Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 25

Project Name DATA CENTER CLARO

Peru ,lima
Date 2020 / 5 / 23

Calculation and Selection Result

A.Project Overview

Project Name DATA CENTER CLARO


Country Peru
City lima
Address
Client Name
Client Address
Reference
Revision
Project Date 5 / 23 / 2020
Altitude m
Cooling Condition: Indoor Dry-bulb 27.0 °C
Cooling Condition: Indoor Wet-bulb 19.0 °C
Cooling Condition: Outdoor Dry-bulb 34.1 °C
Cooling condition: Outdoor wet bulb 26.6 °C
Heating Condition: Indoor Dry-bulb 20.0 °C
Heating Condition: Outdoor Dry-bulb 7.0 °C
Heating Condition: Outdoor Wet-bulb 6.0 °C

B.Material List

Model Quantity Description


MV5-X280W/V2GN1 2 All DC Inverter V5 X (380V)
MDV-D36Q4/VN1-A3 14 Compact Four-way Cassette
MDV-D22Q4/VN1-A3 6 Compact Four-way Cassette
MDV-D28Q4/VN1-A3 12 Compact Four-way Cassette
MV5-X252W/V2GN1 1 All DC Inverter V5 X (380V)
MV5-X450W/V2GN1 1 All DC Inverter V5 X (380V)
MDV-D56Q4/VN1-E 4 Four-way Cassette (E
series,silent type)
FQZHN-03D 6 Branch Joint
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

Model Quantity Description


FQZHN-02D 2 Branch Joint
FQZHN-01D 26 Branch Joint
FQZHW-02N1D 2 Branch Joint
Ø31.8 50.8 m Copper Pipe
Ø25.4 17.2 m Copper Pipe
Ø22.2 12.1 m Copper Pipe
Ø19.1 86.1 m Copper Pipe
Ø15.9 54.8 m Copper Pipe
Ø12.7 169.7 m Copper Pipe
Ø9.53 58.1 m Copper Pipe
Ø6.35 108.4 m Copper Pipe
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

Primer Piso

1.1 Material List

Model Quantity Description


MV5-X280W/V2GN1 2 All DC Inverter V5 X (380V)
MDV-D36Q4/VN1-A3 6 Compact Four-way Cassette
MDV-D22Q4/VN1-A3 1 Compact Four-way Cassette
MDV-D28Q4/VN1-A3 8 Compact Four-way Cassette
FQZHN-03D 1 Branch Joint
FQZHN-02D 1 Branch Joint
FQZHN-01D 12 Branch Joint
FQZHW-02N1D 1 Branch Joint
Ø31.8 18.0 m Copper Pipe
Ø25.4 2.0 m Copper Pipe
Ø22.2 1.6 m Copper Pipe
Ø19.1 32.3 m Copper Pipe
Ø15.9 34.5 m Copper Pipe
Ø12.7 53.5 m Copper Pipe
Ø9.53 50.5 m Copper Pipe
Ø6.35 51.5 m Copper Pipe
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

1.2 Indoor Unit Specifications

IDU Name Model Sound (dB(A)) Weight(kg) Dimension(mm) Power Supply Rated Power(W) MCA(A) MFA(A)
WxHxD
IAC-3 MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-1 MDV-D22Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-3 MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-2 MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-3 MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-3 MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-2 MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2 MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2 MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2 MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2 MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2 MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2 MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-3 MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-3 MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

