Professional Documents
Culture Documents
ACS 1000 Medium Voltage Drives: 315 - 5000 KW 400 - 6200 HP
ACS 1000 Medium Voltage Drives: 315 - 5000 KW 400 - 6200 HP
cn
www.PLCworld.cn
ABB
ACS 1000
Medium Voltage Drives
315 – 5000 kW
400 – 6200 hp
Commissioning Manual
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
ABB
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
ABB reserves all rights to this document, also in the event of patent issue
or registration of any other industrial property protection right. Misuse, in
particular duplication and forwarding to third parties, is not permitted. This
document has been checked with due care and attention. However,
should the user find any errors, these should be reported to ABB. ABB
aims to maintain the most modern standard, therefore, entries in this
manual may differ from the actual product.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
ABB
Table of Contents
Chapter 1 - Overview .........................................................................................................5
1.1. Safety................................................................................................................................ 5
1.2. Scope of Commissioning .................................................................................................. 5
1.3. Reports ............................................................................................................................. 6
1.4. Related Documents and Parameter References .............................................................. 6
1.5. Tools ................................................................................................................................. 6
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
Chapter 1 - Overview
The purpose of the manual is to assist in commissioning the ACS 1000
frequency converter. It includes necessary instructions, practical hints and
references to related documentation to successfully commission the
converter and the related equipment as needed for the application.
NOTICE!
Commissioning of the converter may only be carried out by personnel
who have been certified at “expert” or “master” level by the Product
Responsible Unit.
1.1. Safety
The safety instructions in this manual, in the User’s Manual and the local
safety regulations must be observed to maintain safety to all those
involved in commissioning the drive system.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
1.5. Tools
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
For an efficient commissioning, make sure that the following items are
completed before travelling to site:
• Needed tools 2
w
LC
.P
w
• Digital camera
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
completed
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
4. Converter Transformer
• Grounding is completed
www.91HMI.com www.PLCworld.cn
4. Motor
• Motor is installed, aligned and alignment protocol is available
• Grounding is completed
5. Megger Tests
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
6. Power
• Medium voltage is available for start-up of the converter
7. Miscellaneous
Sufficient number and correct type of spare parts are
•
available
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
3.1. MCB
Check that the main circuit breaker is installed properly according to the
local requirements and according to the instructions in the MCB
documentation. Pay special attention to the following:
• Ambient conditions,
www.91HMI.com www.PLCworld.cn
•
.c
The local control of the MCB must be inhibited; all external controls to
w
LC
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
following:
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
3.4. Converter
Check List
• Installation and damages of components.
• Cable openings should be closed to avoid dust entering into the
cabinets.
www.91HMI.com • Foreign parts, dust and moisture must not be present in the converter
www.PLCworld.cn
cabinets.
It is very important that there is no dust and moisture inside the
cabinets. Dust and moisture weaken the busbar insulation. Dust
tends to build up on air-cooling elements, thus impairing cooling.
• Converter doors must open and close easily.
n
.c
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
3.6. Motor
The motor frame must be connected to the ground network of the plant.
.c
ld
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
Chapter 4 - Safety
Before power is applied to the converter, it must be checked that all
covers are back in place so that voltage-carrying parts cannot be touched
accidentally. Interlocks, which prevent that medium and high voltage units
can be accessed accidentally, must be in operation.
• Protection covers inside the converter must be refitted.
If covers have to be removed for measuring purposes, appropriate
safety signs and temporary barriers must be installed and personnel
involved in the commissioning must be informed.
• Cabinet door locks must be checked.
The doors should be kept closed whenever possible. This also helps
to keep the cabinets clean.
Door keys should only be given to persons who take part in the
commissioning.
• All openings of the motor must be closed and shaft covers must be
installed.
The area around the motor must be cordoned off to prevent
accidents during the uncoupled motor tests.
www.91HMI.com • All covers of power cable terminals or terminal boxes in the
www.PLCworld.cn
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
11 Check that the output voltage of the EPS-board(s) are ok (27 VDC,
w
w
12 Check that both the yellow and green LED’s on all subprints on both
GUSP-units (Gate Unit power Supply) are on.
When the ACS 1000 is equipped with Phoenix auxiliary power supplies,
the supply can be arranged different ways. The exact configuration can
be checked from position 18 in the typecode.
A External 3-phase supply and external 1-phase safe line for control.
