Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

DeLoach

Industries, Inc.
818 Cattlemen Rd, Sarasota, FL 34232
Phone: 941-371-4995 Email: TonyD@DeLoachIndustries.com

GENERAL SPECIFICATIONS FOR A DUAL STAGE ODOR CONTROL


SCRUBBER
MODEL#
1.0 SCOPE

This section covers the odor control system to be furnished and installed as indicated within the
following specifications including the packed tower scrubbers, pumps, fan, motor, drives,
interconnecting piping, dampers, controls, and accessories required for a complete and properly
operating system. The odor control system shall consist of a Dual-stage single pass packed tower
scrubber system as manufactured by DeLoach Industries, Inc., (DI) Sarasota, FL or WES Industries
Inc. (WES) Sarasota, FL.

All items of the odor control system shall be provided by a single supplier who shall be responsible
for the design, manufacturing, delivery, coordination, and function of the systems. The odor
control manufacturer will be responsible for final sizing and selection of all major components.
The manufacturer shall select live load rates for final foundation design and sizing.

1.1 Manufacturer’s Qualifications

The odor control system shall be manufactured by a single source fabricator specializing in the
manufacturing of fiberglass reinforced plastic (FRP) scrubbers and towers and shall produce at a
minimum from the factory, the FRP vessel, distribution header, interconnecting ductwork,
demister housing, anchor cleats, recirculation sump, media support plate, air exhaust system, and
control panel. A minimum of 90 percent of all components shall be manufactured in-house by the
supplier. The manufacturer shall be an UL certified control panel fabricator and will develop the
proper logic sequence. The engineer may inspect the facilities to verify that all major components
are being fabricated in accordance to the specification and by a single source manufacturer. The
supplier of the odor control system shall own and operate the manufacturing plant that is providing
all major components and controls as stipulated.

1.2 Process Type

The odor control system shall be a Dual-stage dual pass type system utilizing sodium hydroxide
and sodium hyper chlorite solution as the scrubbing agent.

2.0 GENERAL

Odor Control E_Book Word 3 Page 1 02/99


Equipment provided under this section shall be fabricated, assembled, erected, and placed in
proper operating condition in full conformity with drawings, specifications, engineering data,
instructions, and recommendations of the equipment manufacturer unless exceptions are noted by
the Owner/Engineer.

The system shall be furnished and installed complete with all mechanical and electrical equipment
required for proper operation, all components indicated on the drawings or specified, and any
additional materials or construction required by the manufacturer's design.
Equipment shall be designed for long life under working conditions specified herein, including
corrosive atmospheres and intermittent or continuous operation. All wearing parts and items
requiring adjustment shall be readily accessible. All parts which are exposed to corrosive
conditions shall be made from corrosion-resistant materials.

2.1 Coordination

The odor control system supplier shall insure that each system component is compatible with all
other components of the system; that all pipe, fans, dampers, valves, motor sizes, and materials are
appropriate; and that all devices necessary for a properly functioning system have been provided.

2.2 General Equipment Stipulations

The General Equipment Stipulations shall apply to all equipment furnished under this section.

2.3 Electrical Equipment

All electrical equipment shall conform to applicable standards of the National Electrical
Manufacturers Association and the National Electrical Code. Both power and control equipment
shall be insulated for not less than 600 volts even though operating voltages may be lower.

2.4 Anchor Bolts

All anchor bolts, nuts, and washers shall be AISI Type 316 stainless steel and shall comply with
the requirements of the anchor bolts and expansion anchors section.

2.5 Equipment Identification

All equipment, scrubbers, pumps, fans, piping, valves, and control equipment denoted by a symbol
and an identifying number shall be provided with equipment identification plastic nameplates,
plastic tags, metal nameplates, or metal tags. Mechanical identification used shall be the same as
the symbols indicated herein or on the drawings and shall be located in a conspicuous place.

2.6 Manufacturer's Nameplate

Each major component of equipment shall have the manufacturer's name, address, and catalog
number on a nameplate securely affixed. The nameplate of the distributing agent only will not be
acceptable.

2.7 Piping

Odor Control E_Book Word 3 Page 2 02/99


Piping identification shall conform to the requirements of the operator's manual which shall be
furnished by the odor control manufacturer.

2.8 Spare Parts

One of each size and type of flexible connection shall be furnished.

