OUTDOOR UNITS

R2–SERIES

The only two–pipe heat recovery system that simultaneously cools and heats.

The R2-Series simultaneously cools and heats different zones within a building to provide
energy-saving heat-recovery operation through the use of the Branch Circuit (BC) Controller.

KEY FEATURES: L-GENERATION


• Up to 54% increase in efficiency ratings.
• Single modules up to 14 tons with the ability to combine modules for systems up
to 28 tons.
• HexiCoil™ aluminium flat tube heat exchanger technology, eliminating copper
tubing from the coil.
• Up to 50% less refrigerant charge required than previous generations.
• Supports up to 50 indoor units per system.
• Optimized refrigerant circuit and component design for improved flow
distribution, allowing maximum energy transfer with minimal power input.
• Superior high-ambient cooling performance with guaranteed operation
to 126°F.
• Extended 10-year parts and compressor warranty available.

HEXICOIL™ CONDENSER COIL TECHNOLOGY


• Turbulated tube walls and optimized cross section ensure maximum heat transfer.
• Zinc coated for long-term corrosion resistance.
• Unique fin shape and coating provide water shedding capability.
• Capillary tube system leading to even fluid distribution.

Refrigerant Piping Lengths (Maximum Feet)

Total Length¹ 1,761-3,073

Farthest Indoor from Outdoor 541 (623 equivalent)

Maximum Length between Outdoor and Single/Main BC Controller 360

Maximum Length between Single/Main BC Controller & Indoor 131-197

Vertical Separation Between Components (Maximum Feet)

Indoor/Outdoor (Outdoor Higher)3 164


4
Indoor/Outdoor (Outdoor Lower) 131

Indoor/BC Controller (Single/Main)² 49

Indoor/Indoor 98

Main Controller/Sub BC Controller 49

1. Maximum Total Length is dependent on the outdoor unit model and distance between BC Controller.
2. Maximum length between single/main BC Controller and indoor is dependent upon the vertical differential between the single/main
BC Controller and the indoor unit.
3. 295’ is available depending on model and installation conditions. For more detailed information, contact your local distributor.
4. 197’ is available depending on model and installation conditions. For more detailed information, contact your local distributor.