B External 3-phase supply and internal UPS.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
D Internal 3-phase supply and external 1-phase supply (no safe line) for
control and internal back-up battery.
E Internal 3-phase supply and internal 1-phase supply for control and
internal back-up battery.
F Only available for 575 VAC 3-phase supply.
IMPORTANT!
Configurations A and B are only available for 400 VAC / 480 VAC 3-
phase supply.
Configurations D and E are only available for ACS 1000i with 60Hz
supply network.
www.91HMI.com www.PLCworld.cn
Table 5-3 Settings for protection switches (control hardware supply)
1P- Auxiliary Supply 3P- Auxiliary Supply
Voltage [V] Voltage [V]
120 230 400 480
Q5052 (control) N.A. N.A. 1.6 1.4
Q5073 (aux. trans.) 1 0.5 0.3 / 0.85* 0.25 / 0.7*
n
.c
ld
Frame size
A1 A2 / A3
Supply Frequency (Hz) 50 Hz 60 Hz 50 Hz 60 Hz
Q5021 (fan 1) 4.25 4.25 7.30 6.87
400
Q5023 (fan 2) 4.25 4.25 7.30 6.87
Auxiliary Supply
Q5021 (fan 1) N.A. 3.54 N.A. 5.73
Voltage 480
[V] Q5023 (fan 2) N.A. 3.54 N.A. 5.73
Q5021 (fan 1) N.A. 2.95 N.A. 4.78
575
Q5023 (fan 2) N.A. 2.95 N.A. 4.78
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
supplied from customer side is within tolerance and write down the
w
LC
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
IMPORTANT!
During commissioning the Battery Select switch on the UPS modules
can be set to “Service”. In the service mode, the UPS module will not
keep the control hardware supplyed from the backup batteries and thus
rebooting of the converter is faster.
If it is more than 6 months from the dispatch of the converter from the
factory in Switzerland, check the charging of the auxiliary backup
www.91HMI.com www.PLCworld.cn
batteries and check the function of the auxiliary ride-through function. If
necessary replace the batteries with new ones.
IMPORTANT!
Auxiliary batteries are considered to be wear-and-tear-parts and cannot
n
be replaced as warranty.
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
CAUTION!
Do not switch on a cooling pump if the cooling circuit is empty. If a pump
runs dry, the pump seals will be immediately damaged.
NOTICE!
Especially the hoses on the sinus filter choke can easily be bent during
n
.c
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
In case the converter is equipped with redundant cooling fans, check the
function according to the instruction below.
1 Start pump number 1, fan number 1 (standard fan inside cabinet)
www.91HMI.com www.PLCworld.cn
starts rotating, the air-flaps under the redundant fan should be closed
and the air flaps under the internal fan should open.
2 Feel the air flow (how strong does the fan blow).
3 Switch off the motor circuit breaker of the standard fan, the redundant
fan starts rotating, the air flaps under the redundant fan should open
and the air flaps under the internal fan should close.
n
.c
ld
4 Feel the air flow of redundant fan, it should blow as strong as fan
or
w
number 1.
LC
.P
5 In case the air flow is much weaker you have to change the direction
w
w
• Check that the air exhaust box on top of the converter is assembled
according to the instructions (ACS 1000i: N.A.).
• Check that all applicable fans installed on top of the converter are
installed (only ACS 1000i).
• Check that the fan(s) are rotating smoothly and in the right direction.
• In case of redundant fans check that the installation of the fan box is
made according to the instructions.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
• In case of redundant fans check that the air flap limiting device is
functioning properly.
• Check and test the function of the installed differential pressure
switches (see Table 6-1 and Table 6-2).
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
7.1. Preparations
• Make sure that the Main Circuit Breaker is locked in test position
(ACS 1000i: make sure that the external supply breaker is locked in
www.91HMI.com test position).
www.PLCworld.cn
isolate them from ground and the frames of the converter and the
or
motor.
w
LC
.P
w
w
w
The main circuit breaker is commissioned and the insulation tests are
performed according to the documentation of the manufacturer. The
signed MCB commissioning report must be received from the responsible
person.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
All poles should be meggered against each other and against ground.
The absolute value depends on other equipment connected to the
breaker but it should be higher than 1 MΩ per 1 kV.
