SINDH BUILDING CONTROL AUTHORITY (SBCA)

VETTING REPORT
NAME OF PROJECT: PLOT- 13, TYPE SB, SECTOR-Z, SUB
SECTOR – II, GULSHAN-E-MAYMAR,
SCHEME NO - 45, KARACHI.

NAME OF ARCHITECT: ARCHITECT FAIZA MUNIR

NAME OF OWNER: MR. ABDUL JABBAR

NAME OF STRUCTURAL ENGINEER: ENGR. SULEHA KISHWAR

NAME OF ENGINEER:PROOF ENGR. M. KAMIL DEHLVI

DATE:

1
Sindh Building Control Authority (SBCA)

STRUCTURAL DESIGN / DRAWINGS

PROOF CHECKING/ VETTING REPORT

When a work of vetting/ proof checking is awarded to any proof structure section of SBCA shall hand over
following documents to Vetting Engineer.

1. Set of Structural Drawings provided by the Original Designer.


2. Set of Structural Calculation provided by the Original Designer.
3. Original Soil Report of the Project provided by the Original Designer.
4. Approved Concept Architectural Plan forwarded by concerned town.
5. Specified Vetting Performa.

VETTING REPORT & PROCEDURE OF VETTING

On receipt of above documents from structure section, vetting engineer shall thoroughly proof check the
design and drawings or make individual calculations wherever required. The vetting engineers should also
ensure the compatibility of structural drawings with approved architectural concept plan. In case vetting
engineer observe any discrepancy in design & drawing provided by the original designer. He should inform
in writing to original design for rectification along with a copy to structure section.

On compilation of job vetting consultants is required to submit vetting report on prescribed format. This
report will summarized the approached adopted and certify it by stamping and signing the final structural
drawing as VETTED drawings for submission in SBCA. By certifying and signing the vetting report and
vetted drawing and design the vetting engineer would assure equal responsibility with original design
engineer for the adequacy of structural design as required by code.

The following documents are required to be submitted along with vetting report in SBCA by vetting
Engineer.

Six sets of Structural Drawings dully Vetted and Signed by all Professionals and Owner of the Project.
Two sets of Structural Calculations dully Vetted and Signed by Structural Engineer and Proof Engineer.
Two sets of Soil Investigation Report with verified copy of Soil certificate.
4. Two copies of Vetting Report on the prescribe format dully signed and stamped by the proof Engineer
and structural Engineer.
5. Verified copy of the approved concept architecture plan provided by the SBCA.

2
SECTION – 1

OWNER/PLOT INFORMATION

Parameter/ Details to be Filled To be Filled by Remarks By


By Original Structural Designer Original Structural Designer Proof Engineer

a) Name of Owner MR. ABDUL JABBAR


OK

PLOT- 13, TYPE SB, SECTOR-Z, SUB


SECTOR – II, GULSHAN-E-MAYMAR,
SCHEME NO - 45, KARACHI.
b) Name & Address of the
Project. OK

3
SECTION – 2

ARCHITECTURAL INFORMATION

Parameter/Details to be filled To be Filled by Remarks By


By Original Structural Designer Original Structural Designer Proof Engineer

a) Name & Address of Architect AR. FAIZA, SUIT # 11, SADAF OK


APPARTMENT , SB-13, BLOCK-
13B,GULSHAN TOWN , KARACHI.

b) Total No. of Stories incl. OK


1 BASEMENT+GROUND+15
Basement STORIES

c) Type of Occupancy OK
COMMERCIAL

4
SECTION – 3
STRUCTURAL DESIGNER’S INFORMATION

Parameter/Details to be Filled To be Filled by Remarks By


By Original Structural Designer Original Structural Designer Proof Engineer

a) Name & Address of OK


ENGR. SULEHA KISHWAR
Structural Design
, SINDH PAKISTAN.

e) SBCA Reg. No & Exp. Date SE-06- 311 OK


ST
31 DECEMBER,2021

5
SECTION – 4
DESIGN DATA AND PARAMETERS

Parameter/Details to be Filled To be Filled by Remarks By


By Original Structural Designer Original Structural Designer Proof Engineer

a) Name & Address of Soil


Consultants OK
b) Building Structural Design

Codes used ACI-318-05

UBC-97 OK

c) Peak Ground Acceleration  Ca = 0.24


(PGA) on Rock Assumed for
Seismic Design  Cv = 0.32
OK
 0.16g to 0.24g

6
Parameter/Details to be Filled To be Filled by Remarks By
By Original Structural Designer Original Structural Designer Proof Engineer

d) Soil Class Definition as per OK


Soil Report SC
AS PER SOIL REPORT

e) Safe Bearing Capacity of RAFT FOUNDATION:


Foundation at Depth Tons/ft2 4.6 @ Depth 13 ft OK

f) Type of Structure  Reinforced Concrete.