3.0 QUALITY ASSURANCE

3.1 Qualifications

The scrubber manufacturer shall be established as a designer and fabricator of odor control
components and systems; be able to demonstrate experience on systems with water treatment
exhausts; and have the resources, experience, and capabilities to provide a full line of maintenance
spare parts for the system under a service contract with the Owner.

4.0 SERVICE CONDITIONS

4.1 Environmental Requirements

The odor control equipment will be installed outdoors with expected temperature range from
°F minimum to °F maximum.

4.2 Elevation

The Contractor shall verify the elevation of the scrubber and shall take the necessary steps required
to assure proper alignment and scrubber performance.

4.3 Power Supply

Power supply to equipment will be 480 volts, 60 Hz, 3-phase. Power supply to the controls will
be 120 volts, 60 Hz, single-phase.

5.0 CONTROLS

The control systems shall be furnished and installed by the supplier of the odor control system and
shall conform as specified herein. All controls shall consist of electric equipment.

5.1 Control Panels

The Contractor shall supply the Owner a complete design of the electrical requirements of the odor
control system for approval. Control panels shall be designed for outdoor wall mounting and shall
be completely prewired and checked. The control panel shall be FRP material and shall have an
epoxy white finish suitable for chemical exposure to hydrogen sulfide gas. The odor control
manufacturer shall be responsible for selecting the proper surface protection and shall supply the
control panel. The panel will be UL certified and built in an UL shop.

Control panels shall be NEMA Type 4X and shall conform to NEMA ICS 1, NEMA ICS 2, NEMA
ICS 3, and NFPA 70. The panels shall be mounted so that selector switches and indicating lights

Odor Control E_Book Word 3 Page 3 02/99


on the panel are located approximately 4 feet-6 inches above the finished floor. The control panels
will be supplied with 120 volt, 60 Hz, single-phase power. All electrical accessory devices and
internal electrical wiring shall be furnished and installed.

All controllers, selector relays, switching relays, interlock relays, manual switches, alarm and
indicating lights, and other devices shall be mounted in or on the respective control panel.

Accessories, such as indicating lights and selector switches, shall be mounted on the front hinged
covers of the panels. The accessories and panels shall be identified by engraved phenolic
nameplates with ¼-inch high letters. Nameplates shall be attached to the panel covers with
stainless steel pan head screws.

5.2 Selector Switches

Selector switches shall be heavy-duty, oil-tight type with gloved-hand or wing level operators.
Position legends shall be engraved on switch faceplate. Switches for electric circuits shall have
silver butting or sliding contacts, rated 10 amperes continuous at 120 volts AC. Contact
configuration shall be as indicted on the drawings or required for the application. Switches used
in electronic signal circuits shall have contacts suitable for that duty. Switches shall be Alan
Bradley, Square D, Cutler-Hammer "Type T", General Electric "CR", or acceptable equal.

5.3 Indicating Lights

Indicating lights shall be heavy-duty, push-to-test, oil-tight type, which utilize a low voltage lamp
and a built-in transformer. Legends shall be engraved on the lens or on a legend faceplate. Lamps
shall be easily replaceable from the front of the indicating light. Indicating lights shall be Alan
Bradley, Square D, Cutler-Harnmer "Type T", General Electric "CR", or acceptable equal.

5.4 Accessory Components

All additional control components, such as electric relays, controllers, and position switches, shall
be furnished as required to ensure a complete, properly operating installation. Accessory
components not mounted inside the control panel shall be furnished with equipment enclosures.

5.5 Electrical Wiring

Detailed wiring diagrams shall be submitted by the Contractor with the submittals. The wiring
diagrams shall show the internal connections of the control panels and all field wiring to equipment
remote from the control panels. The wiring diagrams shall be complete, showing all connections
necessary to place the control systems in operation.

5.6 Motor Starters

Motor starters shall be provided in motor control centers in accordance with the recommendations
of the odor control manufacturer. The motor control starters shall be either Alan Bradley or Square
D with a NEMA rating.

6.0 ACCESSORIES

Odor Control E_Book Word 3 Page 4 02/99


6.1 Differential Pressure Gauges

Differential pressure gauges shall be furnished for monitoring the pressure differential across each
fan, mist eliminator, and packed section of each scrubber. The gauges shall be permanently
mounted and shall be furnished with a mounting bracket, tubing, and all required fittings. The
gauges shall be installed to allow gravity drainage of condensate back through the sensing lines to
the pipe or vessel. Indicators mounted on towers shall be installed approximately 4 feet-6 inches
above the surrounding floor or concrete slab.

