FTKM-PVMK, RKM-PVMK Service Manual
FTKM-PVMK, RKM-PVMK Service Manual
Service
Manual
Inverter Pair
Wall Mounted Type
FTK(X)M-P Series
[Applied Models]
z Inverter Pair : Heat Pump
SiMT041509E
Inverter Pair
Wall Mounted Type
FTK(X)M-P Series
zCooling Only
Indoor Unit
FTKM18PVMK
FTKM24PVMK
FTKM28PVMK
Outdoor Unit
RKM18PVMK
RKM24PVMK
RKM28PVMK
zHeat Pump
Indoor Unit
FTXM18PVMK
FTXM24PVMK
FTXM28PVMK
Outdoor Unit
RXM18PVMK
RXM24PVMK
RXM28PVMK
i Table of Contents
SiMT041509E
1. Safety Cautions.......................................................................................v
1.1 Warnings and Cautions Regarding Safety of Workers.............................v
1.2 Warnings and Cautions Regarding Safety of Users................................ xi
2. Used Icons ........................................................................................... xiv
Table of Contents ii
SiMT041509E
Part 8 Appendix........................................................................... 96
1. Piping Diagrams....................................................................................97
1.1 Indoor Unit..............................................................................................97
1.2 Outdoor Unit ...........................................................................................98
2. Wiring Diagrams..................................................................................101
2.1 Indoor Unit............................................................................................101
2.2 Outdoor Unit .........................................................................................102
Table of Contents iv
Safety Cautions SiMT041509E
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
Caution Items The caution items are classified into Warning and Caution. The Warning items are
especially important since they can lead to death or serious injury if they are not followed
closely. The Caution items can also lead to serious accidents under some conditions if they
are not followed. Therefore, be sure to observe all the safety caution items described below.
Pictograms This symbol indicates the item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates the prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates the action that must be taken, or the instruction.
The instruction is shown in the illustration or near the symbol.
Be sure to disconnect the power cable plug from the plug socket before
disassembling the equipment for repair.
Working on the equipment that is connected to the power supply may cause an
electrical shock.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If the refrigerant gas is discharged during the repair work, do not touch
the discharged refrigerant gas.
The refrigerant gas may cause frostbite.
If the refrigerant gas leaks during the repair work, ventilate the area.
The refrigerant gas may generate toxic gases when it contacts flames.
v
SiMT041509E Safety Cautions
Warning
Do not start or stop the air conditioner operation by plugging or
unplugging the power cable plug.
Plugging or unplugging the power cable plug to operate the equipment may
cause an electrical shock or fire.
Be sure to wear a safety helmet, gloves, and a safety belt when working
at a high place (more than 2 m).
Insufficient safety measures may cause a fall accident.
Do not mix air or gas other than the specified refrigerant (R-32 / R-410A /
R-22) in the refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable when
cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Be sure to check that the refrigerating cycle section has cooled down
enough before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
vi
Safety Cautions SiMT041509E
Caution
Use the welder in a well-ventilated place.
Using the welder in an enclosed room may cause oxygen deficiency.
Work procedure
Work shall be conducted under a controlled procedure so as to minimise the risk of working in
the presence of R-32 or vapour.
No ignition sources
During work on a refrigeration system which involves exposing any piping work that contains or
has contained R-32, any sources of ignition shall not be used in a manner that may lead to the
risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be
kept at a safe distance from the site of installation, repairing, or removing space. Before starting
work, the area around the equipment shall be examined to make sure that there are no
flammable hazard or ignition risks. No Smoking signs shall be displayed.
Ventilated area
Ensure that the working area is open or that it is adequately ventilated before work.
Adequate ventilation shall be maintained during the entire period of work.
The ventilation should disperse any released refrigerant and preferably discharge it into the
external atmosphere.
vii
SiMT041509E Safety Cautions
Wiring
Check that wiring is not subject to wear, corrosion, excessive pressure, vibration, sharp edges
or any other adverse environmental effects. The check shall also take into account the effects of
ageing or continuous vibration from sources such as compressors or fans.
viii
Safety Cautions SiMT041509E
Detecting of R-32
Under no circumstances shall potential sources of ignition be used in the search for or detection
of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode
the copper piping work.
If a leak is suspected, all naked flames shall be removed or extinguished.
If a refrigerant leakage which requires brazing is found, all of the refrigerant shall be recovered
from the system, or isolated (by means of shut off valves) in a part of the system remote from
the point of the leakage. Oxygen free nitrogen (OFN) shall then be purged through the system
both before and during the brazing process.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and that there is
ventilation available.
Charging procedures
In addition to conventional charging procedures, the following requirements shall be met.
Ensure that the charging equipment to be used is not contaminated by different refrigerants.
Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in
them.
• Cylinders shall be kept upright.
• Ensure that the refrigeration system is earthed before charging the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the refrigeration system.
Before recharging, the system shall be tested for leakage with OFN. On completion of charging,
the system shall be tested before commissioning. Follow up leakage test shall be carried out
before leaving the site.
ix
SiMT041509E Safety Cautions
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with
the equipment and all its details. It is recommended to train technicians so that all of the
refrigerant is recovered safely. In case analysis is required before re-using the reclaimed
refrigerant, an oil and refrigerant sample shall be taken before proceeding with
decommissioning. It is essential that electrical power is available before work.
a) Comprehend the equipment and its operation.
b) Isolate the system electrically.
c) Before starting work, ensure that:
• mechanical handling equipment is available if required, for handling refrigerant cylinders;
• protective equipment can be used in compliance with specifications;
• the recovery process is supervised by a competent person at all times;
• recovery equipment and cylinders conform to the appropriate standards.
d) Pump down the refrigerant system, if possible.
e) If vacuum can not be ensured, apply a manifold so that refrigerant can be removed from
various parts of the system.
f) Make sure that the cylinder is situated on the scale before recovery takes place.
g) Start the refrigerant recovery device and operate it in accordance with the manufacturer's
instructions.
h) Do not overfill cylinders. (Do not exceed 80% liquid charge volume).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process is completed, make sure
that the cylinders and the equipment are removed from site promptly and all valves on the
equipment are closed.
k) Recovered refrigerant shall not be charged into another refrigeration system before it has
been cleaned and checked.
Labelling
Equipment shall be labelled stating that it has been decommissioned and emptied of refrigerant.
The label shall be dated and signed. Ensure that there are labels on the equipment stating the
equipment contains R-32.
Refrigerant recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended to conduct training so that all refrigerants can be removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are used.
Ensure that the correct number of cylinders for holding the total system charge are available. All
cylinders to be used must be designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be equipped
with a pressure relief valve and associated shut-off valves in good working order. If possible,
empty recovery cylinders shall be cooled in a separate place before recovery is conducted.
The recovery equipment shall be in good working order with instructions concerning the
equipment at hand, and shall be suitable for the recovery of R-32. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be equipped with
leak-free disconnect couplings and in good condition. Before using the recovery device, check
that it has undergone proper maintenance, that it is in satisfactory working order, and that any
associated electrical components are sealed to prevent ignition in the event of a refrigerant
leakage. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, with the relevant Waste Transfer Note attached. Do not mix refrigerants in recovery
units and especially not in cylinders.
If compressors or compressor oil are to be removed, ensure that the refrigerant melted into the
oil has been evacuated to an acceptable level to make certain that R-32 does not remain within
the oil. The evacuation process shall be carried out before returning the compressor to the
supplier. Only electric heating to the compressor body shall be employed to accelerate this
process. Oil drained from the system shall be treated safely.
x
Safety Cautions SiMT041509E
Be sure to use parts listed in the service parts list of the applicable model
and appropriate tools to conduct repair work. Never attempt to modify the
equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires have scratches or deteriorated, be sure
to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same
power outlet with other electrical appliances, since it may cause an
electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and follow
the local technical standards related to the electrical equipment, the
internal wiring regulations, and the instruction manual for installation
when conducting electrical work.
Insufficient power circuit capacity and improper electrical work may cause an
electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and
outdoor units.
Make the connections securely and route the cable properly so that there is no
force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that the
terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may cause
an electrical shock, excessive heat generation or fire.
Do not mix air or gas other than the specified refrigerant (R-32 / R-410A /
R-22) in the refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and repair
it before charging the refrigerant. After charging refrigerant, make sure
that there is no refrigerant leak.
If the leaking point cannot be located and the repair work must be stopped, be
sure to perform pump-down and close the service valve, to prevent the
refrigerant gas from leaking into the room. The refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such as fan
and other heaters, stoves and ranges.
xi
SiMT041509E Safety Cautions
Warning
When relocating the equipment, make sure that the new installation site
has sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation
work is not conducted securely, the equipment may fall and cause injury.
Check to make sure that the power cable plug is not dirty or loose, then
insert the plug into a power outlet securely.
If the plug has dust or loose connection, it may cause an electrical shock or fire.
Be sure to install the product correctly by using the provided standard For unitary type
installation frame. only
Incorrect use of the installation frame and improper installation may cause the
equipment to fall, resulting in injury.
Be sure to install the product securely in the installation frame mounted For unitary type
on the window frame. only
If the unit is not securely mounted, it may fall and cause injury.
Caution
Installation of a leakage breaker is necessary in some cases depending
on the conditions of the installation site, to prevent electrical shocks.
Check to see if the parts and wires are mounted and connected properly,
and if the connections at the soldered or crimped terminals are secure.
Improper installation and connections may cause excessive heat generation,
fire or an electrical shock.
xii
Safety Cautions SiMT041509E
Caution
Check the earth / grounding, and repair it if the equipment is not properly
earthed / grounded.