IDU Name Model Cooling AT Req.TC TC Req.SC SC Heating AT Req.HC HC Air flow ESP
(°C) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (°C) (Btu/h) (Btu/h) (m^3/h) (Pa)
IAC-3 MDV-D36Q4/VN1-A3 27.0/19.0 0 11,514 0 7,665 20.0 0 13,033 496(High) N/A
IAC-1 MDV-D22Q4/VN1-A3 27.0/19.0 0 7,054 0 5,124 20.0 0 7,829 397(High) N/A
IAC-3 MDV-D36Q4/VN1-A3 27.0/19.0 0 11,549 0 7,688 20.0 0 13,073 496(High) N/A
IAC-2 MDV-D28Q4/VN1-A3 27.0/19.0 0 9,016 0 6,111 20.0 0 10,487 408(High) N/A
IAC-3 MDV-D36Q4/VN1-A3 27.0/19.0 0 11,562 0 7,697 20.0 0 13,087 496(High) N/A
IAC-3 MDV-D36Q4/VN1-A3 27.0/19.0 0 11,616 0 7,733 20.0 0 13,149 496(High) N/A
IAC-2 MDV-D28Q4/VN1-A3 27.0/19.0 0 9,157 0 6,207 20.0 0 10,651 408(High) N/A
IAC-2 MDV-D28Q4/VN1-A3 27.0/19.0 0 9,212 0 6,244 20.0 0 10,747 408(High) N/A
IAC-2 MDV-D28Q4/VN1-A3 27.0/19.0 0 9,212 0 6,244 20.0 0 10,747 408(High) N/A
IAC-2 MDV-D28Q4/VN1-A3 27.0/19.0 0 9,080 0 6,154 20.0 0 10,561 408(High) N/A
IAC-2 MDV-D28Q4/VN1-A3 27.0/19.0 0 9,113 0 6,176 20.0 0 10,599 408(High) N/A
IAC-2 MDV-D28Q4/VN1-A3 27.0/19.0 0 9,125 0 6,185 20.0 0 10,613 408(High) N/A
IAC-2 MDV-D28Q4/VN1-A3 27.0/19.0 0 9,158 0 6,207 20.0 0 10,652 408(High) N/A
IAC-3 MDV-D36Q4/VN1-A3 27.0/19.0 0 11,795 0 7,852 20.0 0 13,352 496(High) N/A
IAC-3 MDV-D36Q4/VN1-A3 27.0/19.0 0 11,834 0 7,878 20.0 0 13,396 496(High) N/A
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

1.3 Outdoor Unit Specifications

Name Model Module Dimension(mm) Weight(kg) Base refr(kg) Add refr(kg) Power Supply MCA(A) MFA(A)
ODU1 MV5-X560W/V2GN1 MV5-X280W/V2GN1 990*1635*790 219.00 9.00 9.54 380-415-3-60 21.0 25
MV5-X280W/V2GN1 990*1635*790 219.00 9.00 380-415-3-60 21.0 25

Name Model CR% Temp(°C) CC(Btu/h) Req CC(Btu/h) Temp(H/RH)(°C) HC(Btu/h) Req HC(Btu/h)
ODU1 MV5-X560W/V2GN1 82.50 34.1 184,516 0 7.0/87% 211,947 0

Name Model EER COP Cooling Power(kW) Heating Power(kW)


ODU1 MV5-X560W/V2GN1 5.07 5.47 9.12 9.5
Req.TC: Required Total Cooling Capacity
Req.SC: Required Sensible Cooling Capacity
Req.HC: Required Total Heating Capacity
TC: Available Total Cooling Capacity
SC: Available Sensible Cooling Capacity
HC: Available Total Heating Capacity
AT: Ambient Temperature
ESP: External Static Pressure
Req.CC: Required Cooling Capacity
CC: Available Cooling Capacity
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

1.4 Piping and Mode Selection Devices

IDU Quantity 15/33


Combination Ratio 82.50%
Additional refrigerant charge 9.54 kg
= 51.48(6.35) * 0.022 + 56.99(9.53) * 0.057 +
2.00(12.7) * 0.110 + 19.00(19.1) * 0.260
Factory refrigerant charge 18.00 kg
Total refrigerant charge 27.54 kg
Total Pipe Length 126.97 m / 1000 m
Furthest Actual 42.15 m / 175 m
Furthest Equivalent 44.65 m / 200 m
Furthest Equivalent from First Branch to IDU 26.15 m / 40(90) m
Drop Height between IDU and IDU 0 m / 30 m
Drop height between IDU and ODU(Below 3 m / 90 m
ODU)
Available Capacity Cooling 152,205 Btu/h
Available Capacity Heating 174,928 Btu/h
Note:
1.The equivalent length of each branch joint is 0.5m.

Pipe
No. Length Gas Pipe Liquid Pipe
(1) 18.0 m Ø31.8 Ø19.1
(2) 1.6 m Ø22.2 Ø9.53
(3) 4.0 m Ø19.1 Ø9.53
(4) 7.1 m Ø19.1 Ø9.53
(5) 6.7 m Ø15.9 Ø9.53
(6) 1.1 m Ø15.9 Ø9.53
(7) 3.0 m Ø15.9 Ø9.53
(8) 3.2 m Ø15.9 Ø9.53
(9) 3.7 m Ø15.9 Ø9.53
(10) 3.2 m Ø19.1 Ø9.53
(11) 3.7 m Ø15.9 Ø9.53
(12) 6.0 m Ø15.9 Ø9.53
(13) 3.5 m Ø15.9 Ø9.53
(14) 3.7 m Ø15.9 Ø9.53
(15) 4.8 m Ø12.7 Ø6.35
(16) 3.2 m Ø12.7 Ø6.35
(17) 5.1 m Ø12.7 Ø6.35
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