Each gauge shall be of the diaphragm-actuated dial type with adjustable pointer, white dial, and
black figures and markings. Each gauge shall have a range that under normal operating conditions
registers a reading approximately in the middle of the range. Accuracy shall be within 3 percent
of full scale. Two shutoff cocks shall be furnished with each gauge.

Gauges across packing sections and mist eliminators shall be furnished with a transparent red
overlay extending from the maximum allowable differential pressure reading, as indicated in the
Performance and Design Requirements Section for the packed tower scrubber.

Differential pressure gauges shall be Dwyer "Series 4000 Capsuhellic" with Viton diaphragm, or
equal.

6.2 Differential Pressure Switches

Differential pressure switches, denoted by the symbol "FS" and an identifying number, shall be
furnished and in indicated on the drawings.

Air flow switches shall be as manufactured by Dwyer Instrument, Inc. "Series 1800" or equal.
Switches shall be standard pipe thread, diaphragm operated by an air pressure differential across
the odor control fans, and rated 4 amperes at 120 volts AC. The air flow switches across the odor
control fans shall be initially set at 0.5 inches of water column. Switches shall be provided with
mounting brackets and weatherproof enclosures.

6.3 Flexible Connections

Flexible connections shall be as specified by the odor control manufacturer.

7.0 SEQUENCE OF OPERATION

The sequence of operation for the odor control system shall be as required to connect to the new
scrubber and allow for the future expansion of additional odor control scrubber towers should the
Owner elect.

8.0 INSTALLATION

Equipment and accessories shall be installed following the procedures recommended by the
equipment manufacturers and as required herein.

Odor Control E_Book Word 3 Page 5 02/99


Equipment shall be installed on individual concrete pads after the initial fitting and alignment, but
before the final bolting of connecting piping. No stress shall be transmitted to the equipment
flanges.

9.0 FIELD QUALITY CONTROL

9.1 Performance Test

The Contractor is responsible for the performance of the scrubber. Written documentation
indicating the proper operation of all fans, pumps, chemical feed systems, drains, valves and
control systems shall be provided in accordance with the scrubber manufacturer.

Personnel in charge of the tests shall be competent authorized representatives of the manufacturer,
who are familiar with the operation of the equipment furnished and who have previous experience
in conducting similar tests. Qualified personnel shall perform the tests, record the data, make the
required calculations, and prepare a report on the results. Copies of the reports shall be submitted
in accordance with the submittals section. The Engineer and Designer may observe the tests and
collect a copy of the recorded data. The information collected will be used as a basis for
determining acceptability of the manufacturer's results.

Testing shall be performed in a manner acceptable to the Owner. At least 4 weeks prior to the
proposed testing date, the Contractor shall inform the Owner of the testing date and shall submit,
for the Owner’s acceptance, a report from the coordinating supplier detailing the proposed
performance testing procedure and analyses. The proposed test procedure shall be accepted by the
Owner before testing may proceed.

The Contractor shall provide all necessary personnel, materials and equipment for the test,
including power, chemicals, test gas and testing apparatus for initial operation and testing. The
performance test shall be conducted using aqueous solutions of ammonium hydroxide. Sufficient
quantities of the chemical shall be prepared for the duration of the test.

Prior to the start of the test, the Contractor shall operate the systems until the adaptive controllers
have obtained stable control, and shall adjust the controller set points so that the recirculation
liquor pH is below the specified rate indicated by the scrubber manufacturer.

The Contractor shall monitor and record the air flow rate, hydrogen sulfide concentrations in the
scrubbers influent and effluent air streams, pH, scrubbing fluid recirculation rate, and quantity of
ammonium hydroxide. All instrumentation test equipment to measure hydrogen sulfide shall be
accurate to parts per million (PPM) of hydrogen sulfide.

Results of the performance tests shall be provided in accordance with the submittals section in a
written report. Each report shall include, as a minimum, legible photocopies of actual test data,
percentage of hydrogen sulfide removal achieved under actual test conditions, and the weight of
ammonium hydroxide consumed per unit weight of hydrogen sulfide removed.

Failure of the equipment to meet the specified performance and design requirements will
necessitate equipment modifications made by and at the expense of the Contractor. The costs of
additional testing and subsequent observation by the Engineer and Designer will be borne entirely
by the Contractor.