Improper earth / grounding may cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make
sure that the resistance is 1 MΩ or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause the water to enter the room and wet the furniture
and floor.
Be sure to install the packing and seal on the installation frame properly. For unitary type
If the packing and seal are not installed properly, water may enter the room and only
wet the furniture and floor.
xiii
SiMT041509E Used Icons
2. Used Icons
The following icons are used to attract the attention of the reader to specific information.
Warning
Caution A Caution is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, lose data, get
Caution an unexpected result or has to restart (part of) a procedure.
xiv
SiMT041509E
Part 1
List of Functions
1. Functions.................................................................................................2
1 List of Functions
SiMT041509E Functions
1. Functions
FTKM18/24/28PVMK
FTXM18/24/28PVMK
FTKM18/24/28PVMK
FTXM18/24/28PVMK
RKM18/24/28PVMK
RXM18/24/28PVMK
RKM18/24/28PVMK
RXM18/24/28PVMK
Category Functions Category Functions
Basic Inverter (with inverter power control) z z Health & Air-purifying filter — —
Function Clean
Operation limit for cooling (°CDB) 10 ~ 10 ~ Photocatalytic deodorizing filter — —
52 52
0~ Air-purifying filter with photocatalytic
Operation limit for heating (°CWB) — 18 deodorizing function — —
List of Functions 2
SiMT041509E
Part 2
Specifications
1. Specifications ..........................................................................................4
3 Specifications
SiMT041509E Specifications
1. Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTKM18PVMK FTKM24PVMK
Model
Outdoor Unit RKM18PVMK RKM24PVMK
kW 5.28 (1.7 ~ 6.0) 7.03 (1.9 ~ 8.6)
Capacity Btu/h 18,000 (5,700 ~ 20,500) 24,000 (6,500 ~ 29,500)
Rated (Min. ~ Max.)
kcal/h 4,540 (1,440 ~ 5,170) 6,050 (1,640 ~ 7,430)
Moisture Removal L/h 2.9 4.5
Running Current (Rated) A 6.4 - 6.1 - 5.8 / 6.4 - 6.1 8.8 - 8.4 - 8.1 / 8.8 - 8.4
Power Consumption W 1,350 (300 ~ 1,700) 1,890 (350 ~ 2,600)
Rated (Min. ~ Max.)
Power Factor (Rated) % 95.9 - 96.2 - 97.0 / 95.9 - 96.2 97.6 - 97.8 - 97.2 / 97.6 - 97.8
COP W/W 3.91 (5.57 ~ 3.54) 3.72 (5.46 ~ 3.32)
Rated (Min. ~ Max.)
Liquid mm φ 6.4 φ 6.4
Piping φ 12.7 φ 12.7
Connections Gas mm
Drain mm — —
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 30 30
Max. Interunit Height Difference m 20 20
Chargeless m 10 10
Amount of Additional Charge of g/m 20 20
Refrigerant
Indoor Unit FTKM18PVMK FTKM24PVMK
Front Panel Color (Mancel No.) White (N95) White (N95)
H 20.5 (724) 22.0 (777)
M m³/min 16.5 (583) 17.7 (625)
Airflow Rate (cfm)
L 12.6 (445) 13.7 (484)
SL 10.9 (385) 12.2 (431)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 48 48
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward
Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof
Running Current (Rated) A 0.45 - 0.43 - 0.41 / 0.45 - 0.43 0.70- 0.67 - 0.64 / 0.70 - 0.67
Power Consumption (Rated) W 59 85
Power Factor (Rated) % 59.6 - 59.7 - 60.0 / 59.6 - 59.7 55.2 - 55.2 - 55.3 / 55.2 - 55.2
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 340 × 1,050 × 259 340 × 1,050 × 259
Packaged Dimensions (H × W × D) mm 342 × 1,160 × 429 342 × 1,160 × 429
Weight (Mass) kg 15 15
Gross Weight (Gross Mass) kg 21 21
Sound
Pressure H / M / L / SL dB(A) 48 / 42 / 35 / 32 51 / 45 / 37 / 34
Level
Outdoor Unit RKM18PVMK RKM24PVMK
Casing Color Ivory White Ivory White
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 2YC40BXD 2YC40BXD
Motor Output W 1,300 1,300
Refrigerant Type FW68DA FW68DA
Oil Charge L 0.650 0.650
Type R-32 R-32
Refrigerant
Charge kg 1.12 1.40
H m³/min 76.9 (2,715) 74.2 (2,620)
Airflow Rate (cfm)
SL 62.0 (2,189) 61.4 (2,168)
Type Propeller Propeller
Fan
Motor Output W 128 128
Running Current (Rated) A 6.1 - 5.8 - 5.5 / 6.1 - 5.8 8.4 - 8.0 - 7.7 / 8.4 - 8.0
Power Consumption (Rated) W 1,291 1,805
Power Factor (Rated) % 96.2 - 96.8 - 97.8 / 96.2 - 96.8 97.7 - 98.1 - 97.7 / 97.7 - 98.1
Starting Current A 6.4 8.8
Dimensions (H × W × D) mm 695 × 930 × 350 695 × 930 × 350
Packaged Dimensions (H × W × D) mm 762 × 1,004 × 475 762 × 1,004 × 475
Weight (Mass) kg 46 49
Gross Weight (Gross Mass) kg 52 56
Sound
Pressure H dB(A) 51 56
Level
Drawing No. 3D093404 3D093405
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Piping Length
kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB 7.5 m Btu/h = kW × 3412
Outdoor ; 35°CDB / 24°CWB cfm = m³/min × 35.3
Specifications 4
Specifications SiMT041509E
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Piping Length
kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB 7.5 m Btu/h = kW × 3412
Outdoor ; 35°CDB / 24°CWB cfm = m³/min × 35.3
5 Specifications
SiMT041509E Specifications
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Heating Piping Length
kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB 7.5 m Btu/h = kW × 3412
Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB cfm = m³/min × 35.3
Specifications 6
Specifications SiMT041509E
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Heating Piping Length
kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB 7.5 m Btu/h = kW × 3412
Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB cfm = m³/min × 35.3
7 Specifications
SiMT041509E
Part 3
Printed Circuit Board
Connector Wiring Diagram
1. Indoor Unit...............................................................................................9
2. Outdoor Unit..........................................................................................11
1. Indoor Unit
Control PCB
(PCB1) 1) S1 Connector for DC fan motor
2) S21 Connector for centralized control (HA)
3) S25 Connector for INTELLIGENT EYE sensor PCB
4) S32 Indoor heat exchanger thermistor
5) S41 Connector for swing motors
6) S46 Connector for display PCB
7) S47 Connector for signal receiver PCB
8) H1, H2, H3, FG Connector for terminal board
9) JA Address setting jumper
∗ Refer to page 94 for detail.
10)JB Fan speed setting when compressor stops for thermostat OFF
∗ Refer to page 94 for detail.
11)JC Power failure recovery function (auto-restart)
∗ Refer to page 94 for detail.
12)LED A LED for service monitor (green)
13)FU1 (F1U), Fuse (3.15 A, 250 V)
FU2 (F2U)
14)V1 Varistor
S41 S1
S32
H3 FG H2 H1
LED A FU2 FU1
S46
S25 V1
S21
S47 JA
JC JB
2P227881-10
2P227881-11
Note: The symbols in the parenthesis are the names on the appropriate wiring diagram.
Signal Receiver
PCB (PCB2) 1) S48 Connector for control PCB
S48
3P224121-1
Display PCB
(PCB3) 1) S49 Connector for control PCB
2) SW1 Forced cooling operation ON/OFF button
∗ Refer to page 92 for detail.
3) LED1 (H1P) LED for operation (green)
4) LED2 (H2P) LED for timer (yellow)
5) LED3 (H3P) LED for INTELLIGENT EYE (green)
6) RTH1 (R1T) Room temperature thermistor
RTH1 SW1
S49
3P224121-1
INTELLIGENT
EYE Sensor PCB 1) S36 Connector for control PCB
(PCB4)
S36
3P227885-1
Note: The symbols in the parenthesis are the names on the appropriate wiring diagram.
2. Outdoor Unit
Main PCB
1) S20 Connector for electronic expansion valve coil
2) S40 Connector for overload protector and high pressure switch
3) S70 Connector for DC fan motor
4) S80 Connector for four way valve coil
5) S90 Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
6) S92 Jumpers for local setting
∗ Neither disconnect the connector nor cut any of the jumpers.
7) S100 Connector for fan motor (for cooling electrical box)
8) HL1, HN1, S Connector for terminal board
9) E1, E2 Terminal for earth wire
10) U, V, W Connector for compressor
11) FU1, FU2 Fuse (3.15 A, 250 V)
12) FU3 Fuse (30 A, 250 V)
13) LED A LED for service monitor (green)
14) V2, V3, V401 Varistor
E2 E1
V401 FU1 V2 V3 HN1
HL1
FU3
S40
S20
S92
Part 4
Function and Control
1. Main Functions......................................................................................13
1.1 Temperature Control ..............................................................................13
1.2 Frequency Principle................................................................................13
1.3 Airflow Direction Control.........................................................................15
1.4 Fan Speed Control for Indoor Unit .........................................................16
1.5 Program Dry Operation ..........................................................................17
1.6 Automatic Operation...............................................................................18
1.7 Thermostat Control.................................................................................19
1.8 NIGHT SET Mode ..................................................................................20
1.9 ECONO Operation .................................................................................20
1.10 INTELLIGENT EYE Operation ...............................................................21
1.11 Inverter POWERFUL Operation .............................................................22
1.12 Clock Setting ..........................................................................................23
1.13 WEEKLY TIMER Operation ...................................................................24
1.14 Other Functions......................................................................................30
2. Function of Thermistor ..........................................................................31
3. Control Specification .............................................................................32
3.1 Mode Hierarchy ......................................................................................32
3.2 Frequency Control..................................................................................33
3.3 Controls at Mode Changing / Start-up....................................................35
3.4 Discharge Pipe Temperature Control.....................................................36
3.5 Input Current Control..............................................................................37
3.6 Freeze-up Protection Control .................................................................38
3.7 Heating Peak-cut Control .......................................................................38
3.8 Outdoor Fan Control...............................................................................39
3.9 Liquid Compression Protection Function................................................39
3.10 Defrost Control .......................................................................................40
3.11 Electronic Expansion Valve Control .......................................................41
3.12 Discharge Pipe Thermistor Disconnection Control.................................43
3.13 Malfunctions ...........................................................................................43
1. Main Functions
1.1 Temperature Control
Definitions of The definitions of temperatures are classified as following.