7.4. Transformer
www.91HMI.com HV
www.PLCworld.cn
+ -
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
50 7.85
or
w
55 11.20
LC
60 15.85
.P
w
65 22.40
w
w
70 31.75
75 44.70
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
1 Connect all medium voltage input and output connections 1U1, 1V1,
1W1, 2U1, 2V1, 2W1, U2, V2, W2 (and 3U1, 3V1, 3W1, 4U1, 4V1
and 4W1 in case of a 24-pulse rectifier) together.
2 Connect the DC-capacitor terminals Plus, Minus and NP together
(the easiest place is the terminals on the grounding switch).
3 Remove the DC-voltage measurement cables from the ADCVI- and
OVVP-boards (terminals X2.1, X2.3 and X2.5) and make sure that
the wires don’t touch the frame or the boards.
4 Remove the door center post in front of the inverter swing frame (only
in water-cooled converters, see Figure 7-3).
5 Remove the ground-connection of resistor RN.
6 Remove the ground-connection of the star point of the output filter
capacitors Cf.
7 Close the doors to the medium voltage cabinets of the converter.
8 Open the grounding switch.
9 Switch off the auxiliary voltage of the converter.
10 Connect the megger between the main connections (1U1, 1V1, 1W1,
2U1, 2V1, 2W1, U2, V2, W2) and ground.
11 Megger the converter main circuit against ground.
www.91HMI.com www.PLCworld.cn
The test voltage should be 5000 VDC for 60 seconds. The measured
insulation resistance must be higher than 10 Mohm in a water-cooled
ACS 1000 and higher than 100 Mohm in an air-cooled ACS1000. In
the water-cooled ACS 1000, the result is depending on the actual
water conductivity of internal cooling water, if the conductivity is
below 0,3 uS it is normally possible to get an acceptable result.
n
.c
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
CAUTION!
Serious damage can be caused on the converter in case it is energized
without removing all short-circuit-jumpers.
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
w
w
w
.P
LC
w
or
ld
.c
32/64
n
www.91HMI.com
www.PLCworld.cn
5 KV / 60
seconds
Fs1
Rpre1
Ls1
Chapter 7 - Insulation Resistance Measurements
Rdis1
Cr1 V2u V2v V2w
V2a V2b V2c Cdc1 Ccl1
www.PLCworld.cn
Lf
V1Nu V1Nv V1Nw
Rsym
Fm
Ls2
Rpre2
Fs2
Disconnect:
1. The star point of the output filter
Open the grounding switch 2. The ground connection on resistor Rn
ABB
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
1 Connect the medium voltage input and output connections U1, V1,
W1, U2, V2 and W2 together (in the cable cabinet on the left side of
the converter).
2 Close the MCB by jumpers (if applicable).
3 Short circuit all four 6-pulse rectifiers (AC and DC terminals) and
connect them to the input and output connectors.
4 Connect the auxiliary windings of all transformers together and
ground them.
5 Remove the ground-connection of resistor RN (input section).
6 Remove the ground-connection from the star point of the output filter
capacitors Cf (input section).
7 Disconnect the surge arrestors from ground.
8 Remove the DC-voltage measurement cables from the ADCVI-,
OVVP1- and OVVP2-boards (terminals X2.1, X2.3 and X2.5) and
make sure that the wires don’t touch the frame of the converter or the
board.
9 Open the grounding switch (manual unlocking).
10 Close the doors of the converter.
11 Switch off the auxiliary voltage of the converter.
www.91HMI.com www.PLCworld.cn
12 Connect the megger between the main connections (1U, 1V, 1W, U2,
V2, W2) and the ground.
13 Megger the converter main circuit against ground.
The test voltage should be 5000 VDC for 60 seconds. The measured
insulation resistance must be higher than 100 Mohm.
n
.c
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
7.7. Motor
1 The frame and the windings not being tested must be grounded
during the insulation resistance measurement.
2 All resistance temperature detectors (RTD) must be grounded.
The insulation resistance of new motor is normally very high. A thumb
rule can be that if the measured value is one decade or more lower than
the value measured in the factory, check the winding for excess moisture
or dirt. The test report contains the insulation resistance value measured
in the factory.
If the motor star point is reachable, measure each phase separately as
shown in Figure 7-6.
If the star point is not reachable, measure all phases together as shown in
Figure 7-7.
n
.c
ld
or
w
LC
.P
w
w
M
w
If the reading is too low, dry the motor windings according to instructions
in the motor documentation.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
Measure the insulation resistance of all power cables and write down the
measured results. Measurements have to be made between all phases
(all cables apart from each other) and between all cables and ground (all
cables bound together at one end). Record the lowest value for each
measurement.