Odor Control E_Book Word 3 Page 6 02/99


The equipment manufacturer's representative shall be on-site a minimum of 1 day for initial
operation and 1 day for testing.

9.2 Startup Training

A competent authorized manufacturer's representative shall spend at least 1 day on-site devoted
exclusively to operations and maintenance training. This training shall be scheduled at the
convenience of the plant staff.

9.3 Applied Pipe Stress Test

After final alignment and bolting, all flanged connections shall be tested for applied piping stresses
by loosening the flange bolts. If any movement or opening of the joint is observed, piping shall
be adjusted to proper fit.

9.4 Installation Check

After the applied pipe stress test and prior to being placed in operation, each item of equipment
shall be inspected and checked by an experienced and competent technical representative of the
equipment manufacturer.

10.0 ADJUSTING, CLEANING, TESTING, AND BALANCING

10.1 Adjustments

The Contractor shall make all adjustments as directed by the equipment manufacturer and the
Engineer.

10.2 Cleaning

The inside of all pipe, specials, and fittings shall be smooth, clean, and free from blisters, sand, or
dirt when erected. All lines shall be thoroughly air purged before placing in service.

10.2.1 Fabricated Piping Assemblies

Fabricated piping assemblies shall be cleaned by hand or mechanical means to remove all loose
foreign materials, such as scale, sand, weld splatter particles, or cutting chips.

10.2.2. Installed Piping

All installed piping shall be cleaned by hand or flushing and free from debris and any loose foreign
materials, as may be introduced during field installation.

10.2.3 Odor Control Air Piping

Odor control air piping shall be purged clean using the system fans. The piping being cleaned
shall be purged continuously for not less than 48 hours at a flow rate not less than the design flow
rate for that piping section. If required, the system fans shall be throttled on the inlet side to prevent
motor overload. A temporary screen shall be installed in the fan suction piping to protect the fans

Odor Control E_Book Word 3 Page 7 02/99


from damage due to debris within the piping. Process equipment downstream of the fans shall be
disconnected during the cleaning procedure.

10.3 Testing and Balancing

The Contractor shall provide the services of a licensed independent Contractor, certified by NEBB
or AABC, who shall test and balance the odor control systems installed under these specifications.
The odor control systems shall be balanced at the same time as the HVAC systems which supply
air to the areas exhausted by the odor control systems. An operational check of all odor control
equipment and fans installed under this contract shall also be performed. The Owner reserves the
right to waive this test if deemed appropriate.

All air systems shall be balanced to within 10 percent of the air flow rates indicated on the
drawings. Final test readings shall be recorded and copies shall be submitted in accordance with
the submittals section for acceptance within one week after completion of the testing.

Following acceptance by the Owner, the position of each damper in throttling service shall be
permanently marked on the operator quadrant.

11.0 DRAWINGS AND DATA

Complete assembly, foundation, and installation drawings, together with detailed specifications
and data covering materials used, parts, devices, and other accessories forming a part of the
equipment furnished, and operation and maintenance manuals shall be submitted by the Contractor
after award for approval by the Owner before work commencement.

PACKED TOWER SCRUBBER

1.0 SCOPE

This section covers one vertical, countercurrent, packed tower scrubber, complete with
recirculation pump and accessories.

2.0 GENERAL

Equipment furnished and installed under this section shall be fabricated, assembled, erected, and
placed in proper operating condition in conformity with drawings, specifications, engineering data,
instructions, and recommendations of the equipment manufacturer, unless exceptions are noted by
the Owner.

The packed tower scrubber shall be as manufactured by DeLoach Industries, Inc. (DI) Sarasota, FL
or Water Equipment Services, Inc. (WES) Sarasota, FL. The products of other manufacturers will
not be acceptable. The packed tower scrubber must be from a single source manufacturer.

2.1 Manufacturer

Equipment furnished under this section shall be from one (1) single source supplier. All
components, pumps, ductwork, and controls shall be supplied by the odor control manufacturer
only.

Odor Control E_Book Word 3 Page 8 02/99


2.2 General Equipment Stipulations

The General Equipment Stipulations shall apply to all equipment furnished under this section.

2.3 Anchor Bolts

All anchor bolts, nuts, and washers shall be AISI Type 316 stainless steel and shall comply with
the requirements of the anchor bolts and expansion anchors section.