Temperatures
Room temperature: temperature of lower part of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
Target temperature
Set temperature
Room temperature
(R12321)
Temperature The temperature of the room is detected by the room temperature thermistor. However, there is
Control a difference between the temperature detected by room temperature thermistor and the
temperature of lower part of the room, depending on the type of the indoor unit or installation
condition. Practically, the temperature control is done by the target temperature appropriately
adjusted for the indoor unit and the temperature detected by room temperature thermistor.
Inverter Principle To regulate the capacity, a frequency control is needed. The inverter makes it possible to
control the rotation speed of the compressor. The following table explains the inverter principle:
Phase Description
1 The supplied AC power source is converted into the DC power source for the present.
2 The DC power source is reconverted into the three phase AC power source with variable
frequency.
When the frequency increases, the rotation speed of the compressor increases resulting
in an increase of refrigerant circulation. This leads to a larger amount of heat exchange
per unit.
When the frequency decreases, the rotation speed of the compressor decreases
resulting in a decrease of refrigerant circulation. This leads to a smaller amount of heat
exchange per unit.
high speed
Amount of heat Amount of heat
exchanged air (large) high f exchanged air (large)
power
power
DC
AC
Amount of heat low f Amount of heat
exchanged air (small) exchanged air (small)
low speed
freq= 50 Hz capacity=
constant 60 Hz freq=variable variable
Frequency Limits The following functions regulate the minimum and maximum frequency:
Frequency Functions
Low Four way valve operation compensation. Refer to page 35.
High Compressor protection function. Refer to page 36.
Discharge pipe temperature control. Refer to page 36.
Input current control. Refer to page 37.
Freeze-up protection control. Refer to page 38.
Heating peak-cut control. Refer to page 38.
Defrost control. Refer to page 40.
<Cooling / Dry>
During cooling or dry operation, the flap retracts into the indoor unit. Then, cool air can be blown
far and distributed all over the room.
<Heating>
During heating operation, the large flap directs airflow downward to spread the warm air to the
entire room.
Wide-Angle The louvers, made of elastic synthetic resin, provide a wide range of airflow that guarantees
Louvers comfortable air distribution.
Auto-Swing The following table explains the auto-swing process for cooling, dry, heating, and fan:
Flap (up and down) Louver
Cooling / Dry Heating Fan (right and left)
15° 15°
30°
25° 25° 75° °
50° 60° 40° 75° 45 °
45
70° 70°
(R9303) (R9304) (R9305) (R9306)
3-D Airflow Alternative repetition of vertical and horizontal swing motions enables uniform air-conditioning of
the entire room.
When the horizontal swing and vertical swing are both set to automatic operation, the airflow
becomes 3-D airflow. The horizontal and vertical swing motions are alternated and the airflow
direction changes in the order shown in the following diagram.
(2)
(4)
(3)
(R13554)
COMFORT The flaps are controlled not to blow the air directly at the people in the room.
AIRFLOW Cooling Heating
Operation
10°
20°
75° 80°
(R22374) (R9654)
Automatic Fan In automatic fan speed operation, the step SL is not available.
Speed Control Step Cooling Heating
LLL
LL
L
ML
M
MH
H
HH (POWERFUL) (R11681) (R6834)
= The airflow rate is automatically controlled within this range when the FAN setting
button is set to automatic.
<Cooling>
The following drawing explains the principle of fan speed control for cooling.
Room thermistor temperature – target temperature
Fan speed MH*
+3°C
+2.5°C M
+2°C
+1.5°C ML
+1°C
+0.5°C L
(R14588)
*The upper limit is M tap for 30 minutes from the operation start.
<Heating>
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
COMFORT The fan speed is controlled automatically within the following steps.
AIRFLOW <Cooling>
Operation L tap ~ MH tap (same as automatic)
<Heating>
L ~ M tap
The latest command has the priority between POWERFUL and COMFORT AIRFLOW.
Detail The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in an appropriate capacity for each zone to maintain the
temperature and humidity at a comfortable level.
Room thermistor Target temperature Thermostat OFF point Thermostat ON point
temperature at start-up X Y Z
Thermostat turns on also when the room temperature is in the zone B for 10 minutes.
Zone C = Thermostat ON Z
Zone B
Zone B
Y
+0.5ºC
Zone A = Thermostat OFF
(R11581)
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry: 10 minutes, Heating: 10 seconds)
<Cooling / Dry>
<Heating>
Zone A
2.0˚C
Zone B
1.5˚C
Zone C
0.5˚C
ON (R22129)
Detail NIGHT SET Mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in the case of cooling, or lowers it slightly in
the case of heating. This prevents excessive cooling in summer and excessive heating in winter
to ensure comfortable sleeping conditions, and also conserves electricity.
<Cooling>
0.5˚C
Target temperature
Operation stops
1 hour at the set hours
TIMER operation +0.5˚C
NIGHT SET Mode ON temperature shift
(R22018)
<Heating>
Target temperature
2˚C
1 hour
Detail When this function is activated, the maximum capacity also decreases.
The remote controller can send the ECONO command when the unit is in cooling, heating,
dry, or automatic operation. This function can only be set when the unit is running. Press the
ON/OFF button on the remote controller to cancel the function.
This function and POWERFUL operation cannot be used at the same time. The latest
command has the priority.
ECONO operation
Time
(R21051)
High
Sensor output
Low
Human motion
Human detection ON
signal OFF (R19471)
The sensor detects human motion by receiving infrared rays and displays the pulse wave
output.
The microcomputer in the indoor unit carries out a sampling every 20 msec. and if it detects
10 cycles of the wave in 1 second in total, it judges humans are in the room as the motion
signal is ON.
The sensor may detect human motion with up to 20 msec. latency.
Human detection ON
signal OFF
↑ ↑ ↑
Reset Reset Reset
Target temperature
Remote controller ON
INTELLIGENT OFF
EYE button
Operation ON
OFF
Set speed Set speed
Fan speed (+)
OFF
(R19414)
Note: For dry operation, the temperature cannot be set with a remote controller, but the target
temperature is shifted internally.
Detail When the POWERFUL button is pressed, the fan speed and target temperature are converted
to the following states for 20 minutes.
Operation mode Fan speed Target temperature
COOL H tap + A rpm 18°C
DRY Dry rotating speed + A rpm Lowered by 2.5°C
HEAT H tap + A rpm 31.5°C
FAN H tap + A rpm —
AUTO Same as cooling / heating in The target temperature is
POWERFUL operation kept unchanged.
A = 40 ~ 50 rpm (depending on the model)
18˚C
(R19177)
Note: POWERFUL operation cannot be used together with ECONO or COMFORT AIRFLOW
operation.
0:00
Select
button
Clock
button
(R19926)
Detail
ON OFF ON OFF
[Tuesday] Use the copy mode to make settings for Tuesday to Friday, because these settings are the same as
to those for Monday.
[Friday]
Programme 1 Programme 2 Programme 3 Programme 4
ON OFF ON OFF
25˚C 27˚C
6:00 8:30 17:30 22:00
ON OFF OFF ON
• Up to 4 reservations per day and 28 reservations per week can be set using the WEEKLY TIMER. The effective use of the
copy mode simplifies timer programming.
• The use of ON-ON-ON-ON settings, for example, makes it possible to schedule operating mode and set temperature
changes. Furthermore, by using OFF-OFF-OFF-OFF settings, only the turn off time of each day can be set. This will turn off
the air conditioner automatically if you forget to turn it off.
Setting Displays
1. Press .
• The day of the week and the reservation number of the current day will be displayed.
• 1 to 4 settings can be made per day.
3. Press .
• The day of the week and reservation number will be set.
•“ ” and “ ” blink.
blank
• In case the reservation has already been set, selecting “ blank ” deletes the reservation.
• Proceed to STEP9 if “ blank ” is selected.
• To return to the day of the week and reservation number setting, press .
5. Press .
• The ON/OFF TIMER mode will be set.
•“ ” and the time blink.
7. Press .
• The time will be set.
•“ ” and the temperature blink.
9. Press .
• The temperature will be set and go to the next reservation setting.
• The temperature is set while in ON TIMER operation, and the time is set while in OFF
TIMER operation.
• The next reservation screen will appear.
• To continue further settings, repeat the procedure from STEP 4.
Display
• A reservation made once can be easily copied and the same settings used for another
day of the week. Refer to Copy mode .
NOTE
Notes on WEEKLY TIMER operation
• Do not forget to set the clock on the remote controller first.
• The day of the week, ON/OFF TIMER mode, time and set temperature (only for ON TIMER mode) can be set with the WEEKLY TIMER.
Other settings for the ON TIMER are based on the settings just before the operation.