No. Length Gas Pipe Liquid Pipe


(18) 3.2 m Ø12.7 Ø6.35
(19) 4.3 m Ø12.7 Ø6.35
(20) 1.6 m Ø12.7 Ø6.35
(21) 6.9 m Ø12.7 Ø6.35
(22) 3.3 m Ø12.7 Ø6.35
(23) 1.3 m Ø12.7 Ø6.35
(24) 4.0 m Ø12.7 Ø6.35
(25) 1.9 m Ø12.7 Ø6.35
(26) 3.6 m Ø12.7 Ø6.35
(27) 1.5 m Ø12.7 Ø6.35
(28) 4.3 m Ø12.7 Ø6.35
(29) 2.4 m Ø12.7 Ø6.35

Branch Joint
No. Load Btu/h Model
(1) 157,630 FQZHN-03D
(2) 94,851 FQZHN-02D
(3) 75,744 FQZHN-01D
(4) 66,191 FQZHN-01D
(5) 19,789 FQZHN-01D
(6) 46,402 FQZHN-01D
(7) 21,836 FQZHN-01D
(8) 24,566 FQZHN-01D
(9) 19,107 FQZHN-01D
(10) 62,779 FQZHN-01D
(11) 38,213 FQZHN-01D
(12) 19,107 FQZHN-01D
(13) 19,107 FQZHN-01D
(14) 24,566 FQZHN-01D
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

1.5 Piping Diagram


Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

VRF 60Hz R410A


ODU:184,516/211,947 Btu/h IDU Total:151,966/102,493/174,689 Btu/h

MV5-X560W/V2GN1

IAC-3
(2) (3) (4) (5)
(1) Ø15.9,Ø9.53 Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
Ø31.8,Ø19.1 Ø22.2,Ø9.53 Ø19.1,Ø9.53 Ø19.1,Ø9.53
(4)7.1 m,0 (5)6.7 m,0 (15)4.8 m,0 TC:11,514 Btu/h
(1)18.0 m,0 (2)1.6 m,0 (3)4.0 m,0 FQZHN-01D SC:7,665 Btu/h
FQZHN-03D FQZHN-02D FQZHN-01D FQZHN-01D
HC:13,033 Btu/h
IAC-1
Ø12.7,Ø6.35 MDV-D22Q4/VN1-A3
(16)3.2 m,0 TC:7,054 Btu/h
SC:5,124 Btu/h
HC:7,829 Btu/h
IAC-3
(6) (7)
Ø15.9,Ø9.53 Ø15.9,Ø9.53 Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(6)1.1 m,0 (7)3.0 m,0 (17)5.1 m,0 TC:11,549 Btu/h
FQZHN-01D FQZHN-01D SC:7,688 Btu/h
HC:13,073 Btu/h
IAC-2
Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(18)3.2 m,0 TC:9,016 Btu/h
SC:6,111 Btu/h
HC:10,487 Btu/h

IAC-3
(8)
Ø15.9,Ø9.53 Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(8)3.2 m,0 (19)4.3 m,0 TC:11,562 Btu/h
FQZHN-01D SC:7,697 Btu/h
HC:13,087 Btu/h
IAC-3
Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(20)1.6 m,0 TC:11,616 Btu/h
SC:7,733 Btu/h
HC:13,149 Btu/h
IAC-2
Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(21)6.9 m,0 TC:9,157 Btu/h
SC:6,207 Btu/h
HC:10,651 Btu/h
IAC-2
(9)
Ø15.9,Ø9.53 Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(9)3.7 m,0 (22)3.3 m,0 TC:9,212 Btu/h
FQZHN-01D SC:6,244 Btu/h
HC:10,747 Btu/h
IAC-2
Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(23)1.3 m,0 TC:9,212 Btu/h
SC:6,244 Btu/h
HC:10,747 Btu/h
IAC-2
(10) (11) (12)
Ø19.1,Ø9.53 Ø15.9,Ø9.53 Ø15.9,Ø9.53 Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(10)3.2 m,0 (11)3.7 m,0 (12)6.0 m,0 (24)4.0 m,0 TC:9,080 Btu/h
FQZHN-01D FQZHN-01D FQZHN-01D SC:6,154 Btu/h
HC:10,561 Btu/h
IAC-2
Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(25)1.9 m,0 TC:9,113 Btu/h
SC:6,176 Btu/h
HC:10,599 Btu/h