2.4 Spare Parts

The following spare parts shall be furnished:

Item Quantity
Mechanical seals for recirculation pump 1 seal for each pump
Chemical feed pump 1 sensor (pH)

2.5 Power Supply

Power supply to equipment will be 480 volts, 60 Hz, 3-phase. Power supply for controls will be
120 volts, 60 Hz, single-phase.

3.0 SERVICE CONDITIONS

Service conditions shall be as specified in the odor control systems section.

4.0 PERFORMANCE AND DESIGN REQUIREMENTS

The scrubber and recirculation pump shall be provided to operate at the following conditions. The
packed tower scrubber and chemical feed system shall be sized to operate at the ultimate
conditions. The odor control system’s performance test shall be conducted on the tower at the
following initial conditions.

Unit Designations Odor Control Scrubber No. Odor Control Scrubber


1 No. 2
Design gas flow, CFM
Initial Design
Maximum
Inlet gas temperature, minimum ºF
Inlet gas temperature, maximum ºF
Inlet gas hydrogen sulfide
concentration, load rate per day
Max. scrubber height, without stack
Minimum scrubber diameter
Type of FRP vessel Exterior molded, hand lay- Exterior molded, hand lay-
up with exterior molded up with exterior molded
gelcoat finish only gelcoat finish only
Minimum FRP wall thickness 1/4" 1/4"

Odor Control E_Book Word 3 Page 9 02/99


Unit Designations Odor Control Scrubber No. Odor Control Scrubber
1 No. 2
Minimum packing depth
Maximum pressure loss at ultimate
design air flow rate, inches water
column
Scrubber, total
Packing
Mist eliminator Munters T-271. No equal. Munters T-271. No equal.
Minimum hydrogen sulfide removal 99% 99%
efficiency percent
Wind load, mph 120 mph 120 mph
Design operating pressure inches
water column
Scrubber recirculation pumps
Unit designations
Rated total head, feet, H2O
Minimum motor size, hp
Minimum capacity at rated head,
GPM

Maximum pump speed, rpm

Pump manufacturer Ingersoll-Dresser or equal Ingersoll-Dresser or equal

The scrubber shall be designed to achieve the required minimum hydrogen sulfide removal
efficiency under the initial operating conditions set forth herein, using the specified scrubbing
solution.

All items of equipment in contact with the scrubbing solution shall be suitable for continuous
operation at temperatures up to °F, using a solution of ___________ to maintain the
proper pH. The scrubbers shall also be suitable for periodic cleaning with a hydrochloric acid
solution.

The structural design of each scrubber vessel shall be adequate for the wind load and design
operating pressure and vacuum conditions specified.

5.0 PACKED TOWER SCRUBBERS

5.1 Construction

The scrubber shall be constructed of fiberglass reinforced exterior molded plastic in accordance
with ASTM D3299 or ASTM D4097. All fiberglass reinforced plastic (FRP) fabrications shall
have a flame spread of 25 or less when tested in accordance with ASTM E84. The resin used shall
be limited to a Bisphenol-A polyester or Hetron Resin suitable for contact with the specified
scrubbing solution and shall contain ultraviolet inhibitors.

The scrubber shall consist of one exterior molded FRP tower. The tower shall be flanged and shall
have lifting lugs. The tower shall have at a minimum wall connections and accessories as indicated

Odor Control E_Book Word 3 Page 10 02/99


below and on the specifications. The vessel wall shall be a minimum of 1/4" thick and will be a
hand lay-up process for controlled thickness. The vessel shell will be as manufactured by DI or
WES.

The top section shall include a flanged circular air outlet connection, access doors, a treated air
sample tap, and a mist eliminator. At least two access doors shall be provided for inspection and
maintenance of the spray nozzle. An access door shall also be located above the mist eliminator.
The top shall be reinforced to support the air discharge piping.

The scrubber tower shall include the packing, one or more spray nozzles, scrubbing solution
recirculation line connection and distribution piping, media support plate, access ports arranged
vertically with transparent covers for inspection of the packing, and any other piping connections
or components which are required by the manufacturer's design. The vessel wall shall have an
exterior molded FRP support ring every 3 feet on center for structural integrity. The support rings
shall be molded in place with a smooth exterior finish. One access port shall be located above the
support plate near the bottom of the packing and shall be suitably sized to permit removal of
packing material.

The bottom section of the scrubber shall include a transition air inlet connection, access port,
recirculating pump suction connection, integral recycle tank, makeup water connection, recycle
tank drain connection, overflow connection, acid wash connection, external level control stilling
well, sample taps, hold-down lugs, access door, and all other connections or components required
for proper operation or by the manufacturer's design. The bottom of the scrubbers shall be elevated
as required to provide a positive suction head for the recirculation pumps. If required, anti-
vortexing devices shall be provided internally at the pump suction connections.