• WEEKLY TIMER and ON/OFF TIMER operation cannot be used at the same time. The ON/OFF TIMER operation has priority if it is set while
WEEKLY TIMER is still active. The WEEKLY TIMER will enter the standby state, and “ ” will disappear from the LCD. When the
ON/OFF TIMER is up, the WEEKLY TIMER will automatically become active.
• Only the time and set temperature with the WEEKLY TIMER are sent with the . Set the WEEKLY TIMER only after setting the operation
mode, the airflow rate and the airflow direction ahead of time.
• Turning off the circuit breaker, power failure, and other similar events will render operation of the indoor unit’s internal clock inaccurate. Reset the clock.
• can be used only for the time and temperature settings. It cannot be used to go back to the reservation number.
Copy mode
• A reservation made once can be copied to another day of the week. The whole reservation of
the selected day of the week will be copied.
Setting Displays
1. Press .
3. Press .
• The whole reservation of the selected day of the week will be copied.
5. Press .
• The reservation will be copied to the selected day of the week. The whole reservation of
the selected day of the week will be copied.
• To continue copying the settings to other days of the week, repeat STEP 4 and STEP 5.
NOTE
Note on COPY MODE
• The entire reservation of the source day of the week is copied in the copy mode.
In the case of making a reservation change for any day of the week individually after copying the content of weekly reservations, press and
change the settings in the steps of Setting mode .
Confirming a reservation
• The reservation can be confirmed.
Setting Displays
Normal Confirmation
1. Press .
• The day of the week and the reservation number of the current day will be displayed.
• To change the confirmed reserved settings, select the reservation number and press .
The mode is switched to setting mode. Proceed to Setting mode STEP4.
Display
NOTE
• If not all the reservation settings are reflected, deactivate the WEEKLY TIMER operation once. Then press again to reactivate the
WEEKLY TIMER operation.
To delete reservations
An individual reservation
1. Press .
• The day of the week and the reservation number will be displayed.
blank
5. Press .
• The selected reservation will be deleted.
6. Press .
• If there are still other reservations, WEEKLY TIMER operation will be activated.
All reservations
Note: The cold air blast is prevented using similar control when defrost control starts or when the
thermostat is turned ON.
Note: When the ON/OFF button is pressed for 10 seconds or more, the forced cooling operation is
stopped.
Note: It takes 3 minutes to restart the operation because the 3-minute standby function is activated.
2. Function of Thermistor
Electronic
expansion valve
(1) (3)
(1) Outdoor Heat 1. The outdoor heat exchanger thermistor is used for controlling the target discharge pipe
Exchanger temperature. The system sets the target discharge pipe temperature according to the
Thermistor outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
2. In cooling operation, the outdoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature
becomes lower than the outdoor heat exchanger temperature, the discharge pipe thermistor
is judged as disconnected.
3. In cooling operation, the outdoor heat exchanger thermistor is used for high pressure
protection.
(2) Discharge 1. The discharge pipe thermistor is used for controlling discharge pipe temperature. If the
Pipe Thermistor discharge pipe temperature (used in place of the inner temperature of the compressor) rises
abnormally, the operating frequency becomes lower or the operation halts.
2. The discharge pipe thermistor is used for detecting disconnection of the discharge pipe
thermistor.
(3) Indoor Heat 1. The indoor heat exchanger thermistor is used for controlling the target discharge pipe
Exchanger temperature. The system sets the target discharge pipe temperature according to the
Thermistor outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
2. In cooling operation, the indoor heat exchanger thermistor is used for freeze-up protection
control. If the indoor heat exchanger temperature drops abnormally, the operating frequency
becomes lower or the operation halts.
3. In heating operation, the indoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature
becomes lower than the indoor heat exchanger temperature, the discharge pipe thermistor
is judged as disconnected.
3. Control Specification
3.1 Mode Hierarchy
Outline The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Note: Unless specified otherwise, a dry operation command is regarded as cooling operation.
Dropping function
Input current control, etc.
Initial Frequency When starting the compressor, the frequency is initialized according to the ∆D value of the
indoor unit.
PI Control 1. P control
The ∆D value is calculated in each sampling time (20 seconds), and the frequency is
adjusted according to its difference from the frequency previously calculated.
2. I control
If the operating frequency does not change for more than a certain fixed time, the frequency
is adjusted according to the ∆D value.
When the ∆D value is low, the frequency is lowered.
When the ∆D value is high, the frequency is increased.
Detail ON Condition
Outdoor temperature < 20°C
Discharge pipe temperature < outdoor temperature × 238/256 + 32.5°C
Radiation fin temperature < 85°C
OFF condition
Outdoor temperature > 22°C
Discharge pipe temperature > outdoor temperature × 238/256 + 37°C
Radiation fin temperature ≥ 90°C
Cooling Heating
A (Hz) 48 38
B (seconds) 70
C (°C) 15
C
B
A
(sec.)
D E F Time
(R13528)
A (Hz) 32
B (Hz) 55
C (Hz) 75
D (seconds) 200
E (seconds) 200
F (seconds) 470
Detail
Stop zone
A˚C
B˚C
Dropping zone
C˚C
Keep zone
D˚C
Up zone
E˚C
Reset zone
Discharge pipe
(R22432)
temperature
A (ºC) 120
B (ºC) 110
C (ºC) 108
D (ºC) 106
E (ºC) 104
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
Detail
Compressor Stop
(A)
Stop Zone
A
Dropping Zone
Keep Zone
C
(R14643)
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level
(depending on the model).
13˚C
Reset zone
A˚C
Up zone
B˚C
Keep zone
C˚C
Dropping zone
0˚C
Stop zone
(R22433)
Stop zone
A˚C
B˚C
Dropping zone
C˚C
Keep zone
D˚C
Up zone
E˚C
Indoor heat exchanger Reset zone
thermistor temperature
(R22434)
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
8. Fan ON/OFF control when operation (cooling, heating, dry) starts / stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF when
the operation stops.
D Hz
C Hz
PI control
Frequency
0 Hz 0 Hz
F sec.
E sec. G sec. H sec.
ON
Compressor
OFF
ON
Four way valve
OFF
J sec. 8 sec.
ON
Fan
OFF
Electronic expansion
valve opening Normal K pulse L pulse zone M pulse Starting
control zone zone control
(R21208)
A (minutes) 25
B (°C) 6 ~ 30
C (Hz) 55
D (Hz) 70
E (seconds) 60
F (seconds) 60
G (seconds) 460
H (seconds) 60
J (seconds) 5
K (pulse) 450
L (pulse) 400
M (pulse) 400
: The same value continues.
Detail The followings are the examples of electronic expansion valve control which function in each
operation mode.
: Available
: Not available
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every 20 seconds. The opening degree of the electronic expansion valve is adjusted by the
followings.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
3.13 Malfunctions
3.13.1 Sensor Malfunction Detection
Sensor malfunction can be detected in the following thermistor:
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
Detail If the OL (compressor head) temperature exceeds 130°C, the system shuts down the
compressor.
If the inverter current exceeds 18.0 A, the system shuts down the compressor.
Part 5
Remote Controller
1. Remote Controller .................................................................................45
Remote Controller 44
Remote Controller SiMT041509E
1. Remote Controller
Signal transmitter
Display (LCD)
• Displays the current settings.
Receiver (In this illustration, each section is
shown with all its displays on for the
purpose of explanation.)
• To use the remote controller, aim
the transmitter at the indoor unit. If
there is anything blocking the
signals between the unit and the
remote controller, such as a curtain,
the unit may not operate. Temperature adjustment
• The maximum transmission distance buttons
is about 7 m. • Changes the temperature setting.
Middle low
On/Off button
• Press this button once to start
operation.
Press once again to stop it.
High Middle high Middle
(R22030)
Note: Refer to the operation manual of applicable model for detail. You can download operation
manuals from Daikin Business Portal:
Daikin Business Portal → Product Information → Operation/Installation Manual
(URL: https://global1d.daikin.com/business_portal/login/)
45 Remote Controller
SiMT041509E Remote Controller
Note: Refer to the operation manual of applicable model for detail. You can download operation
manuals from Daikin Business Portal:
Daikin Business Portal → Product Information → Operation/Installation Manual
(URL: https://global1d.daikin.com/business_portal/login/)
Remote Controller 46
SiMT041509E
Part 6
Service Diagnosis
1. General Problem Symptoms and Check Items .....................................48
2. Troubleshooting with LED .....................................................................49
2.1 Indoor Unit..............................................................................................49
2.2 Outdoor Unit ...........................................................................................49
3. Service Diagnosis .................................................................................50
4. Troubleshooting ....................................................................................53
4.1 Error Codes and Description ..................................................................53
4.2 Indoor Unit PCB Abnormality .................................................................54
4.3 Freeze-up Protection Control / Heating Peak-cut Control ......................55
4.4 Fan Motor (DC Motor) or Related Abnormality.......................................56
4.5 Thermistor or Related Abnormality (Indoor Unit)....................................58
4.6 Low-voltage Detection or Over-voltage Detection..................................59
4.7 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)......61
4.8 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) ...............63
4.9 Outdoor Unit PCB Abnormality...............................................................64
4.10 Actuation of High Pressure Switch .........................................................65
4.11 OL Activation (Compressor Overload) ...................................................66
4.12 Compressor Lock ...................................................................................68
4.13 DC Fan Lock ..........................................................................................69
4.14 Input Overcurrent Detection ...................................................................70
4.15 Four Way Valve Abnormality..................................................................71
4.16 Discharge Pipe Temperature Control.....................................................73
4.17 Compressor System Sensor Abnormality ..............................................74
4.18 Position Sensor Abnormality ..................................................................75
4.19 Thermistor or Related Abnormality (Outdoor Unit).................................77
4.20 Electrical Box Temperature Rise............................................................79
4.21 Radiation Fin Temperature Rise ............................................................80
4.22 Output Overcurrent Detection ................................................................81
5. Check ....................................................................................................83
5.1 Thermistor Resistance Check ................................................................83
5.2 Indoor Fan Motor Connector Output Check ...........................................84
5.3 Power Supply Waveforms Check...........................................................84
5.4 Electronic Expansion Valve Check.........................................................84
5.5 Four Way Valve Performance Check .....................................................85
5.6 Inverter Unit Refrigerant System Check.................................................85
5.7 Inverter Analyzer Check .........................................................................86
5.8 Rotation Pulse Check on the Outdoor Unit PCB ....................................87
5.9 Installation Condition Check...................................................................88
5.10 Discharge Pressure Check.....................................................................88
5.11 Outdoor Fan System Check ...................................................................89
5.12 Main Circuit Short Check........................................................................89
5.13 Power Module Check .............................................................................90
47 Service Diagnosis
SiMT041509E General Problem Symptoms and Check Items
Check the outdoor temperature. Heating operation cannot be used when the
outdoor temperature is 18°CWB or higher, and —
cooling operation cannot be used when the
outdoor temperature is below 10°CDB.
