Professional Documents
Culture Documents
Ch3 - Generator Model New
Ch3 - Generator Model New
1
One-Line Diagrams
Synchronous Generators
Synchronous Generator Model
Real and Reactive Power Generation and
Control
2
The main function of a one-line diagram /
single-line diagram is to portray the most
information in the simplest manner possible.
A three-phase power system drawing
showing generators, transformers,
transmission lines, capacitors, reactors and
loads are normally drawn with a single line
joining such devices.
3
Large-scale power is generated
by three-phase synchronous
generators:
◦ driven either by steam turbines,
hydroturbines, or gas turbines.
5
◦ Figure below illustrate an elementary two-pole three-
phase generator. The stator contains three coils, aa’ ,
bb’ , and cc’ , and displaced from each other by 120˚.
◦ The concentrated full-pitch coils
represent distributed windings
producing sinusoidal mmf
waves concentrated on the
magnetic axes of the respective
phases.
◦ When the rotor is excited to
produce an air gap flux per
pole and revolving with
constant angular velocity ω,
the flux linkage of the coil
varies with the position of the
rotor mmf axis ωt. 6
◦ The flux linkage for an N-turn concentrated coil aa’
will be maximum at ωt = 0, and zero at ωt = /2.
The flux linkage with coil a is
a = N cos ωt
◦ the voltage induced in coil aa’ is
obtained from faraday’s law as
d
ea N sin t
dt
E max sin t
E max cos( t )
where, 2
N is number of turns in phase a
E max N 2 f N
7
◦ The rms value of the generated voltage is
2 f N
E 4.44 f N
2
◦ In actual ac machine windings, armature coil is
distributed in a number of slots. Since the emfs
induced in different slots are not in phase, their
phasor sum is less than their numerical sum.
E 4.44 Kw f N
Kw factor is about 0.85 ~ 0.95 8
◦ The magnetic field of the rotor revolving at constant
speed induces three-phase sinusoidal voltages in the
armature, displaced by 2/3 radians. The frequency of
the induced armature voltages depends on the rotor
speed n (in rpm an referred as synchronous speed ),
and number of poles P, is given by
P n
f
2 60
◦ During normal conditions, the generator operates
synchronously with the power grid. Assuming the
current in phase a is lagging the generated emf ea by an
angle , the instantaneous armature currents are
ia I max sin ( t )
2
ib I max sin ( t )
3 4
ic I max sin ( t ) 9
3
Figure shows a typical synchronous
machine field alignment for operation
as a generator using space vectors to
represent the various fields.
• When rotor is revolving at
synchronous speed and the
armature current Ia is zero, the
field mmf Fr produces the no-load
generated emf E in each phase.
10
• When the armature is carrying
balanced three-phase currents, Fs
is produced perpendicular to line
mn.
• The interaction of armature mmf Fs
and the field mmf Fr , known as
armature reaction, gives rise to the
resultant air gap mmf Fsr .
• the resultant mmf is responsible
for the resultant air gap flux sr
that induces the generated emf
on-load Esr .
◦ The armature mmf Fs induces the emf Ear , called armature
reaction voltage, which is perpendicular to Fs .
◦ The voltage Ear leads Ia by 90˚and can be represented by a
voltage drop across a reactance Xar due to the current,Ia.
(Xar reactance of the armature reaction). 11
• The phasor sum of E and Ear is
shown by Esr represents the on-
load generated emf.
E = Esr + j Xar Ia
◦ The terminal voltage V is less
than Esr by the amount of
resistive voltage RaIa and
leakage reactance voltage Xl Ia
E = V + [Ra + j( Xl + Xar )] Ia
E = V + [Ra + j Xs ] Ia
◦ where Xs =( Xl + Xar ) is the
synchronous reactance.
◦ angle between I and V, cos Θ
represents the power factor
at the generator terminals
12
• The power developed by the machine
is proportional to the product of field
mmf Fr , air gap mmf Fsr and sin r
and dictates the action of the
synchronous machine.
◦ when Fr is ahead of Fsr by an angle r
operating as a generator
◦ when Fr falls behind Fsr by an angle r
operating as a motor
◦ Since E and Esr are proportional to Fr and Fsr , power
developed by machine proportional to E , Esr and sin r
angle r known as the power angle
◦ usually the developed power is expressed in terms of
◦ Excitation voltage E
◦ Terminal voltage V and sin
* r leakage impedance is very small
compared to the magnetization reactance. 13
• Due to nonlinearity of the machine magnetization curve, the
synchronous reactance is not constant.
• For operation at or near terminal voltage, it is usually assumed
that the machine is equivalent to an unsaturated one;
magnetization curve is a straight line through origin and the
rated voltage point on the open-circuit characteristic.
◦ For steady-state analysis, the saturated value of the
synchronous reactance corresponding to the rated voltage
is used E = V + [R + j X ] I
a s a
◦ the armature resistance is much
smaller than the synchronous
reactance and often neglected.
◦ Equivalent circuit connected to an
infinite bus reduces to
E = V + j Xs Ia
14
15
E = V + [Ra + j Xs ] Ia
E = V + j X s Ia
16
• The phasor diagram of the generator with terminal voltage as
reference for excitations corresponding to lagging, unity, and
leading power factors is shown below.
