We can divide alternator faults in two type -Internal fault, External fault. There is internal Fault like 1.Stator Winding Fault (most severe),
2.Excitation circuit fault or failure of rotor field, 3.Unbalanced loading. On the other hand, there is external fault like 3.Failure of prime Mover,
4.Over current, 5.Over / under Voltage, 6.Over Speed; 7.over / under frequency.8. Loss of synchronism or pulling out of step . 9.Over or under
frequency fault of alternator(newly added).
The effect of prime mover failure in an alternator– we can imagine the situation, an alternator is coupled with prime mover running, and it
is directly connected to the grid or some parallel electrical bus supplying power. When the prime mover fails, it is still connected to the live
electric bus. Then the alternator fails to supply power but starts receiving power from live electric bus. This time the synchronous alternator
takes power acts as an synchronous motor and run the engines or turbine in uncontrolled high speed. This is called reverse power.
Lenovo™ Laptop
Lenovo India
Severity of reverse power: For gas turbine and any hydroelectric system the turbine installed is capable of running in very high speeds, so
when high speed occurs due to reverse power, any technician can decouple the circuit breaker. But for diesel / engine system, the reverse
power is so dangerous, as the over speed limit of engines re nominal like 120% of rated speed. As example our plant’s Wartsila engines rated
speed was 750 RPM, and its high speed limit was 840/880 RPM.
Remedy -A reverse power relay is recommended.But this relay should have time delay to avoid false trip in case of short time system
disturbance,phase swinging and fluctuation in synchronization.Thus when a reverse power problem occurs, the first thing is to decouple the
corresponding circuit breaker to disconnect the alternator from live line. If it is stuck, then shut down the whole bus, if that too is not possible
then shut the whole power plant for engine based power plant only.
https://eblogbd.com/faults-in-an-alternator/ 1/8
7/26/2021 Major faults in an alternator and their protection. - Electrical Blog
False tripping on an alternator by over current protection relay is need to be considered as this might disconnect alternator from bus for
some fault out side of plant.This will cause interruption of continuous operation, so over current relay used must have time delay.
However, if somehow alternator suddenly disconnected from the load, its speed exceeds rated speed, over voltage might occur. So an over
voltage relay is recommenced to install where alternator rpm is not closely supervised.
To sense and protect the unbalanced loading a simple conception is used that the three phase current is equal in magnitude but 120
degree separate by phase angle. So when we vectorically sum up three phase current- the result is zero. Thus we can apply some simple
instrument transformer to watch out the summation of three phase to zero, if by some means there is some value other than zero that is not
in the range of tolerable, then this circuit can send a trip signal.
The below circuit follow the above conception. See the secondaries of three CT’s are shorted, so the sum of normal phase currents is zero, no
current in the trip coil. By some instance if there is some unbalanced, then there will be some current in the secondary, that will eventually
sen trip signal.
https://eblogbd.com/faults-in-an-alternator/ 2/8
7/26/2021 Major faults in an alternator and their protection. - Electrical Blog
This specific protection is for alternators with multiple coils turns like in double phase winding used in large steam turbine alternators. The
concept is that this protection scheme covers the stator coil inter turn to turn short circuit, not coil to coil(phase to phase) or coil to
ground(phase to ground). Its like a local fault in one of the coil.
The protection scheme to cover stator inter turn fault is simply on the basis of the theory of differential theory. In normal condition, the two
coil or multi coils individually carry same magnitude of current but with a phase displacement. If this current is summed up in a common
circuit then the result will be zero. So we can just place some CT’s with their secondaries shorted and primaries with individual coils. If some
fault persists, then there will be current in the secondaries which will energize the trip circuit.
To understand this fault we can have some brief theory. As in all electrical rotating machine, the common working
principle is that there is some disalignment generated between two flux- rotor flux & stator flux. Thus a force is
exerted to straighten this dis alignment-which is harnessed as working force.
https://eblogbd.com/faults-in-an-alternator/ 3/8
7/26/2021 Major faults in an alternator and their protection. - Electrical Blog
As the prime-mover torque is increased, the magnitude of Drf must increase until the electromechanical torque balances the shaft torque.