Diagnose with remote controller
indication. — 53
Check the remote controller Check if address settings for the remote 94
addresses. controller and indoor unit are correct.
Operation sometimes Check the power supply. A power failure of 2 to 10 cycles stops air
stops. conditioner operation. (Operation lamp OFF) —
Check the outdoor temperature. Heating operation cannot be used when the
outdoor temperature is 18°CWB or higher, and —
cooling operation cannot be used when the
outdoor temperature is below 10°CDB.
Diagnose with remote controller
indication. — 53
The unit operates but does Check for wiring and piping errors in
not cool, or does not heat. the connection between the indoor — —
unit and outdoor unit.
Check for thermistor detection errors. Check if the thermistor is mounted securely. —
Check for faulty operation of the Set the unit to cooling operation, and check the
electronic expansion valve. temperature of the liquid pipe to see if the —
electronic expansion valve works.
Diagnose with remote controller
indication. — 53
Service Diagnosis 48
Troubleshooting with LED SiMT041509E
Operation lamp
(green)
(R21433)
Service Monitor The indoor unit has a green LED (LED A) on the control PCB. When the microcomputer works
in order, the LED A blinks. (Refer to page 9 for the location of LED A.)
49 Service Diagnosis
SiMT041509E Service Diagnosis
3. Service Diagnosis
Method 1 1. When the timer cancel button is held down for 5 seconds, 00 is displayed on the temperature
display screen.
(R21282)
< ARC466 Series >
2. Press the timer cancel button repeatedly until a long beep sounds.
The code indication changes in the sequence shown below.
Service Diagnosis 50
Service Diagnosis SiMT041509E
Method 2
1. Press the center of the Temp button and the Mode button at the same time.
(R11669)
(R11821)
(R11672)
(R11670)
4. Press the Temp or Temp button and change the number until you hear the two
consecutive beeps or the long beep.
(R11671)
51 Service Diagnosis
SiMT041509E Service Diagnosis
(R11672)
(R11673)
7. Press the Temp or Temp button and change the number until you hear the long beep.
(R11671)
10.Press the Mode button for 5 seconds to exit from the service check mode.
(When the remote controller is left untouched for 60 seconds, it returns to the normal mode
also.)
(R11672)
Service Diagnosis 52
Troubleshooting SiMT041509E
4. Troubleshooting
4.1 Error Codes and Description
Error Codes Description Reference
Page
System 00 Normal —
U2 Low-voltage detection or over-voltage detection 59
U4 Signal transmission error (between indoor unit and outdoor unit) 61
UA Unspecified voltage (between indoor unit and outdoor unit) 63
Indoor A1 Indoor unit PCB abnormality 54
Unit
A5 Freeze-up protection control / heating peak-cut control 55
A6 Fan motor (DC motor) or related abnormality 56
C4 Indoor heat exchanger thermistor or related abnormality 58
C9 Room temperature thermistor or related abnormality 58
Outdoor E1 Outdoor unit PCB abnormality 64
Unit
E3 Actuation of high pressure switch 65
E5 OL activation (compressor overload) 66
E6 Compressor lock 68
E7 DC fan lock 69
E8 Input overcurrent detection 70
EA Four way valve abnormality 71
F3 Discharge pipe temperature control 73
H0 Compressor system sensor abnormality 74
H6 Position sensor abnormality 75
H9 Outdoor temperature thermistor or related abnormality 77
J3 Discharge pipe thermistor or related abnormality 77
J6 Outdoor heat exchanger thermistor or related abnormality 77
L3 Electrical box temperature rise 79
L4 Radiation fin temperature rise 80
L5 Output overcurrent detection 81
P4 Radiation fin thermistor or related abnormality 77
: Displayed only when system-down occurs.
53 Service Diagnosis
SiMT041509E Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Combination of NO
the indoor and outdoor Match the compatible
unit matched? models.
YES
Check the connection of ∗ To secure the connection,
connectors (See Note.). once disconnect the connector
and then reconnect it.
NO NO
Voltage as rated? Correct the power
supply.
YES
Start operation.
Correct the connection.
YES
Error repeats? Replace the indoor unit
PCB (control PCB).
NO
Completed.
NO NO
Voltage as rated? Correct the power
supply.
YES
Start operation.
YES
Error repeats? Replace the indoor unit
PCB (control PCB).
NO
Completed.
Completed.
(R20486)
Service Diagnosis 54
Troubleshooting SiMT041509E
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.01
Refer to P.83 Check the air passage.
YES
Is there any short circuit? Provide sufficient air passage.
NO
YES
Dirty? Clean the air filter.
NO
Check the dust accumulation on
the indoor heat exchanger.
YES
Dirty? Clean the indoor heat
exchanger.
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
As
described in the NO
thermistor characteristic Replace the indoor heat
chart? exchanger thermistor.
YES
Replace the indoor unit PCB
(control PCB).
(R21064)
55 Service Diagnosis
SiMT041509E Troubleshooting
Error Decision The detected rotation speed does not reach the demanded rotation speed of the target tap, and
Conditions is less than 50% of the maximum fan motor rotation speed.
Service Diagnosis 56
Troubleshooting SiMT041509E
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the
voltage
fluctuation NO
within ±10% from Correct the power
the rated supply.
value?
YES
Turn off the power and
rotate the fan by hand.
YES
Turn on the power and
start operation.
Turn off the power and Note: The motor may break when the
NO disconnect the fan motor motor connector is disconnected
Does the fan while the power is turned on.
rotate? connector, then turn the
power on. (Be sure to turn off the power
before reconnecting the
YES connector.)
Check No.02
Check the output of the
fan motor connector.
Motor
power supply NO
voltage 310 ~ 340 Replace the indoor
VDC? unit PCB (control
PCB).
YES
Motor
control voltage 15 NO
VDC generated? Replace the indoor
unit PCB (control
PCB).
YES
Rotation NO
Stop the fan motor. command voltage Replace the indoor
1 ~ 6.5 VDC? unit PCB (control
PCB).
Check No.02 YES
Check the output of the
fan motor connector. Indoor fan
motor rotation pulse NO Replace the indoor
generated? fan motor.
YES
Replace the indoor
unit PCB (control
Indoor fan PCB).
NO
motor rotation pulse Replace the indoor
generated? fan motor.
YES
Replace the indoor
unit PCB (control
PCB). (R22444)
Note: The rotation pulse is the feedback signal from the indoor fan motor.
57 Service Diagnosis
SiMT041509E Troubleshooting
Error Decision The voltage between the both ends of the thermistor is 4.96 V and more or 0.04 V and less
Conditions during compressor operation.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.01
Refer to P.83 Check the connection of
connectors.
NO
Normal? Correct the connection.
YES
Check No. 01
Check the thermistor resistance
value.
NO
Normal? Replace the defective
thermistor.
YES
Replace the indoor unit PCB
(control PCB).
(R21870)
Service Diagnosis 58
Troubleshooting SiMT041509E
Outdoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Outdoor Unit
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 196 V.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer
(over 480 V).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
59 Service Diagnosis
SiMT041509E Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the
voltage fluctuation NO
within ±10% from the Correct the power supply.
rated value?
YES
Check the connection of the
compressor harness.
Loose or YES
disconnected? Reconnect the harness.
NO
Does the
NO
outdoor fan rotate Replace the outdoor fan motor
smoothly? and the outdoor unit PCB
(main PCB).
YES
NO
Error
again within 3 minutes NO
after turning on the Replace the outdoor
power? unit PCB (main PCB).
YES
Replace the indoor
unit PCB (control PCB).
(R20413)
Service Diagnosis 60
Troubleshooting SiMT041509E
Error Decision The data sent from the outdoor unit cannot be received normally, or the content of the data is
Conditions abnormal.
61 Service Diagnosis
SiMT041509E Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.11
Refer to P.84 Check the power supply voltage.
Is the
voltage fluctuation NO
within ±10% from the Correct the power supply.
rated value?
YES
Check the indoor unit - outdoor
unit connection wires.
YES
Is there any wiring error? Correct the indoor unit -
outdoor unit connection wires.
NO
NO
Properly insulated? Replace the connection wires
∗ Before you check the LED A, cancel between the indoor unit and
the standby electricity saving outdoor unit.
YES
function by starting fan operation
with the remote controller.
∗ Wait at least for 7 sec. after turning
on the power.
Check the LED A on the outdoor
unit PCB.
Continuously ON or OFF
Is LED A blinking? Replace the outdoor unit PCB
(main PCB).