E = V + [Ra + j Xs ] Ia
17
◦ the voltage regulation of an alternator is used for
comparison with other machines – defined as the
percentage change in terminal voltage from no-load
to rated load. Gives an indication of the change in
field current required to maintain system voltage at
some specific power factor.
|Vnl | |Vrated | | E | |Vrated |
VR 100 100
|Vrated | |Vrated |
18
P3.1: A three-phase, 318.75 kVA, 2300 V alternator (generator) has an
armature resistance of 0.35 Ω /phase, and a synchronous reactance of
1.2 Ω /phase. Determine the no-load line-to-line generated voltage and
the voltage regulation at:
a) Full-load kVA, 0.8 power factor lagging, and rated voltage.
E = V + [Ra + j Xs ] Ia
E 1327.9 (0. 35 j1.2)(80 36.87 ) 1409. 22.44
E LL 3 E 3 1409. 2 2440.8 V
|Vnl | |Vrated | | E | |Vrated |
the voltage regulation VR 100 100
|Vrated | |Vrated |
|2440.8 | |2300|
100 6. 12%
|2300| 19
Before a generator can be connected to the grid system,
FOUR condition must be satisfied:
◦ Frequency
21
◦ When the synchronous machine is connected on an
infinite busbar, its speed an terminal voltage are fixed
and unalterable.
| E ||V |
P3 3 sin
Xs
|V |
Q3 3 (| E |cos |V |)
Xs
24
| E ||V |
P3 3 sin
Xs
When |E| < |V| the reactive power to the bus is negative,
or the bus is supplying positive reactive power to the
generator. the generator is said to be underexcited.
26
From Figure 3.4, neglecting the armature
resistance, the output power is equal to the power
developed.
28
From Figure 3.6, | E ||V |
P3 3 sin
cd = E1 sin 1 = Xs Ia1 cos Θ1 Xs
29
◦ From the previous equation: E = V + j Xs Ia
For a lagging power factor armature current Ia1
results in E1
31
32
33
E = V + [Ra + j Xs ] Ia
E = V + j X s Ia
34
Load representation – impedance or power
Voltage across the load
Load power – not necessarily the full rated
power of the generator
Any line impedances?
Difference between line impedance and
generator reactance, Xs
35
36
A 50 MVA, 30 kV, three-phase, 60 Hz
synchronous generator has a
synchronous reactance of 9 Ω per phase
and a negligible resistance.
37
a) Determine the excitation voltage per phase E and
the power angle .
The 3-phase apparent power is:
𝑆3∅ = 50∠𝑐𝑜𝑠 −1 0.8 = 50 ∠36.87° 𝑀𝑉𝐴
= 40 MW + j30 Mvar
The rated voltage per phase is:
30
𝑉= = 17.32∠0° 𝑘𝑉
3
The rated current is:
∗
𝑆3∅ 50 ∠36.87° 103
𝐼𝑎 = ∗
= = 962.25 ∠ − 36.87° 𝐴
3𝑉 3 17.32 ∠0°
The excitation voltage per phase is:
𝐸 = 𝑉 + 𝑗 𝑋𝑆 𝐼𝑎
𝐸 = 17320.5 + 𝑗9 962.25 ∠ − 36.87° = 23558∠17.1°𝑉
38
b) With the excitation held constant at the value
found in (a), the driving torque is reduced until
the generator is delivering 25 MW. Determine the
armature current and power factor.
41
42
The generator from Ex 3.1 is delivering 40MW at a
terminal voltage of 30kV.
Compute the power angle, armature current, and
power factor when the field current is adjusted for the
following excitation:
a) The excitation voltage is decreased to 79.2% of the
value found in Ex 3.1
The new excitation voltage is:
𝐸 = 0.792 × 23558 = 18657 𝑉
The power angle is:
𝐸 𝑉
𝑃3∅ =3 𝑠𝑖𝑛𝛿
𝑋𝑠
−1
40𝑀 9
𝛿 = 𝑠𝑖𝑛 = 21.8°
3 18.657𝑘 17.32
43
The armature current is:
44
45
The generator from Ex 3.1 is delivering 40MW at a
terminal voltage of 30kV.
Compute the power angle, armature current, and
power factor when the field current is adjusted for the
following excitation:
b) The excitation voltage is decreased to 59.27% of the
value found in Ex 3.1
The new excitation voltage is:
𝐸 = 0.5927 × 23558 = 13963 𝑉
The power angle is:
𝐸 𝑉
𝑃3∅ =3 𝑠𝑖𝑛𝛿
𝑋𝑠
−1
40𝑀 9
𝛿 = 𝑠𝑖𝑛 = 29.748°
3 13.963𝑘 17.32 46
The armature current is:
47
The generator from Ex 3.1 is delivering 40MW at a
terminal voltage of 30kV.
𝐸 𝑉
𝑃3∅ =3 𝑠𝑖𝑛𝛿
𝑋𝑠
40 (9)
𝐸= = 6.928 kV
3 17.32 (1)
48
The armature current is:
49
TUTORIAL QUESTIONS
Generator
50
51
52
53
MVA
54
55
56
57
58
59
60