Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Generator set data sheet

Model: C900 D6
Frequency: 60 Hz
Fuel type: Diesel

Spec sheet: SS14-CPGK


Noise data sheet (open/enclosed): ND50-OSHHP/ND50-CS550
Cooling system data: MCP-1080

Standby Prime
Fuel consumption kW (kVA) kW (kVA)
Ratings 925 (1156) 835 (1044)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 19.0 31.6 45.2 60.2 15.7 27.9 40.6 54.6
L/hr 72 120 171 228 59 106 154 207

Engine Standby Rating Prime Rating


Engine manufacturer Cummins
Engine model QST30-G3
Configuration Cast iron, 50º V12 cylinder
Aspiration Turbocharged and after-cooled
Gross engine power output, kWm 1007 910
BMEP at set rated load, kPa 2206 1993
Bore, mm 140
Stroke, mm 165
Rated speed, rpm 1800
Piston speed, m/s 9.9
Compression ratio 14:1
Lube oil capacity, L 133
Overspeed limit, rpm 2075 ±50
Regenerative power, kW 82
Governor type Electronic
Starting voltage 24 Volts DC

Fuel flow
Maximum fuel flow, L/hr 570
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 66

power.cummins.com
©2017 Cummins Inc. | DS367-CPGK (08/17)
Air Standby rating Prime rating
3
Combustion air, m /min 76.2 71.4
Maximum air cleaner restriction, kPa 6.2

Exhaust
3
Exhaust gas flow at set rated load, m /min 196.8 180.0
Exhaust gas temperature, °C 481 464
Maximum exhaust back pressure, kPa 10.1

Standard set-mounted radiator cooling


Ambient design, °C 40
Fan load, kW m 30
Coolant capacity (with radiator), L 169
3
Cooling system air flow, m /sec @ 12.7 mm H2O 19.1
Total heat rejection, Btu/min 27940 25790
Maximum cooling air flow static restriction mm H2O 12.7

Weights* Open Enclosed


Unit dry weight kgs 6246 RTF
Unit wet weight kgs 6426 RTF
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length Width Height


Standard open set dimensions mm 4302 1702 2139
Enclosed set standard dimensions mm RTF RTF RTF

Genset outline
Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

power.cummins.com
©2017 Cummins Inc. | DS367-CPGK (08/17)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 150/125 S/P HC6J 380-480

Ratings definitions
Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited-Time Prime Power (PRP) is in unlimited hours.
reliable utility source. Running Power (LTP) is in accordance with Continuous Power (COP)
Emergency Standby accordance with ISO ISO 8528. Ten percent is in accordance with
Power (ESP) is in 8528. overload capability is ISO 8528, ISO 3046, AS
accordance with ISO available in accordance 2789, DIN 6271 and
8528. Fuel stop power in with ISO 3046, AS 2789, BS 5514.
accordance with ISO DIN 6271 and BS 5514.
3046, AS 2789, DIN 6271
and BS 5514.

Formulas for calculating full load currents:

Three phase output Single phase output

kW x 1000 kW x SinglePhaseFactor x 1000


Voltage x 1.73 x 0.8 Voltage

For more information contact your local Cummins distributor


or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS367-CPGK (08/17)