□ Pre or Post Tensioned Conc.
□ Steel Structure □ Composite □ Timber O
Structure
□ Combination of above □ Other
(Describe in detail)

-------------------------------------------

-------------------------------------------

-------------------------------------------

7
Parameter/Details to be Filled To be Filled by Remarks By
By Original Structural Designer Original Structural Designer Proof Engineer

g) Wind Load □ Design Speed …….m/s Basic …m/s


(Does not govern)

□ Pressure ………..… Kg/Sm N/A


□ Gust…………………… %

h) Live Loads a) 100 psf GROUND OK


b) 40 psf UPPER FLOORS

i) Impact Factors (where a) b) N/A


Applicable) c) d)

j) Other Loads a) Fire Engine = ………………


b) Landscape = ………………..
c) Glazing = …………. KN/m2
d) Finishes = 36Psf OK
e) Seismic= as per Zone-2B

8
Parameter/Details to be Filled By To be Filled by Remarks By
Original Structural Designer Original Structural Designer Proof Engineer

k) Pile Dia. Depth and Safe Dia:……………………... mm N/A


Allowable Load Capacity if
Depth……………………. M
Applicable

Safe Allowable Load for :


 ………… mm Dia ………… M Tons
 …………. mm Dia .………. M Tons

l) Types of Foundation in Final RAFT FOOTING OK


Structural Design

□ Reinforced Concrete Piles


□ Raft
□ Other (show on plans and describe here)
……………………………………………..

m) Type of Framing System Used  Concrete Intermediate Moment OK


Resisting Frame – CIMRF
for Gravity and Lateral Load
□ Concrete Special Moment Resisting
Frame – CSMRF

□ Lateral Loads Resisted by Dual Action


Moment Frame and Shear Wall

 Lateral Load Resisted by Shear Wall OK

9
Parameter/Details to be Filled By To be Filled by Remarks By
Original Structural Designer Original Structural Designer Proof Engineer

n) Computer Programs used a) Gravity Analysis ETABS 16.0.2


*Original Designer shall b) Lateral Analysis ETABS 16.0.2
Provide Explanatory Notes c) Design ETABS 16.0.2,SAFE 16.0.0 OK
and Sample Versions of the d) Detailing AUTOCAD
Programs marked in asterisks e) Other …….………
To the Proof Engineer. f) In House EXCEL SHEETS

o) Other Structural Design a) Min width of RCC Column 8 in


Parameters in Original Design b) Max. Width of RCC Beams 12 in
c) Max. Beam and Column Depth-to
Width Ratio 4.5(Beam), 2.5(Column)

d) Min. Beam Span-to-Depth Ratio 2.5

e) Min. Thickness of the Floor


Diaphragm __ in

f) Max. Story Height Ft OK

g) Frame Geometry
i) Beams Span to Column Height Ratio
Max. And Min.0.4

ii) Horizontal or Vertical Irregularity


if any NO

iii) Torsional eccentricities if any


YES

10
Parameter/Details to be Filled By To be Filled by Remarks By
Original Structural Designer Original Structural Designer Proof Engineer

h) Reinforcing Bars Geometry/ Min. Dia


i) Beams – Main #5 OK
Stirrups #3

ii) Columns –Main #5


Stirrups #3

iii) Slabs – Main #3


iv) Footings #4
Soft Stories if any
□ Yes
No OK

j) Are fill-in-block walls reinforced and ties


To peripheral RCC Beam/ Column/
Walls/ Slabs?
□ Yes □ No, If answer is Yes has
In fills considered in analysis. Also identify OK
Such infill walls. If answer is No. Explain.

k) Picked up Columns if any in front façade OK


□ Yes □ No, If Yes provide location.