The readjustment process is actually a dynamic one, requiting a change in the mechanical speed of the rotor.
As can be seen from Fig, an increase in prime-mover torque will result in a corresponding increase in the torque angle. When Drf becomes
90 °, the electromechanical torque reaches its maximum value, known as the pull-out torque. Any further increase in prime-mover torque
cannot be balanced by a corresponding increase in synchronous electromechanical torque, with the result that synchronism will no longer
be maintained and the rotor will speed up. This phenomenon is known as loss of synchronism or pulling out of step.
As remedy– Under these conditions, the generator is usually disconnected from the external electrical system by the automatic operation of
circuit breakers, and the prime mover is quickly shut down to prevent dangerous over speed. The value of the pull-out torque can be
increased by increasing either the field current or the resultant air-gap flux. However, this cannot be done without limit; the field current is
limited by the ability to cool the field winding, and the air-gap flux is limited by saturation of the machine iron.
08. Over frequency & Under frequency fault and protection for alternator
The frequency has a constant stable value, defined by the equation (Ns=120f/p). But frequency varies causing over and under frequency fault.
Over or under frequency has its own severe effect on both the load side and generating equipment side, We are talking here about the
generating set – alternator. The first thing we like to know why the over or under frequency occurs.
The frequency variation created by the load demand(excess or less then generation). Say when a generating station producing power
that equals the net consumption plus the loss, then the system will be stable. But when the load demand is higher then production, that is
production is low then use/demand then frequency will be low, on the other hand when the load demand is less then production or
production is excess then frequency will be higher.
We can summarize over & under frequency in a mathematical concept to understand and memorize as below-
The remedy or protection of over and under protection is simple. When under frequency occurs that is more power consumer then the
covering capacity, then the only solution is to effect load shedding or increase the power generation. For over frequency the only solution is
to lower the power generation. A relay can be used to automatically control the loading, unloading of generator or effect the load shedding.
https://eblogbd.com/faults-in-an-alternator/ 4/8
7/26/2021 Major faults in an alternator and their protection. - Electrical Blog
Lenovo™ Laptop
Lenovo India
Share this:
Twitter Facebook
Further reading
Differential protection or Merz-Price Major faults and protection in transformer. Complete Basics of Alternator or Generator
circulating current protection system of Common faults in transformer- Open Circuit The generator or alternator is basically a
alternator. fault, Over heating., Winding short circuit or machine that converts mechanical energy to
Differential protection of alternator or Merz- earth fault. Though the Buchholz relay covers electrical energy. Mechanical energy is
Price circulating current protection system is a most of the fault but additional protection produced from the prime movers. Prime
only protection system that protects also must include in transformer protection Movers would be an engine, a turbine or hydro
alternator stator from burning through at
least 80% of it.
Related Posts
https://eblogbd.com/faults-in-an-alternator/ 5/8
7/26/2021 Major faults in an alternator and their protection. - Electrical Blog
HADY
OCTOBER 16, 2014 AT 3:24 AM
If I set up my wind turbine with AC can I then hook that up to a very heavy duty wire which I thing is 6 gauge and run it about 400 it
start out by my barn and then about 400 to my house I was thiinkng of doing it that way because I didnt want my inverters and stuff to
be out in cold barn or do you think a grid tie inverter would be ok in a barn in below zero temps???????which way is better?????
Recent Post
Two reasons why power quality is a trending topics in modern electrical system
Why Low Power Factor is Harmful for Electrical System: Stated With Basic Calculation
Why and how: Reactive Power symbol is small letter and all other electrical symbol is small letter
What is the disadvantage of low power factor?
What is power factor correction in electrical system?
Is there any needs of reactive power in electrical system?
https://eblogbd.com/faults-in-an-alternator/ 6/8