IAC-2
(13)
Ø15.9,Ø9.53 Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(13)3.5 m,0 (26)3.6 m,0 TC:9,125 Btu/h
FQZHN-01D SC:6,185 Btu/h
HC:10,613 Btu/h
IAC-2
Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(27)1.5 m,0 TC:9,158 Btu/h
SC:6,207 Btu/h
HC:10,652 Btu/h
IAC-3
(14)
Ø15.9,Ø9.53 Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(14)3.7 m,0 (28)4.3 m,0 TC:11,795 Btu/h
FQZHN-01D SC:7,852 Btu/h
HC:13,352 Btu/h
IAC-3
Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(29)2.4 m,0 TC:11,834 Btu/h
SC:7,878 Btu/h
HC:13,396 Btu/h

The piping size may be different with the actual situation because of the software's illustration limitation, please confirm the piping size according to the installation manual before installation.
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

1.6 Wiring Diagram


Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

L1,L2,L3 380-415-3-60
ODU1

3-core Cables PQE

IAC-3

PQE

IAC-1

PQE

IAC-3

PQE

IAC-2

PQE

IAC-3

PQE

IAC-3

PQE

IAC-2

PQE

IAC-2

PQE

IAC-2

PQE

IAC-2

PQE

IAC-2

PQE

IAC-2

PQE

IAC-2

PQE

IAC-3

PQE

IAC-3

The wiring diagram may be different with the actual situation because of software's illustration
limitation, please confirm the wiring diagram according to the installation manual before installation.
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

Segundo Piso

2.1 Material List

Model Quantity Description


MV5-X252W/V2GN1 1 All DC Inverter V5 X (380V)
MV5-X450W/V2GN1 1 All DC Inverter V5 X (380V)
MDV-D36Q4/VN1-A3 8 Compact Four-way Cassette
MDV-D56Q4/VN1-E 4 Four-way Cassette (E
series,silent type)
MDV-D22Q4/VN1-A3 5 Compact Four-way Cassette
MDV-D28Q4/VN1-A3 4 Compact Four-way Cassette
FQZHN-03D 5 Branch Joint
FQZHN-01D 14 Branch Joint
FQZHN-02D 1 Branch Joint
FQZHW-02N1D 1 Branch Joint
Ø31.8 32.8 m Copper Pipe
Ø25.4 15.2 m Copper Pipe
Ø22.2 10.5 m Copper Pipe
Ø19.1 53.8 m Copper Pipe
Ø15.9 20.3 m Copper Pipe
Ø12.7 116.3 m Copper Pipe
Ø9.53 7.6 m Copper Pipe
Ø6.35 56.9 m Copper Pipe
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

2.2 Indoor Unit Specifications

IDU Name Model Sound (dB(A)) Weight(kg) Dimension(mm) Power Supply Rated Power(W) MCA(A) MFA(A)
WxHxD
IAC-3(EAAC20) MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-3(EAAC22) MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-3(EAAC21) MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-3(EAAC23) MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-4(EAAC38) MDV-D56Q4/VN1-E 35(High) 23.70 840*230*840 208-230V-1ph-60Hz 88 0.40 15
IAC-4(EAAC37) MDV-D56Q4/VN1-E 35(High) 23.70 840*230*840 208-230V-1ph-60Hz 88 0.40 15
IAC-4(EAAC40) MDV-D56Q4/VN1-E 35(High) 23.70 840*230*840 208-230V-1ph-60Hz 88 0.40 15
IAC-4(EAAC39) MDV-D56Q4/VN1-E 35(High) 23.70 840*230*840 208-230V-1ph-60Hz 88 0.40 15
IAC-1(EAAC36) MDV-D22Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-1(EAAC33) MDV-D22Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-1(EAAC32) MDV-D22Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-1(EAAC35) MDV-D22Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-1(EAAC34) MDV-D22Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2(EAAC29) MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2(EAAC28) MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2(EAAC31) MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-2(EAAC30) MDV-D28Q4/VN1-A3 36(High) 16.00 570*260*570 208-230,60,1 50 0.175 15
IAC-3(EAAC26) MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