11
Parameter/Details to be Filled By To be Filled by Remarks By
Original Structural Designer Original Structural Designer Proof Engineer

p) Material Specifications: Reinforcing Steel 60 Ksi OK


(Ref: ASTM or Compatible BS
Standards)

Cylinder Strength of Concretes:


Footings & Tie Beams 3600 Psi w/c 0.5 OK
..
(w/c= water cement ratio)

i) Piles ……………. Psi w/c ……


ii) Piles Caps………….Psi w/c ….
iii)Water Retaining Struct. 4000 Psi w/c OK
0.4

iv) Ret. Walls 4000Psi w/c 0.4 OK

v) Columns: 4000 Psi w/c 0.4 OK

vi) Beams / Slabs : OK


 3000 Psi w/c 0.5
vii) Struct Steel: ASTM/BS Designation
Yield Strength …………. MPa

viii) Bolts Type with yield strength: ______


Welds: AWS Designations……………

ix) Timber Structures: -

x) Reinforced Concrete Masonry Strength

12
Parameter/Details to be Filled By To be Filled by Remarks By
Original Structural Designer Original Structural Designer Proof Engineer

q) Original Designers All Designed requirements are fulfilled. OK


Explanatory Remarks and
Notes

r) Physical site inspection report


and safety measures taken for
adjoining buildings.
1. Right Side: PLOT # 87-B

2. Left Side: PLOT # 89-B OK

3. Front: 66’-0” WIDE ROAD

4. Rear: PLOT # 176-B

13
SECTION – 5
PROOF ENGINEER’S VETTING PROCEDURE

ARE ALL COMMENTS AND RECOMMENDATION


DESIGN SUMMARY OF COMMENTS
INCOPORATED IN FINAL DESIGN

REF.
Fulfilled all SBCA Structural
SECTION – 4
Requirements.  Yes
□ No, If No Explain (Brief Summary)

14
ARE ALL COMMENTS AND
PROOF
DRAWING RECOMMENDATION
TITLE OF DRAWING ENGINEER’S
NO. INCORPORATED IN FINAL
COMMENTS
SUBMISSION DESIGN

S.No DRAWING NO DRAWING TITLE

1 00 TITLE PAGE

2 S-01 LIST OF DRAWING

3 S-02 GENERAL NOTES

4 S-03 MISCELLANOUS DETAILS


FOUNDATION/COLUMN/RETAINING WALL LAYOUT PLAN & GROUND FLOOR
5 S-04
FRAMNG PLAN
GROUND FLOOR BEAM ELEVATION,PLINTH BEAM SECTION & FOOTING
6 S-05
SECTION
7 S-06 FIRST FLOOR FRAMING PLAN & 2ND TO 5Th FLOOR FRAMING PLAN

8 S-07 FIRST FLOOR BEAM ELEVATION

9 S-08 6TH FLOOR FRAMING PLAN & ROOF FRAMING PLAN

10 S-09 2ND TO 5TH, 6TH & ROOF FLOOR BEAM ELEVATION

11 S-10 MUMTY ROOF FRAMING PLAN & REINFORCEMENT DEAILS

12 S-11 MUMTY ROOF BEAM ELEVATION & OVER HEAD WTER TANK PLAN

13 S-12 LIFT, COLUMN & RETAINING WALL SECTION

14 S-13 STAIR SECTION

15
16
NAME OF PROJECT: MIDWAY COMMERCIAL

NAME OF ORIGINAL STRUCTURAL DESIGNER: ENGR. SULEHA KISHWAR

CERTIFICATE OF VETTING (PROOF CHECKING)

The Structural Design and Drawings have been Checked and Vetted by
me and hereby recommended for approval of Structural NOC.

_________________________________ _________________________
ORIGINAL STRUCTURE DESIGNER PROOF ENGINEER
Sign: _____________________ Sign:__________________
Name: ENGR. SULEHA KISHWAR Name: ENGR. M.KAMIL DEHLVI
SBCA Regd. No. SBCA Regd. No.
as Structural Engineer: SE-06-311 as Proof Engineer: VE-A/3
Date: Date:_____________

Seal: _____________________ Seal: ___________________

CERTIFICATE OF STABILITY FOR ADJOINING BUILDING

17
We undersigned hereby certify that, we have physically inspected the site the

plot situation is under:

PLOT # COMMERICAL BAHRIA TOWN KARACHI, PAKISTAN

1. Right Side: PLOT #

2. Left Side: PLOT # 89-B

3. Front: 66’-0” WIDE ROAD

4. Rear: PLOT-176-B

In existence of above explained position of the plot we undertake that there is no dangerous

for excavation of proposed building, all excavation to be done as per excavation plan.

Name of Structure Engineer: ENGR.

License No. SE-06-

Recommendation of Proof Engineer.

18