Blink
Rotate the
outdoor fan by hand. NO
Does the outdoor fan rotate Replace the outdoor fan motor
smoothly? and the outdoor unit PCB
(main PCB).
YES
Check No.11
Check the power supply
waveform.
NO
Is there any disturbance? Replace the indoor unit PCB
(control PCB).
YES
Locate the cause of the
disturbance of the power
supply waveform, and correct
it.
(R21189)
Service Diagnosis 62
Troubleshooting SiMT041509E
Error Decision The pair type and multi type are interconnected.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check the combination of the
indoor and outdoor unit.
NO
OK? Match the compatible models.
YES
Connector S92 NO
properly connected to the Reconnect the connector S92.
PCB?
YES
NO
Are the NO
connecting wires connected Correct the connection.
property?
YES
Check the code numbers
(2P012345, for example) of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
(R22028)
63 Service Diagnosis
SiMT041509E Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
∗ Before you check the LED A,
Turn on the power again. cancel the standby electricity
saving function by starting fan
operation with the remote
controller.
∗ Wait at least for 7 sec. after
turning on the power.
Continuously ON or OFF
Is LED A blinking? Replace the outdoor unit
PCB (main PCB).
Blink
Check if the outdoor unit is
grounded.
NO
Grounded? Ground the system.
YES
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (main PCB).
(R21201)
Service Diagnosis 64
Troubleshooting SiMT041509E
Error Decision High pressure switch (S1PH) activating pressure: 4.15 MPa
Conditions High pressure switch (S1PH) recovery pressure: 3.2 MPa
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Stop valve open? Open the stop valve.
YES
High
pressure switch NO
connector S40 properly Reconnect the connector.
connected?
YES
Check
the resistance Nearly 0 Ω
between the pins 1 - 2 on Replace the outdoor unit PCB
the connector (main PCB).
S40.
Resistance ∞
Check
the resistance
between the 2 Nearly 0 Ω
Replace the harness for the high
terminals of the high pressure switch.
pressure switch
(S1PH).
Resistance ∞
Replace the high pressure switch
(S1PH).
(R22435)
65 Service Diagnosis
SiMT041509E Troubleshooting
Service Diagnosis 66
Troubleshooting SiMT041509E
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.01
Refer to P.83 Discharge YES
pipe thermistor Insert the thermistor in
disconnected? position.
Check No.12 NO
Refer to P.84
Check No. 01 NG
Check the thermistors. Replace the discharge pipe
∗ Discharge pipe thermistor thermistor.
Check No.13 OK
Refer to P.85
Connectors are NO
properly connected? Connect the connectors
∗ Connector S40 properly.
Check No.14 ∗ 2 terminals of OL (Q1L)
Refer to P.85 YES
Disconnect the connector S40
from the PCB.
Check Resistance
the resistance ∞
between the 2 terminals on Disconnect the 2 terminals of
connector S40. the OL (Q1L).
Check No. 12 NG
Check the electronic Replace the electronic
expansion valve. expansion valve or the coil.
OK
Check No. 13 NG
Check the four way Replace the four way valve
valve. or the coil.
Replace the outdoor unit
OK PCB (main PCB).
Check No. 14 NG
Check the refrigerant ∗ Refrigerant shortage Refer to the refrigerant line
line. ∗ Water mixed check procedure.
∗ Stop valve
OK
Replace the outdoor unit
PCB (main PCB).
(R20415)
67 Service Diagnosis
SiMT041509E Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
(Precaution before turning on the power again)
Check No.12
Make sure the power has been off for at least 30 seconds.
Refer to P.84
YES
Stop valve closed? Open the stop valve.
Check No.15
Refer to P.86
NO
Turn off the power. Disconnect the
harnesses U, V, and W.
NO
Any LED off? Correct the power supply or
replace the outdoor unit
PCB (main PCB).
YES
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
Emergency YES
stop without compressor Replace the compressor.
running?
NO
System shut NO
down after errors repeated Check the electronic
several times? expansion valve coil.
Go to Check No. 12.
YES
Replace the compressor.
(R21067)
Service Diagnosis 68
Troubleshooting SiMT041509E
Error Decision The fan does not start in about 30 seconds even when the fan motor is running.
Conditions If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.16
Fan motor connector YES
Refer to P.87 Turn off the power and
disconnected?
reconnect the connector.
NO
NO
Fan rotates NO
smoothly? Replace the outdoor fan
motor.
YES
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
YES YES
Replace the fuse.
69 Service Diagnosis
SiMT041509E Troubleshooting
Error Decision The current exceeds about 18.0 A for 2.5 seconds with the compressor running.
Conditions (The upper limit of the current decreases when the outdoor temperature exceeds a certain
level.)
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.15 ∗ An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input
Refer to P.86 overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
Check No. 17
Check No.17 Check the installation condition.
Refer to P.88
Start operation and measure the
input current.
Check No.18
Refer to P.88
Input current flowing NO
above its stop level? Replace the outdoor unit
PCB (main PCB).
YES
Turn off the power and disconnect
the harnesses U, V, and W.
YES
Any LED off? Correct the power supply or
replace the outdoor unit
PCB (main PCB).
NO
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Check No. 18
Check the discharge pressure.
(R21863)
Service Diagnosis 70
Troubleshooting SiMT041509E
Error Decision A following condition continues over 10 minutes after operating for 5 minutes.
Conditions <Cooling / Dry>
A – B < –5°C
<Heating>
B – A < –5°C
71 Service Diagnosis
SiMT041509E Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Check No.13
YES
Refer to P.85 Harness disconnected? Reconnect the harness.
NO
Check No.14 Check the continuity of the four way
Refer to P.85 valve coil and harness.
Resistance NO
between harnesses about Replace the four way
1000 ~ 2000 Ω? valve coil.
YES
Check No. 13 NG
Check the four way valve Replace the outdoor
switching output. unit PCB (main PCB).
OK
Check No. 01 NG
Check the thermistors. Replace the defective
thermistor(s).
OK
Check No. 14 NG
Check the refrigerant Refer to the refrigerant line
line. ∗ Refrigerant shortage check procedure.
∗ Water mixed
OK ∗ Stop valve
Service Diagnosis 72
Troubleshooting SiMT041509E
Error Decision If the temperature detected by the discharge pipe thermistor rises above A°C, the
Conditions compressor stops.
The error is cleared when the discharge pipe temperature has dropped below B°C.
A (°C) B (°C)
120 104
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.01
Check No. 01 NG
Refer to P.83 Check the thermistors. Replace the defective
∗ Discharge pipe thermistor thermistor(s).
∗ Outdoor heat exchanger thermistor
OK ∗ Outdoor temperature thermistor
Check No.12
Refer to P.84 Check No. 12 NG
Check the electronic Replace the electronic
expansion valve. expansion valve or the coil.
Check No.14 OK
Refer to P.85 Check No. 14 NG
Check the refrigerant Refer to the refrigerant line
line. ∗ Refrigerant shortage check procedure.
∗ Four way valve
OK ∗ Water mixed
∗ Stop valve
Replace the outdoor unit
PCB (main PCB).
(R20417)
73 Service Diagnosis
SiMT041509E Troubleshooting
Error Decision The voltage converted from the DC current before compressor start-up is out of the range
Conditions 0.5 ~ 4.5 V.
The DC voltage before compressor start-up is below 50 V.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Is the harness broken? Replace the harness.
NO
Restart operation NO
and error displayed Not a malfunction.
again? Keep observing.
YES
Replace the outdoor unit
PCB (main PCB).
(R22016)
Service Diagnosis 74
Troubleshooting SiMT041509E
Error Decision The compressor fails to start in about 15 seconds after the compressor run command signal
Conditions is sent.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
75 Service Diagnosis
SiMT041509E Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
OK? Replace the stop valve.
YES
Check No. 20
Check the short circuit of the diode
bridge.
NO
Normal? Replace the outdoor unit
PCB (main PCB).
YES
Electrical
components or NO
compressor harnesses Reconnect the electrical
connected as components or compressor
specified? harnesses as specified.
YES
Turn on the power. Check the
electrolytic capacitor voltage.
+ 100 NO
Within 320 – 50 VDC? Replace the outdoor unit
PCB (main PCB).
YES
Turn off the power. Disconnect the
harnesses U, V, and W.
NO
Any LED off? Replace the compressor.
YES
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
(R22376)
Service Diagnosis 76
Troubleshooting SiMT041509E
Error Decision The voltage between the both ends of the thermistor is above 4.96 V or below 0.04 V with
Conditions the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Troubleshooting In case of P4
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
77 Service Diagnosis
SiMT041509E Troubleshooting
Error displayed NO
again on remote Reconnect the connectors
controller? or thermistors.
YES
Check No. 01
Check the thermistor resistance
value.
NO
Normal? Replace the defective
thermistor(s) of the following
J3 error: the discharge thermistors.
pipe temperature is YES ∗ Outdoor temperature
lower than the heat thermistor
exchanger temperature. ∗ Discharge pipe thermistor
Cooling: Outdoor heat ∗ Outdoor heat exchanger
exchanger thermistor
temperature
Heating: Indoor heat
exchanger
temperature
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
Indoor heat NO
exchanger thermistor Replace the indoor heat
functioning? exchanger thermistor.
YES
Replace the outdoor unit
PCB (main PCB).
(R20406)
Service Diagnosis 78
Troubleshooting SiMT041509E
Error Decision With the compressor off, the radiation fin temperature is above A°C.
Conditions The error is cleared when the radiation fin temperature drops below B°C.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above C°C and stops when it drops below B°C.