An external caged ladder with landing platform shall be provided as required to allow access to
the top service hatch. The external ladder shall be supported on and anchored to the concrete base
and bracketed to the tank shell as required. The ladder shall include safety handrails around the
top of the landing platform as required. The ladder shall be fabricated of Type 316 stainless steel
or FRP. No uncoated or exposed carbon steel parts or fastenings will be permitted. The ladder
shall have a clear width of at least 16 inches, shall have rungs at least ¾-inch in diameter and
spaced not more than 12 inches apart, and shall have a minimum clearance of at least 7 inches
between the back of the ladder and the tank wall. The ladder and landing platform shall be
constructed in conformance with OSHA Standard 1910.27.

A pH sensor housing shall be constructed to allow removal of the sensor with the scrubber in
service, without venting untreated gas or loss of scrubbing solution. The recycle tank shall have a
minimum liquid depth of 30-inches or 2 minutes retention of recirculation flow, whichever is
greater.

The support for the packing material shall consist of an FRP plate with proper FRP I beams as
designed by the odor control fabricator. Recirculation pipe supports shall be provided on the
scrubber tower. No PVC supports will be allowed, and all structural supports must have
engineering structural calculations to support media weight at full flood conditions.

5.2 Packing

Odor Control E_Book Word 3 Page 11 02/99


The packing shall be manufactured from low weight, low resistance polypropylene; shall have a
minimum surface area of 36 square feet per cubic foot; shall have a minimum void fraction of 92
percent. The packing shall be Mas-Pac, Lan Pac, or Q Pac, no other packing shall be allowed.
The configuration shall be as required to maintain good liquid distribution through the packing
depth at the required efficiencies and pressure drops.

5.3 Media Support Plate

The packing support plate or grating shall be fabricated from fiberglass, and be designed to support the
weight of packing and liquid. To prevent structural failure under full load or fouled conditions, the use
of PVC or other plastic will not be allowed. The FRP scrubber shall be equipped with a FRP media
support plate as manufactured by DI or WES. The support plate shall be minimum ¼-inch FRP
material with 2-inch diameter holes on 3-inch centers. The media support plate shall be fiber glassed
on all perimeters to the interior of the vessel and shall be sealed with a NSF approved resin,
polyurethane or epoxy.

5.4 Distribution System

The inlet distribution system shall be a header lateral type distributor with a minimum
main pipe and diameter FRP laterals. The nozzles shall be Munters (D) type or equal with
a maximum of 10 psi back pressure for a minimum through rate of GPM. The minimum
free passage diameter shall be ¼-inch and shall be specifically designed to be clog-resistant. The
inlet shall be a minimum of diameter with a 150 pound Sch. 80 PVC flanged connection.
The distribution system shall be manufactured by DI or WES.

5.5 Mist Eliminator

One replaceable polypropylene mist eliminator shall be provided in the scrubber. The mist
eliminator shall have a minimum efficiency of percent and shall prevent carryover
of liquid droplets having a nominal size larger than 10 microns. The demister shall be
manufactured by Munters. The mist eliminator will be supplied by the scrubber manufacturer.

5.6 Piping Connections

Flanged piping connections shall conform to ANSI/ASME B16.5, Class 150 diameter and drilling.
Flanges on air inlet and discharge connections shall be furnished predrilled and shall match bolt
hole locations on connecting piping flanges. Flanges for air connections shall comply with PS-15,
Table 5, at a design pressure of 25 psi.

5.7 Access Hatches

Access doors shall be at least 24 inches in diameter and shall permit convenient access to all
interior components for inspection, removal, repair, or cleaning. All access hatches covers shall
be fully gasketed with Hypalon or Viton gaskets and shall be gastight under the positive internal
design operating pressure specified herein. Each access door shall be provided with a transparent
PVC or polycarbonate cover held in place by at least eight easily removable, AISI Type 316
stainless steel bolts. There shall be a minimum of two access hatches on the tower.