IDU Name Model Sound (dB(A)) Weight(kg) Dimension(mm) Power Supply Rated Power(W) MCA(A) MFA(A)
WxHxD
IAC-3(EAAC27) MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-3(EAAC24) MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15
IAC-3(EAAC25) MDV-D36Q4/VN1-A3 42(High) 18.00 570*260*570 208-230,60,1 60 0.210 15

IDU Name Model Cooling AT Req.TC TC Req.SC SC Heating AT Req.HC HC Air flow ESP
(°C) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (°C) (Btu/h) (Btu/h) (m^3/h) (Pa)
IAC-3(EAAC20) MDV-D36Q4/VN1-A3 27.0/19.0 0 11,120 0 7,402 20.0 0 12,973 496(High) N/A
IAC-3(EAAC22) MDV-D36Q4/VN1-A3 27.0/19.0 0 11,174 0 7,438 20.0 0 13,036 496(High) N/A
IAC-3(EAAC21) MDV-D36Q4/VN1-A3 27.0/19.0 0 11,174 0 7,438 20.0 0 13,036 496(High) N/A
IAC-3(EAAC23) MDV-D36Q4/VN1-A3 27.0/19.0 0 11,225 0 7,472 20.0 0 13,096 496(High) N/A
IAC-4(EAAC38) MDV-D56Q4/VN1-E 27.0/19.0 0 16,322 0 9,895 20.0 0 19,251 942(High) N/A
IAC-4(EAAC37) MDV-D56Q4/VN1-E 27.0/19.0 0 16,313 0 9,890 20.0 0 19,241 942(High) N/A
IAC-4(EAAC40) MDV-D56Q4/VN1-E 27.0/19.0 0 16,409 0 9,948 20.0 0 19,353 942(High) N/A
IAC-4(EAAC39) MDV-D56Q4/VN1-E 27.0/19.0 0 16,416 0 9,952 20.0 0 19,362 942(High) N/A
IAC-1(EAAC36) MDV-D22Q4/VN1-A3 27.0/19.0 0 6,481 0 4,707 20.0 0 7,424 397(High) N/A
IAC-1(EAAC33) MDV-D22Q4/VN1-A3 27.0/19.0 0 6,606 0 4,799 20.0 0 7,569 397(High) N/A
IAC-1(EAAC32) MDV-D22Q4/VN1-A3 27.0/19.0 0 6,630 0 4,816 20.0 0 7,596 397(High) N/A
IAC-1(EAAC35) MDV-D22Q4/VN1-A3 27.0/19.0 0 6,674 0 4,848 20.0 0 7,647 397(High) N/A
IAC-1(EAAC34) MDV-D22Q4/VN1-A3 27.0/19.0 0 6,675 0 4,849 20.0 0 7,648 397(High) N/A
IAC-2(EAAC29) MDV-D28Q4/VN1-A3 27.0/19.0 0 8,562 0 5,820 20.0 0 10,270 408(High) N/A
IAC-2(EAAC28) MDV-D28Q4/VN1-A3 27.0/19.0 0 8,567 0 5,823 20.0 0 10,276 408(High) N/A
IAC-2(EAAC31) MDV-D28Q4/VN1-A3 27.0/19.0 0 8,600 0 5,845 20.0 0 10,315 408(High) N/A
IAC-2(EAAC30) MDV-D28Q4/VN1-A3 27.0/19.0 0 8,624 0 5,862 20.0 0 10,345 408(High) N/A
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

IDU Name Model Cooling AT Req.TC TC Req.SC SC Heating AT Req.HC HC Air flow ESP
(°C) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (°C) (Btu/h) (Btu/h) (m^3/h) (Pa)
IAC-3(EAAC26) MDV-D36Q4/VN1-A3 27.0/19.0 0 11,156 0 7,426 20.0 0 13,016 496(High) N/A
IAC-3(EAAC27) MDV-D36Q4/VN1-A3 27.0/19.0 0 11,213 0 7,464 20.0 0 13,082 496(High) N/A
IAC-3(EAAC24) MDV-D36Q4/VN1-A3 27.0/19.0 0 11,169 0 7,435 20.0 0 13,031 496(High) N/A
IAC-3(EAAC25) MDV-D36Q4/VN1-A3 27.0/19.0 0 11,224 0 7,471 20.0 0 13,095 496(High) N/A
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