A (°C) B (°C) C (°C)
90 75 81
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.17 WARNING
Turn off the power. Then, turn on
Refer to P.88 the power to restart the system. To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above C °C. The outdoor fan stops
Check No.19 when the radiation fin temperature
Refer to P.89 drops below B°C.
Error again or outdoor YES
fan activated?
NO
Check the radiation fin
temperature.
NO
Above A˚C? Replace the outdoor unit
PCB (main PCB).
YES
Check No. 19 NG
Check the outdoor fan. Replace the outdoor fan
motor.
Correct the connectors
OK and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
NO
Radiation fin dirty? Check the installation
condition.
Go to Check No. 17.
YES
Clean up the radiation fin.
(R21436)
79 Service Diagnosis
SiMT041509E Troubleshooting
Error Decision If the radiation fin temperature with the compressor on is above A°C.
Conditions The error is cleared when the radiation fin temperature drops below B°C.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
A (°C) B (°C)
90 84
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No.17
Refer to P.88 Turn off the power. Then, turn on
the power to restart the system.
NO
Above A ˚C? Replace the outdoor unit
PCB (main PCB).
YES
Check No. 19 NG
Check the outdoor fan. Replace the outdoor fan
motor.
Correct the connectors and
OK fan motor leads.
Replace the outdoor unit
PCB (main PCB).
NO
Radiation fin dirty? Check the installation
condition.
Go to Check No. 17.
YES
Clean up the radiation fin.
(R21437)
Note: Refer to Silicon Grease on Power Transistor / Diode Bridge on page 95 for detail.
Service Diagnosis 80
Troubleshooting SiMT041509E
Error Decision A position signal error occurs while the compressor is running.
Conditions A rotation speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
81 Service Diagnosis
SiMT041509E Troubleshooting
Troubleshooting Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
∗ An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output
Check No.15 overcurrent after the wires have been disconnected and reconnected for part replacement, check the
Refer to P.86 wiring again.
Check No. 17
Check the installation condition.
Check No.17
Refer to P.88
NO
Stop valve fully open? Fully open the stop valve.
Check No.18
YES
Refer to P.88
Turn off the power. Then, turn on
the power to restart the system.
See if the same error occurs.
Check No.22
Refer to P.90
NO Monitor the power supply voltage,
Error again? discharge and suction pressures,
and other factors for a long term.
YES Possible causes
∗ Momentary drop of power supply
Turn off the power and disconnect voltage Not a malfunction.
the harnesses U, V, and W. ∗ Compressor overload Keep observing.
∗ Short circuit Check the connectors and
other components.
YES
Any LED off? Correct the power supply
or replace the outdoor unit
PCB (main PCB).
NO
Check No. 22
Check the power module.
NO
Normal? Replace the outdoor unit
PCB (main PCB).
YES
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
NO
Voltage as rated? Correct the power supply.
YES
Short circuit or NO
wire breakage between Check the discharge
compressor's coil pressure.
phases? Go to Check No. 18.
YES
Replace the compressor.
(R21438)
Service Diagnosis 82
Check SiMT041509E
5. Check
5.1 Thermistor Resistance Check
Check No.01 Disconnect the connectors of the thermistors from the PCB, and measure the resistance of
each thermistor using multimeter.
The data is for reference purpose only.
Thermistor temperature (°C) Resistance (kΩ)
–20 197.8
–15 148.2
–10 112.1
–5 85.60
0 65.93
5 51.14
10 39.99
15 31.52
20 25.02
25 20.00
30 16.10
35 13.04
40 10.62
45 8.707
50 7.176
(R25°C = 20 kΩ, B = 3950 K)
(kΩ)
150
100
50
–15 0 15 30 45
(˚C) (R11905)
Multimeter (R19752)
(R19751)
When the room temperature thermistor is soldered on a PCB, remove the PCB from the
control PCB to measure the resistance.
When the connector of indoor heat exchanger thermistor is soldered on a PCB, remove the
thermistor and measure the resistance.
83 Service Diagnosis
SiMT041509E Check
(R1444)
(R1736)
1-5
2-5
S20 5P Connector Check 3-5
4-5
1 2 3 4 5
(R20506)
Service Diagnosis 84
Check SiMT041509E
S80
voltage at 220 - 240 NO
VAC with compressor Replace the outdoor unit
on? (Fig. 1) PCB (main PCB).
YES
Disconnect the four way valve coil
from the connector and check the
continuity.
Four way NO
valve coil resistance at Replace the four way valve
1000 ~ 2000 Ω? coil.
YES
Replace the four way valve.
(R21439)
(Fig. 1)
Voltage at S80
Time
Compressor
ON
(R11904)
Is the
discharge pipe YES
thermistor disconnected Reconnect the thermistor.
from the holder?
NO
Check for refrigerant leakage.
See the service diagnosis on
refrigerant shortage (U0).
(R15833)
85 Service Diagnosis
SiMT041509E Check
If an abnormal stop occurs due to compressor startup failure or overcurrent output when using
an inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or
some other failure (main PCB, power module, etc.). The inverter analyzer makes it possible to
judge the cause of trouble easily and securely. (Connect an inverter analyzer as a quasi-
compressor instead of compressor and check the output of the inverter.)
Operation Method
Step 1
Be sure to turn off the power.
Step 2
Install an inverter analyzer instead of a compressor.
Note:
Make sure the charged voltage of the built-in smoothing electrolytic capacitor drops to 10
VDC or below before carrying out the service work.
(2) Connect the terminals to the
(1) Remove the terminals from terminals of the inverter
the compressor. analyzer.
Compressor
Inverter analyzer
Step 3
Activate power transistor test operation from the indoor unit.
Service Diagnosis 86
Check SiMT041509E
Caution
(1) When the output frequency is low, the LEDs blink slowly. As the output frequency increases,
the LEDs blink quicker. (The LEDs look like they are lit.)
(2) On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
Direction of crimp
FASTON terminal
(R15292)
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2 → Defective PCB → Replace the outdoor unit PCB (main PCB).
If NG in step 4 → Defective Hall IC → Replace the outdoor fan motor.
If OK in both steps 2 and 4 → Replace the outdoor unit PCB (main PCB).
PCB
S70
1 Actual rotation pulse input (0 ~ 15 VDC)
2 Rotation command voltage (0 ~ 6.5 VDC)
3 Control voltage 15 VDC
4
5
6
7 320 VDC
(R19655)
87 Service Diagnosis
SiMT041509E Check
OK
NO
NO
NO
High? Replace the compressor.
YES
NO
Is the stop valve open? Open the stop valve.
YES
NO
Is the air
filter or indoor / outdoor NO
heat exchanger Replace the compressor.
dirty?
YES
Clean the dirty air filter or
indoor / outdoor heat
exchanger.
(R19385)
Service Diagnosis 88
Check SiMT041509E
YES YES
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is ∞ or less than 1 kΩ, short circuit occurs on the main circuit.
Positive terminal (+) of – (1)
digital multimeter ~ (2, 3) + (4) ~ (2, 3)
Negative terminal (–) of
digital multimeter + (4) ~ (2, 3) – (1) ~ (2, 3)
Resistance is OK. several kΩ ~ several MΩ
Resistance is NG. 0 Ω or ∞
4 3 2 1
– ~ ~ +
– +
Multimeter
(R22377)
89 Service Diagnosis
SiMT041509E Check
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the terminals of the power
module and the terminals of the compressor with a multimeter. Evaluate the measurement
results referring to the following table.
W V U
DC+
DC–
(R22378)
Service Diagnosis 90
SiMT041509E
Part 7
Trial Operation and Field
Settings
1. Tips for Servicing ..................................................................................92
1.1 Pump Down Operation ...........................................................................92
1.2 Forced Cooling Operation ......................................................................92
2. Trial Operation ......................................................................................93
3. Field Settings ........................................................................................94
3.1 When 2 Units are Installed in 1 Room....................................................94
3.2 Jumper Settings .....................................................................................94
4. Silicon Grease on Power Transistor / Diode Bridge..............................95
Detail 1. Remove the valve caps from the liquid stop valve and the gas stop valve.
2. Carry out forced cooling operation.
3. After 5 ~ 10 minutes, close the liquid stop valve with a hexagonal wrench.
4. After 2 ~ 3 minutes, close the gas stop valve and stop the forced cooling operation.
Hexagonal
wrench
Close
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
for 5 seconds.
Command
frequency 30 Hz
End The forced cooling operation ends when any of the following conditions is
fulfilled.
Indoor Unit
2. Trial Operation
Outline Carry out the trial operation in accordance with the operation manual to ensure that all functions
and parts, such as flap movement, are working properly.
Trial operation should be carried out in either cooling or heating operation.
Detail 1. Measure the power supply voltage and make sure that it falls within the specified range.
2. In cooling operation, select the lowest programmable temperature (18°C); in heating
operation, select the highest programmable temperature (30°C).
Trial operation may be disabled in either operation mode depending on the room
temperature.
After trial operation is complete, set the temperature to a normal level (26°C ~ 28°C in
cooling, 20°C ~ 24°C in heating operation).
For protection, the system does not start for 3 minutes after it is turned off.
ARC466 Series
(1) Press the On/Off button to turn on the system.
(2) Press the center of the Temp button and the Mode button at the same time.
(3) Select T (trial operation) with the Temp or Temp button.
(4) Press the Mode button to start the trial operation.
(5) Press the Mode button and select operation mode.
(6) Trial operation terminates in approximately 30 minutes and switches into normal mode. To
quit trial operation, press the On/Off button.
(3)
(2) (3)
3. Field Settings
3.1 When 2 Units are Installed in 1 Room
Outline When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding
wireless remote controller can be set for different addresses.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB Cut the address setting jumper JA on the control PCB.