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
8.2. Transformer
LC
.P
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
IMPORTANT!
The protectice devices from the supply transformer can be connected
either to the ACS 1000 or to some other protection device. If they are
not conncted to the ACS 1000, it is recommended to connect one
common “Transformer trip signal” to the ACS 1000 tripping loop,
connectors X300:7 and X300:8.
8.3. Converter
The following things must be checked before the ACS 1000 can be
energized.
• Visually all medium voltage connections (busbars and cables).
www.91HMI.com www.PLCworld.cn
• Visually all auxiliary supply cables.
• Visually all fibre optic cables.
• In case of water cooled ACS 1000, the centre post in font of the
inverter must be installed (see Figure 7-3).
• In case of a water-cooled ACS 1000, the shipping brackets securing
n
.c
•
w
•
w
The DIP-switches for configuring the analogue inputs are correct set
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
AI 20mA
AI 10V
ON
OFF
AI 20mA
AI 10V
ON
OFF
AI 10V
OFF OFF
n
.c
ld
•
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
• Check the supply voltage for the motor space heater and write down
the value.
• Check the supply voltage for converter space heaters and write down
the value.
• Check the function of all included options (motor space heater,
converter space heater, motor cooling fan / pump etc.).
Set all customer specific parameters. For more information see the Signal
and Parameter table.
•
.c
with the name plate data of the motor (see Figure 8-5) or with the
w
LC
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
IMPORTANT!
The sine filter damping parameters in group 112 (older software
versions) or group 115 (newer software versions) must not be modified,
they are automatically set to the correct values by the software loading
package.
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
Figure 8-5 Example of motor parameter calculation with the name plate
data
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
Check the function of the MCB and the tripping loop without main voltage.
For more information see the following application notes:
• ACS 1000 Main Circuit Breaker Control
• ACS 1000 Tripping Loop
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
IMPORTANT!
If the MCB Available-function is enabled, it is only possible to operate
the grounding-switch when the MCB is in test-position i.e. when the
MCB Not Available-alarm is active.
8 Close the MCB with the On-Line-pushbutton on the front door of the
.c
ld
converter, the breaker should close and the drive should receive the
or
w
MCB Closed-status-signal.
LC
.P
type), the MCB should be opened by the converter and the fault-
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
13 Wait for about 5 seconds and open the MCB with the Off-Line-
pushbutton on the front-door of the converter, the breaker should
open and the drive should go to RdyForMCBOn-state.
14 Test all used trip-signals connected to the tripping-loop and make
sure that the converter shows the correct fault for each signal.
15 Set the converter to Remote control and test the remote control of the
MCB.
16 Check the mechanical interlocking of the grounding isolator.
IMPORTANT!
If the Fieldbus is only used for monitoring, parameter 75.04 FBA
www.91HMI.com Comm.Module www.PLCworld.cn
must be set to DSET1 READ.
If parameter 75.04 FBA Comm.Module is set to DSET1 R/W, the bits 2
and 3 in the OCW (Overriding Control Word) must be set to 1 to prevent
the drive to trip to the fault “EmergStop” when the drive is in remote
mode.
n
.c
ld
8.4. Motor
or
w
LC
.P
cooling etc.) and make sure that starting the motor does not cause any
w
danger. It is recommended to disconnect the motor from the load for the
first start if there is a risk that the load is damaged in case the motor turns
in the wrong direction.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
IMPORTANT!
ACS 1000i, with 50 Hz transformer have no tap changers.
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
IMPORTANT!
The DC link voltage corresponds to the maximum rated output voltage
(peak voltage), for example for a 3.3 KV drive:
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
NOTICE!
In software-versions before MSOH4300, the ACS 1000 automatically
asks for an ID Run, by showing the warning “ID RunReqst” when the
MCB is closed for the first time.
To disable the ID Run (as recommended) set parameter 112.20 Manual
First Start to ‘YES’, the ID RunReqst-alarm is deactivated and the ACS
1000 should show the status “Rdy To Strt”.
3 Start the motor from the CDP-panel and make sure that the motor is
running in the correct direction.
4 Check that the converter works ok in the whole speed-range from
both local and remote control.