2.3 Outdoor Unit Specifications

Name Model Module Dimension(mm) Weight(kg) Base refr(kg) Add refr(kg) Power Supply MCA(A) MFA(A)
ODU2 MV5-X702W/V2GN1 MV5-X252W/V2GN1 990*1635*790 219.00 9.00 17.12 380-415-3-60 20.0 25
MV5-X450W/V2GN1 1340*1635*790 297.00 13.00 380-415-3-60 29.9 35

Name Model CR% Temp(°C) CC(Btu/h) Req CC(Btu/h) Temp(H/RH)(°C) HC(Btu/h) Req HC(Btu/h)
ODU2 MV5-X702W/V2GN1 104.86 34.1 229,519 0 7.0/87% 269,677 0

Name Model EER COP Cooling Power(kW) Heating Power(kW)


ODU2 MV5-X702W/V2GN1 4.43 4.86 16.04 16.62
Req.TC: Required Total Cooling Capacity
Req.SC: Required Sensible Cooling Capacity
Req.HC: Required Total Heating Capacity
TC: Available Total Cooling Capacity
SC: Available Sensible Cooling Capacity
HC: Available Total Heating Capacity
AT: Ambient Temperature
ESP: External Static Pressure
Req.CC: Required Cooling Capacity
CC: Available Cooling Capacity
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

2.4 Piping and Mode Selection Devices

IDU Quantity 21/39


Combination Ratio 104.86%
Additional refrigerant charge 17.12 kg
= 56.89(6.35) * 0.022 + 7.56(9.53) * 0.057 +
66.87(12.7) * 0.110 + 13.70(15.9) * 0.170 +
22.11(19.1) * 0.260
Factory refrigerant charge 22.00 kg
Total refrigerant charge 39.12 kg
Total Pipe Length 164.63 m / 1000 m
Furthest Actual 60.78 m / 175 m
Furthest Equivalent 65.28 m / 200 m
Furthest Equivalent from First Branch to IDU 49.98 m / 40(90) m
Drop Height between IDU and IDU 0 m / 30 m
Drop height between IDU and ODU(Below 3 m / 90 m
ODU)
Available Capacity Cooling 229,519 Btu/h
Available Capacity Heating 269,677 Btu/h
Note:
1.The equivalent length of each branch joint is 0.5m.

Pipe
No. Length Gas Pipe Liquid Pipe
(1) 14.8 m Ø31.8 Ø19.1
(2) 4.0 m Ø19.1 Ø12.7
(3) 5.3 m Ø19.1 Ø12.7
(4) 3.1 m Ø19.1 Ø12.7
(5) 2.8 m Ø31.8 Ø19.1
(6) 2.5 m Ø31.8 Ø19.1
(7) 5.0 m Ø31.8 Ø15.9
(8) 6.7 m Ø31.8 Ø15.9
(9) 14.2 m Ø25.4 Ø12.7
(10) 9.4 m Ø22.2 Ø12.7
(11) 1.1 m Ø22.2 Ø12.7
(12) 2.5 m Ø19.1 Ø12.7
(13) 3.3 m Ø19.1 Ø12.7
(14) 0.9 m Ø19.1 Ø12.7
(15) 2.6 m Ø19.1 Ø12.7
(16) 2.6 m Ø19.1 Ø12.7
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

No. Length Gas Pipe Liquid Pipe


(17) 1.3 m Ø19.1 Ø12.7
(18) 2.2 m Ø19.1 Ø12.7
(19) 2.7 m Ø19.1 Ø12.7
(20) 3.0 m Ø19.1 Ø12.7
(21) 5.2 m Ø12.7 Ø6.35
(22) 2.4 m Ø12.7 Ø6.35
(23) 4.6 m Ø12.7 Ø6.35
(24) 2.0 m Ø12.7 Ø6.35
(25) 1.4 m Ø15.9 Ø9.53
(26) 1.7 m Ø15.9 Ø9.53
(27) 1.6 m Ø15.9 Ø9.53
(28) 2.9 m Ø15.9 Ø9.53
(29) 8.7 m Ø12.7 Ø6.35
(30) 4.2 m Ø12.7 Ø6.35
(31) 2.1 m Ø12.7 Ø6.35
(32) 1.5 m Ø12.7 Ø6.35
(33) 2.9 m Ø12.7 Ø6.35
(34) 2.2 m Ø12.7 Ø6.35
(35) 1.8 m Ø12.7 Ø6.35
(36) 2.3 m Ø12.7 Ø6.35
(37) 2.5 m Ø12.7 Ø6.35
(38) 4.1 m Ø12.7 Ø6.35
(39) 1.1 m Ø12.7 Ø6.35
(40) 6.1 m Ø12.7 Ø6.35
(41) 3.2 m Ø12.7 Ø6.35