6.0 RECIRCULATION PUMPING UNITS

Odor Control E_Book Word 3 Page 12 02/99


Each recirculation pumping unit shall consist of a horizontal end suction centrifugal pump. The
pump shall be driven by an electric motor directly connected to the pump through a flexible
coupling. Each pump shall have a double mechanical seal and antifriction oil or grease lubricated
bearings and be suitable for chemical application. The type of pump shall be Duriron "Durco Mark
11 Series F", Gould’s "Model NM3196", PACO type KP, or Sta-Rite and shall be supplied by the
manufacturer. There shall be a minimum of two (2) pumps with a minimum flow rate of
GPM. The lubricating water connection from the reclaimed water system to each double
mechanical seal shall be equipped with a 25 micron, reusable ceramic filter. The pump casing
shall be of sufficient size to allow a 10 percent larger impeller to be installed.

6.1 Drive Motor

Each motor shall be totally enclosed, fan-cooled type with antifriction bearings and shall be the
premium high efficiency type.

6.2 Base

Each pump and drive motor shall be shop mounted on a common base. The base shall be of
corrosion resistant design with rounded corners. All exposed seams and contact surfaces of steel
plates and shapes shall be continuously welded and ground smooth. Openings shall be provided
in the top of the base to facilitate grouting. An opening shall also be provided, if necessary, for
electrical conduit to the drive unit.

6.3 Flexible Coupling

The pump couplings shall be of nonlubricated, resilient material, heavy-duty type, sized for
continuous operation at full load and at maximum rpm when the misalignment is within the
manufacturer's tolerance limit.

7.0 ACCESSORIES

7.1 Scrubber Recycle Tank Blowdown and Level Controls

The scrubber will be operated with a continuous blowdown. The rate of blowdown shall be
determined by the scrubber manufacturer and shall be controlled by a manual throttling valve in
the makeup water supply line. An overflow line equipped with an external seal pot shall maintain
a minimum freeboard of 10 inches, as measured from the maximum liquid level in the recycle tank
to the invert of the air inlet connection at the scrubber, while under design operating pressure.

The recycle tank shall be provided with level switches which shall stop the recirculation pump and
provide an alarm indication on the scrubber control panel as indicated in the sequence of
operations. Level switch contacts shall be single-pole, double-throw and shall be rated 10 amperes
at 120 volts AC. The recycle tank shall be located at the base of the scrubber.

7.2 Scrubber Recycle Tank Chemical Feed Monitoring and Control System

The scrubber shall be provided with a pH probe for analyzing the contents in the scrubber sump.
The probes shall be the flow-through type and shall meet the following specifications:

Odor Control E_Book Word 3 Page 13 02/99


pH Probe
Range
Stability
Temperature limits
Pressure rating
Wetted materials Corrosion-resistant material
Accuracy-sensitivity
Interconnecting cable Shielded, 5 wire, length as required

The pH probes shall be Great Lakes Instruments "Model 6050 PO", Signet, Fisher Porter, or equal.

Each probe shall be supplied with an analyzer/controller to be mounted on the scrubber control
panel door. Each analyzer/controller shall meet the following requirements:

Display Digital, LCD.


Range
Set point
Deadband
Outputs Two standard pipe thread contacts rated at 5 amperes each.
Power supply 120 volts, single-phase, 60 Hz.
Sensitivity .
Stability
Enclosure NEMA Type 4X, suitable for pipestand mounting.

The analyzer/controller shall be Great Lakes Instruments "Model 672P", Signet, Fisher Porter, or
equal. Probes and analyzer/controllers shall be by the same manufacturer and shall be furnished
by the manufacturer of the odor control scrubber as one complete unit.

The manufacturer shall provide all instrument cable for connecting each pH probe with its
controller. The manufacturer shall provide mounting kits for surface mounting each controller.

7.3 Flow Meters

Line-mounted bypass flow meters shall be calibrated in gallons per minute and shall have an
operating range of 200 percent of the operating flow of liquid having a specific gravity of 1.0. The
flow meters shall be accurate within 1 percent of full scale and shall be as manufactured by Signet,
Great Lakes Instruments, or equal.

Bypass fittings and piping shall be installed to connect the orifice plates and the rotameters. A
CPVC ball type shutoff valve shall be installed in the bypass piping upstream and downstream
from each rotameter. A range orifice shall be installed in the bypass piping immediately upstream
from each rotameter to limit the flow to that within the range of the rotameter. Rotameter mounting
height shall be 6 feet-6 inches maximum, and 3 feet minimum, above the floor.