5 In case needed, tune the speed-controller.
Error
www.91HMI.com www.PLCworld.cn
Step
height
A B C D E
n
.c
ld
or
w
LC
.P
Time
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
Check that the main power ride through, the auxiliary power ride through
and the auto restart-functions work properly in case they are required.
Monitor the following parameters during the ride through and the auto
restart tests:
• 1.02 MotorSpeed,
• 2.07 DC Voltage Udc1+2,
n
.c
ld
b02),
w
w
w
The converter’s ability to cope with main power supply breaks depends
mainly on the application. In case of a high inertia application (for
example a fan), the converter should be able to cope with quite long
power dips whilst in case of a low inertia application (for example a
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
Test procedure:
1 Enable the main power ride though function with parameter 39.01
RIDE THROUGH ENABLE and make sure that the ride though time
and minimum speed are set correctly with parameters 39.02 RIDE
THROUGH TIME and 39.03 RIDE THROUGH MIN SPEED (it is
usually not necessary to change the values of these parameters).
2 Close the MCB, start the motor and increase the motor speed to the
normal operation point.
3 Open an upper breaker for a short while to make sure the converter
can cope with the power break without tripping.
CAUTION!
Make sure that the backup batteries are charged properly before
performing the auxiliary ride through test.
n
.c
ld
or
w
Test procedure:
LC
.P
1 Enable the auxiliary power ride though function with parameter 39.04
w
w
AUX RIDE THROUGH ENABLE and make sure that the ride though
w
time is set correctly with parameters 39.05 AUX RIDE THROUGH (it
is usually not necessary to change the values of this parameters).
2 Close the MCB, start the motor and increase the motor speed to the
normal operation point.
3 Switch off the auxiliary power supply from a supply contactor for a
short while to make sure the converter can cope with the auxiliary
power break without tripping.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
Before leaving the site, the customer spare parts are to be checked
against the bill of material. If spare parts have not been ordered at all, the
commissioning report is to be marked accordingly.
Spare parts of the customer containing software (AMC and INT-board)
are to be updated with the software used in the converter and the
customer specific parameters are to be set.
If not agreed by contract otherwise, the subjects listed below can be used
as a guide when organizing on-site training. The training can be based on
chapter 6 - Operation in the User’s Manual of the converter.
• Safety instructions related to the operation of the converter
• Door interlocking system in conjunction with the grounding switch
www.91HMI.com •
www.PLCworld.cn
Control panel
• Overview of keypad modes
• Reading and interpreting status, alarm and fault
messages
• Control modes (local/remote)
n
.c
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
The parameters are saved in two steps and the parameters together with
the system software are saved in a third step.
Parameters
Only parameter groups, which are open in DriveWindow, can be saved.
Since the parameter groups above 99 are not open by default, they must
be opened first.
The parameter groups above 99 are opened and all open parameters are
saved in the “drive window parameter” file (“dwp” file) for use with
DriveWindow:
www.91HMI.com www.PLCworld.cn
5 Save the open parameter groups as “dwp” file (see Figure 10-1).
6 Enter pass code 358 into parameter 16.03 to lock the parameter
groups over 100.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
4 When the “Select Drives” dialog box is displayed, select the item from
which the backup is to be made.
n
.c
ld
or
w
LC
.P
w
w
w
5 Press “Backup”.
While the backup is executed the following dialog box is displayed.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
the “target” window ends with /u (with a blank before the slash). This
ld
or
Parameters
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
2 In the target list, select the drive from which parameters will be
uploaded or a software backup will be made.
www.91HMI.com www.PLCworld.cn
4 Press upload.
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
NOTICE!
This step can take up to 10 minutes.
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
After the test runs have been performed and the commissioning report
has been filled in completely, the representative of the customer is asked
to confirm the end of the commissioning with his / her signature on the
report. Date and signature on the report will indicate the beginning of the
warranty period to the factory.
•
ld
For revising and archiving of the factory documentation and for later
assistance of the customer send the following to the MV AC Supportline:
• Commissioning report
• Field report
• Parameter and software backup files (files with extensions “txt”,
“dwp”, “tar” and “pac”)
• Photographs of the installation (photographs only to be taken with
permission of the customer)
• Copy of modified mechanical and electrical drawings
www.91HMI.com
www.PLCworld.cn
www.PLCworld.cn
www.91HMI.com www.PLCworld.cn
n
.c
ld
or
w
LC
.P
w
w
w
www.91HMI.com