Branch Joint
No. Load Btu/h Model
(1) 250,433 FQZHN-03D
(2) 49,131 FQZHN-01D
(3) 24,566 FQZHN-01D
(4) 24,566 FQZHN-01D
(5) 201,302 FQZHN-03D
(6) 176,736 FQZHN-03D
(7) 152,171 FQZHN-03D
(8) 113,957 FQZHN-03D
(9) 83,933 FQZHN-02D
(10) 76,427 FQZHN-01D
(11) 57,320 FQZHN-01D
(12) 38,213 FQZHN-01D
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

No. Load Btu/h Model


(13) 30,025 FQZHN-01D
(14) 22,519 FQZHN-01D
(15) 15,012 FQZHN-01D
(16) 38,213 FQZHN-01D
(17) 28,660 FQZHN-01D
(18) 19,107 FQZHN-01D
(19) 24,566 FQZHN-01D
(20) 24,566 FQZHN-01D
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

2.5 Piping Diagram


Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

VRF 60Hz R410A


ODU:229,519/269,677 Btu/h IDU Total:229,041/150,874/269,370 Btu/h

MV5-X702W/V2GN1

IAC-3(EAAC20)
(1) (2) (3)
Ø31.8,Ø19.1 Ø19.1,Ø12.7 Ø19.1,Ø12.7 Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(1)14.8 m,0 (2)4.0 m,0 (3)5.3 m,0 (21)5.2 m,0 TC:11,120 Btu/h
FQZHN-03D FQZHN-01D FQZHN-01D SC:7,402 Btu/h
HC:12,973 Btu/h
IAC-3(EAAC22)
Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(22)2.4 m,0 TC:11,174 Btu/h
SC:7,438 Btu/h
HC:13,036 Btu/h

IAC-3(EAAC21)
(4)
Ø19.1,Ø12.7 Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(4)3.1 m,0 (23)4.6 m,0 TC:11,174 Btu/h
FQZHN-01D SC:7,438 Btu/h
HC:13,036 Btu/h
IAC-3(EAAC23)
Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(24)2.0 m,0 TC:11,225 Btu/h
SC:7,472 Btu/h
HC:13,096 Btu/h IAC-4(EAAC38)
(10) (11) (12)
(6) (7) (8) (9) Ø15.9,Ø9.53 MDV-D56Q4/VN1-E
(5) Ø25.4,Ø12.7 Ø22.2,Ø12.7 Ø22.2,Ø12.7 Ø19.1,Ø12.7
Ø31.8,Ø19.1 Ø31.8,Ø19.1 Ø31.8,Ø15.9 Ø31.8,Ø15.9 (25)1.4 m,0 TC:16,322 Btu/h
(9)14.2 m,0 (10)9.4 m,0 (11)1.1 m,0 (12)2.5 m,0
(5)2.8 m,0 (6)2.5 m,0 (7)5.0 m,0 (8)6.7 m,0 FQZHN-01D FQZHN-01D SC:9,895 Btu/h
FQZHN-03D FQZHN-02D FQZHN-01D
FQZHN-03D FQZHN-03D FQZHN-03D HC:19,251 Btu/h
IAC-4(EAAC37)
Ø15.9,Ø9.53 MDV-D56Q4/VN1-E
(26)1.7 m,0 TC:16,313 Btu/h
SC:9,890 Btu/h
HC:19,241 Btu/h

IAC-4(EAAC40)
Ø15.9,Ø9.53 MDV-D56Q4/VN1-E
(27)1.6 m,0 TC:16,409 Btu/h
SC:9,948 Btu/h
HC:19,353 Btu/h
IAC-4(EAAC39)
Ø15.9,Ø9.53 MDV-D56Q4/VN1-E
(28)2.9 m,0 TC:16,416 Btu/h
SC:9,952 Btu/h
HC:19,362 Btu/h
IAC-1(EAAC36)
Ø12.7,Ø6.35 MDV-D22Q4/VN1-A3
(29)8.7 m,0 TC:6,481 Btu/h
SC:4,707 Btu/h
HC:7,424 Btu/h
IAC-1(EAAC33)
(13) (14) (15)
Ø19.1,Ø12.7 Ø19.1,Ø12.7 Ø19.1,Ø12.7 Ø12.7,Ø6.35 MDV-D22Q4/VN1-A3
(13)3.3 m,0 (14)0.9 m,0 (15)2.6 m,0 (30)4.2 m,0 TC:6,606 Btu/h
FQZHN-01D FQZHN-01D FQZHN-01D SC:4,799 Btu/h
HC:7,569 Btu/h
IAC-1(EAAC32)
Ø12.7,Ø6.35 MDV-D22Q4/VN1-A3
(31)2.1 m,0 TC:6,630 Btu/h
SC:4,816 Btu/h
HC:7,596 Btu/h