ADDRESS
ADDRESS:JA
1
2
ADDRESS
JB
EXIST
CUT
JA
JC JA
(R9665)
ADDRESS Jumper
EXIST 1
CUT 2
Caution Replace the remote controller if you cut the jumper on the left side.
The heating operation will not be available when the jumper on the left side is cut.
Note: Smoke emission may be caused by bad heat radiation when the silicon grease is not
appropriately applied.
Power transistor
(or diode bridge)
PCB
Radiation
fin
(R21866)
Part 8
Appendix
1. Piping Diagrams....................................................................................97
1.1 Indoor Unit..............................................................................................97
1.2 Outdoor Unit ...........................................................................................98
2. Wiring Diagrams..................................................................................101
2.1 Indoor Unit............................................................................................101
2.2 Outdoor Unit .........................................................................................102
Appendix 96
Piping Diagrams SiMT041509E
1. Piping Diagrams
1.1 Indoor Unit
FTKM18/24PVMK FTKM28PVMK
DISTRIBUTOR DISTRIBUTOR
HEAT EXCHANGER HEAT EXCHANGER
THERMISTOR THERMISTOR
CROSS FLOW FAN ON HEAT EXCH. CROSS FLOW FAN ON HEAT EXCH.
FIELD PIPING FIELD PIPING
6.4 CuT M 6.4 CuT M
FAN MOTOR FAN MOTOR
HEADER HEADER
4D065825C 4D092476
FTXM18/24PVMK FTXM28PVMK
7.9CuT 7.9CuT
DISTRIBUTOR DISTRIBUTOR
HEAT EXCHANGER HEAT EXCHANGER
THERMISTOR THERMISTOR
CROSS FLOW FAN ON HEAT EXCH. CROSS FLOW FAN ON HEAT EXCH.
FIELD PIPING FIELD PIPING
6.4CuT M 6.4CuT M
FAN MOTOR FAN MOTOR
HEADER HEADER
4D065823E 4D081250D
97 Appendix
SiMT041509E Piping Diagrams
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
7.9 CuT THERMISTOR
7.9 CuT
MUFFLER STRAINER
WITH
DC FAN MOTOR M FILTER
PROPELLER FAN
RECEIVER
MUFFLER
9.5 CuT MUFFLER
WITH
7.9 CuT FILTER
HPS MUFFLER FIELD PIPING
9.5 CuT
STOP VALVE
GAS LINE
REFRIGERANT FLOW STOP VALVE
ACCUMULATOR
COOLING COMPRESSOR 12.7 CuT FIELD PIPING
GAS (12.7 CuT)
3D092780
RKM24PVMK
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
7.9 CuT
THERMISTOR
7.9 CuT
PROPELLER FAN
6.4 CuT
4-WAY
VALVE
12.7 CuT 12.7 CuT
MUFFLER
9.5 CuT
7.9 CuT
HPS MUFFLER FIELD PIPING
9.5 CuT
GAS LINE
REFRIGERANT FLOW STOP VALVE
ACCUMULATOR
COOLING COMPRESSOR FIELD PIPING
12.7 CuT GAS (12.7 CuT)
3D092777
Appendix 98
Piping Diagrams SiMT041509E
RKM28PVMK
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
7.9 CuT THERMISTOR
7.9 CuT
12.7 CuT
6.4 CuT
4-WAY
12.7 CuT VALVE 12.7 CuT
MUFFLER
9.5 CuT
7.9 CuT
HPS MUFFLER FIELD PIPING
LIQUID (6.4 CuT)
9.5 CuT
3D092776
RXM18PVMK
OUTDOOR UNIT
THERMISTOR
MOTOR
OPERATED
7.9 CuT 7.9 CuT VALVE 6.4 CuT
MUFFLER STRAINER
WITH
DC FAN MOTOR M FILTER
PROPELLER FAN
RECEIVER
6.4 CuT 6.4 CuT
4-WAY
VALVE
12.7 CuT ON: HEATING 12.7 CuT
MUFFLER
9.5 CuT MUFFLER
7.9 CuT WITH
FILTER
HPS MUFFLER FIELD PIPING
6.4 CuT LIQUID (6.4 CuT)
9.5 CuT
THERMISTOR
STOP VALVE
3D092779
99 Appendix
SiMT041509E Piping Diagrams
RXM24PVMK
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
7.9 CuT THERMISTOR
7.9 CuT
4-WAY
VALVE
6.4 CuT
12.7 CuT ON: HEATING 12.7 CuT
MUFFLER
9.5 CuT
7.9 CuT
HPS MUFFLER FIELD PIPING
9.5 CuT
GAS LINE
REFRIGERANT FLOW STOP VALVE
ACCUMULATOR
COOLING COMPRESSOR FIELD PIPING
HEATING 12.7 CuT GAS (12.7 CuT)
3D092775
RXM28PVMK
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
7.9 CuT THERMISTOR
7.9 CuT
12.7 CuT
PROPELLER FAN
4-WAY
6.4 CuT
VALVE
12.7 CuT ON: HEATING 12.7 CuT
MUFFLER
9.5 CuT
7.9 CuT
HPS MUFFLER FIELD PIPING
LIQUID (6.4 CuT)
9.5 CuT
3D092764
Appendix 100
Wiring Diagrams SiMT041509E
2. Wiring Diagrams
2.1 Indoor Unit
FTK(X)M18/24/28PVMK
WIRING DIAGRAM
1
PCB3 PCB1
S49 S46 FU1 X1M 2
1 BLK 1 F1U H1
LED1 BLK 1
BLK 3
H1P 3.15A OUTDOOR
BLK ~ WHT 2
BLK C102 V1
LED2 - RED 3
BLK MR10 H2
H2P GRN
BLK
BLK FIELD WIRING.
LED3
H3P BLK C101 GRN / YLW
TRANSMISSION H3
9 BLK 9
CIRCUIT CAUTION
SW1 NOTE THAT OPERATION WILL RESTART
S21 FG
AUTOMATICALLY IF THE MAIN POWER SUPPLY
IS TURNED OFF AND THEN BACK ON AGAIN.
t˚
FU2
HA S1
F2U 7
BZ RTH1 RED
R1T 3.15A BZ : BUZZER
C101, C102 : CAPACITOR
4
S25 BLU FG : FRAME GROUND
1 BLK 1 BRN MS F1U, F2U : FUSE
PCB4
S36 BLK ORG 3~
H1P~H3P : PILOT LAMP
3 1 WHT
BLK MR10 : MAGNETIC RELAY
4 S47 S32 S41 M1F
M1F : FAN MOTOR
INTELLIGENT EYE 1 3 1 2 16 8 10 12 14 2 5 3 4 6 15 13 11 9 7 1
M1S~M3S : SWING MOTOR
SENSOR
PCB1~PCB4 : PRINTED CIRCUIT BOARD
BLK
BLK
BLK
BLK
BLK
ORG
ORG
RED
RED
RED
YLW
YLW
YLW
PNK
PNK
PNK
BLU
BLU
BLU
S1~S49 : CONNECTOR
PCB2 S48 SW1 : OPERATION SWITCH
1 3 t˚
WIRELESS V1 : VARISTOR
REMOTE INDOOR
R2T X1M : TERMINAL STRIP
CONTROLLER MSW MSW MSW
SIGNAL : PROTECTIVE EARTH
RECEIVER
M1S M2S M3S
3D060942R
101 Appendix
SiMT041509E Wiring Diagrams
RED
YLW
BLU
1 10 1 4 1 8 1 3 1 5 1 4 7 1 3
FIELD WIRING. S80
POWER SUPPLY 1 3
1~220-240V X11A
WHT
WHT
ORG
WHT
ORG
GRY
GRY
RED
RED
RED
BRN
RED
YLW
YLW
YLW
YLW
BLU
BLU
BLU
BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
RED
YLW
BLU
50/60Hz
IN CASE OF
COOLING P> M
V
JUMPER MS MS Y1S W U
ONLY TYPE MS
(LOCAL SETTING) S1PH Q1L t˚ t˚ t˚ 3~
M2F Y1E M1F IN CASE OF
NOTE R1T R3T
HEAT PUMP M1C
1. REFER TO THE NAMEPLATE (OUTDOOR) R2T (DISCHARGE)
FOR THE POWER REQUIREMENTS. (CONDENSER) OUTDOOR TYPE
C110 : CAPACITOR
DB1 : DIODE BRIDGE PAM : PULSE AMPLITUDE MODULATION SA1 : SURGE ARRESTER
FU1, FU2, FU3 : FUSE PCB : PRINTED CIRCUIT BOARD V2, V3, V401 : VARISTOR
IPM1 : INTELLIGENT POWER MODULE PS : SWITCHING POWER SUPPLY X1M : TERMINAL STRIP
L : LIVE Q1L : OVERLOAD PROTECTOR Y1E : ELECTRONIC EXPANSION VALVE COIL
M1C : COMPRESSOR MOTOR R1T, R2T, R3T : THERMISTOR Y1S : REVERSING SOLENOID VALVE COIL
M1F, M2F : FAN MOTOR S1PH : HIGH PRESSURE SWITCH Z1C, Z2C, Z3C, Z4C : FERRITE CORE
MR4, MR30, S20, S40, S70, ZF : NOISE FILTER
MRM10, MRM20 : MAGNETIC RELAY S80, S90, S92, : PROTECTIVE EARTH
N : NEUTRAL S100, X11A : CONNECTOR : EARTH
3D092518
Appendix 102
Revision History
Month / Year Version Revised contents
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/products/ac/
c All rights reserved
zSpecifications, designs and other content appearing in this brochure are current as of July 2015 but subject to change without notice.
SiMT041509E
07/2015 AK.B