7.4 Sight Glasses

Odor Control E_Book Word 3 Page 14 02/99


One clear PVC sight glass shall be provided for the scrubber. The sight glass shall be of sufficient
length to indicate the full range of liquid level within the recycle tank and shall be equipped with
isolation valves.

7.5 Flexible Connectors

Bellows type flexible connectors shall be furnished and installed on each pump suction and
discharge connection. Flexible connectors shall be suitable for a pressure of 125 psig. Flexible
connectors shall be Resistoflex "R6904" or equal.

7.6 Pressure Gauge

A pressure gauge complete with an all-plastic activator/isolator shall be provided for installation
in each pump discharge and suction piping. The gauges shall have a phenol case, adjustable
pointer, and stainless steel rotary geared movement, and shall be accurate to within 1 percent of
full scale. Each gauge shall have a dial size of at least 4-1/2 inches, with units of measurement
marked on the dial face, and shall be complete with isolation valve. Each gauge shall have such a
range that the normal operating reading shall be near the midpoint of the range.

One activator/isolator with PVC body and Hypalon diaphragm, rated for continuous operation at
psi and °F, shall be furnished with each gauge. The activator/isolators shall be as
manufactured by Vanton Pump and Equipment.

7.7 Level Switches

Level switches shall be as specified by the odor control scrubber manufacturer.

8.0 CHEMICAL FEED SYSTEM

The odor control manufacturer will supply the new chemical storage system, including the required
pipe, valve, and regulator equipment. The Contractor is responsible for final installation and
connection to the chemical feed line. The Contractor is responsible for final installation and for
furnishing all required pipes, valves, fittings, etc. The chemical feed system shall be as supplied
by DI or WES.

9.0 CONTROLS

Controls and control panels shall be as specified in the odor control system components section
and shall be the responsibility of the odor control manufacturer to interface with the existing
controls.

10.0 INSTALLATION

The scrubber, recirculation pumps, and accessories shall be installed in accordance with the
manufacturer's recommendations.

After final alignment and bolting, scrubber air inlet and liquid piping connections shall be tested
for applied piping stresses by loosening the flange bolts. No stresses shall be transmitted to the

Odor Control E_Book Word 3 Page 15 02/99


scrubber flanges. If any movement or opening of the joints is observed, piping shall be adjusted
to proper fit.

After the applied pipe stresses test and before being placed in operation, the unit will be inspected
by a representative of the equipment manufacturer.

Adjustments to scrubber, pump, or accessory items shall be made as directed by the representative
of the equipment manufacturer or the Engineer.

11.0 TESTING

Prior to shipment, the packed tower scrubber vessel shall be hydrostatically tested by filling the
vessel with water to the top of the air inlet nozzle. The water shall be held for at least 1 hour with
no visible signs of leaks or excessive wall deflection. The Engineer may be present at the
manufacturer’s facility during the testing and shall be notified at least 2 weeks prior to each test.

11.1 Field Tests

Field testing of the packed tower scrubber system is covered in the Odor Control System
Section.

12.0 DRAWINGS AND DATA

Complete assembly, foundation, and installation drawings, together with detailed specifications
and data covering materials used, parts, devices, and other accessories forming a part of the
equipment furnished, shall be submitted in accordance with the submittals section. The data shall
include, but not be limited to, the following:

Packed Tower Scrubber

Name of manufacturer
Type and model
Inside diameter
Overall height
Size and orientation of all connections
Packing manufacturer, type, pressure loss and material
Spray nozzle manufacturer, type, material, pressure loss and free passage diameter
Mist eliminator manufacturer, type, material, and efficiency
Net weight
Foundation bolting details
All material types, thickness, and finishes
Details of all control devices
Resin type and chemical resistance
Pressure loss through total unit at design air flow

Pumps

Name of manufacturer
Type and model

Odor Control E_Book Word 3 Page 16 02/99


Rotative speed
Size of suction and discharge connection
Complete performance curves showing capacity versus head
NPSH required, pump efficiency, and bhp
Type of coupling
Overall dimensions and total weight of complete pumping unit
Detailed base fabrication drawings

Motors

Name and manufacturer


Type and model
Bearing type and lubrication
Horsepower rating and service factor
Temperature rating
Full load rotative speed
Net weight
Efficiency and power factor at rated load
Full load current
Locked rotor current
Overall dimensions

Accessories

ORP probe
pH probe
Rotameters
Sight Glass
Flexible connectors
Pressure gauges
Level Switches

Odor Control E_Book Word 3 Page 17 02/99

You might also like