-flash hazard analysis is not required
units but required for service equipment and other for dwelling units but required for service equipment and
18 electrical equipment not part of the individual dwelling other electrical equipment not part of the individual
units of residential condominiums and individual dwelling units of residential condominiums and individual
detached dwelling units. detached dwelling units.

Table 1.10.3.5(E) Elevation of Unguarded Live Table 1.10.3.5(E) Elevation of Unguarded Live
Parts Above Working Space Parts Above Working Space
Nominal Voltage Nominal Voltage
Elevation (m) Elevation (m)
31 Between Phases Between Phases
1001 - 7500 V 3.05 1001 - 7500 V 2.70
7501 - 35000 V 4.57 7501 - 35000 V 2.90
Add 9.5 mm per kV Add 9.5 mm per kV
Over 35 kV Over 35 kV
above 35 kV above 35 kV

3.0.2.20 Underground Installations. 3.0.2.20 Underground Installations.


(A) General. Underground conductors shall (A) General. Underground conductors shall be
165 be identified for the voltage and conditions identified for the voltage and conditions under
unSSder which they are installed. Direct- which they are installed. Direct-burial cables
burial cables shall comply with the provisions shall comply with the provisions of 3.10.2.1(F).
of 3.10.2.1(F).
(C) Protection from Damage. Conductors (C) Protection from Damage. Conductors
emerging from… Where direct-buried emerging from... Where direct-buried conductors,
conductors, raceways, or cables are subject to raceways, or cables are subject to movement by
movement by settlement or frost, they shall be settlement, they shall be installed to prevent
165 installed to prevent damage to the enclosed damage to the enclosed conductors or to the
conductors or to the equipment connected to the equipment connected to the raceways. Metallic
raceways. Metallic enclosures shall be enclosures shall be grounded.
grounded.

Page 1 of 1