Pocket Guide 27: Insulation Resistance Testing - SELV and PELV Circuits
Pocket Guide 27: Insulation Resistance Testing - SELV and PELV Circuits
POCKET GUIDE 27
Insulation resistance testing –
SELV and PELV circuits
This Guide covers insulation resistance (IR) testing of SELV (separated extra-low
voltage) and PELV (protective extra-low voltage) circuits. These are circuits
having a nominal voltage not exceeding 50 V a.c. or 120 V ripple-free d.c.,
complying with Section 414 of BS 7671. IR testing of FELV circuits is not covered
by this Guide; see NICEIC and ELECSA Pocket Guide 26, Insulation resistance
testing – low voltage and FELV circuits.
This Guide should be read in conjunction with Pocket Guide 26, as many of the
general principles referred to in that Guide also apply to IR testing of SELV and
PELV circuits.
SELV and PELV circuits generally form only part of an installation. There is not
usually a SELV or PELV switchboard or distribution board. An example of a SELV
or PELV circuit is an extra-low voltage circuit fed by a safety isolating transformer
and supplying luminaires.
Like IR testing of low voltage (LV) and FELV circuits, IR testing of SELV and PELV
circuits is carried out with a test instrument to BS EN 61557-2, set to the highest
resistance scale, such as 200 M⍀. However, the values of test voltage and
insulation resistance are subject to requirements that are different from those for
LV and FELV circuits, as explained in this Guide.
A and, where applicable, (B)
The IR tests referred to in (A) B of this Guide must
be carried out (with satisfactory results) before the SELV or PELV circuits are first
energised, and should be repeated periodically during the life of the installation.
Amd 3: 2015
Based on information as at January 2015 © Certsure LLP Pocket Guide 27 rev 1 01/15