IAC-1(EAAC35)
Ø12.7,Ø6.35 MDV-D22Q4/VN1-A3
(32)1.5 m,0 TC:6,674 Btu/h
SC:4,848 Btu/h
HC:7,647 Btu/h
IAC-1(EAAC34)
Ø12.7,Ø6.35 MDV-D22Q4/VN1-A3
(33)2.9 m,0 TC:6,675 Btu/h
SC:4,849 Btu/h
HC:7,648 Btu/h IAC-2(EAAC29)
(16) (17) (18)
Ø19.1,Ø12.7 Ø19.1,Ø12.7 Ø19.1,Ø12.7 Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(16)2.6 m,0 (17)1.3 m,0 (18)2.2 m,0 (34)2.2 m,0 TC:8,562 Btu/h
FQZHN-01D FQZHN-01D FQZHN-01D SC:5,820 Btu/h
HC:10,270 Btu/h
IAC-2(EAAC28)
Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(35)1.8 m,0 TC:8,567 Btu/h
SC:5,823 Btu/h
HC:10,276 Btu/h

IAC-2(EAAC31)
Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(36)2.3 m,0 TC:8,600 Btu/h
SC:5,845 Btu/h
HC:10,315 Btu/h
IAC-2(EAAC30)
Ø12.7,Ø6.35 MDV-D28Q4/VN1-A3
(37)2.5 m,0 TC:8,624 Btu/h
SC:5,862 Btu/h
IAC-3(EAAC26) HC:10,345 Btu/h
(19)
Ø19.1,Ø12.7 Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(19)2.7 m,0 (38)4.1 m,0 TC:11,156 Btu/h
FQZHN-01D SC:7,426 Btu/h
HC:13,016 Btu/h
IAC-3(EAAC27)
Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(39)1.1 m,0 TC:11,213 Btu/h
SC:7,464 Btu/h
HC:13,082 Btu/h
IAC-3(EAAC24)
(20)
Ø19.1,Ø12.7 Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(20)3.0 m,0 (40)6.1 m,0 TC:11,169 Btu/h
FQZHN-01D SC:7,435 Btu/h
HC:13,031 Btu/h
IAC-3(EAAC25)
Ø12.7,Ø6.35 MDV-D36Q4/VN1-A3
(41)3.2 m,0 TC:11,224 Btu/h
SC:7,471 Btu/h
HC:13,095 Btu/h

The piping size may be different with the actual situation because of the software's illustration limitation, please confirm the piping size according to the installation manual before installation.
Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

2.6 Wiring Diagram


Project Name DATA CENTER CLARO
Peru ,lima
Date 2020 / 5 / 23

L1,L2,L3 380-415-3-60
ODU2

3-core Cables PQE

IAC-3(EAAC20)

PQE

IAC-3(EAAC22)

PQE

IAC-3(EAAC21)

PQE

IAC-3(EAAC23)

PQE

IAC-4(EAAC38)

PQE

IAC-4(EAAC37)

PQE

IAC-4(EAAC40)

PQE

IAC-4(EAAC39)

PQE

IAC-1(EAAC36)

PQE

IAC-1(EAAC33)

PQE

IAC-1(EAAC32)

PQE

IAC-1(EAAC35)

PQE

IAC-1(EAAC34)

PQE

IAC-2(EAAC29)

PQE

IAC-2(EAAC28)

PQE

IAC-2(EAAC31)

PQE

IAC-2(EAAC30)

PQE

IAC-3(EAAC26)

PQE

IAC-3(EAAC27)

PQE

IAC-3(EAAC24)

PQE

IAC-3(EAAC25)

The wiring diagram may be different with the actual situation because of software's illustration
limitation, please confirm the wiring diagram according to the installation manual before installation.

You might also like