RC9RC5-10.01-150677-MTCO-A1001-0001-Rev.0-Data Sheet For UPS

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

RC9RC5 PROJECT

DOCUMENT TITLE DATA SHEET FOR UPS

TOTAL NO. OF PAGES


09
(INCLUDING FRONT SHEETS)

VENDOR'S ORDER NO. 150677-MTCO

VENDOR'S APPROVAL
VENDOR'S OWN DOCUMENT NO REV. NO DATE
(NAME AND SIGNATURE)
150677-MTCO-A1001-0001 A 13.05.2016 CHAU HUU TIN
0 03.06.2016 CHAU HUU TIN

Submitted For :

REVIEW APPROVAL RC9RC5 PROJECT


INFO FINAL DOCUMENTATION

REVIEW DOES NOT CONSTITUTE ACCEPTANCE OF


DESIGN DETAILS, CALCULATIONS, TEST METHODS OR VENDOR NAME : MTCORP
MATERIALS DEVELOPED OR SELECTED BY VENDOR NOR
DOES IT RELIEVE VENDOR FROM FULL COMPLIANCE
WITH CONTRACTUAL OR OTHER OBLIGATIONS.
PACKAGE
DESCRIPTION :
UPS System

1. ACCEPTED

2. ACCEPTED, PROCEED WITH TAG NOS. : MODEL TYPE NOS. :


WORK AND INCORPORATE
COMMENTS AND RE-SUBMIT

3. NOT ACCEPTED.
REVISE AND RE-SUBMIT.
PURCHASE ORDER NO: VT-261/15-XL - MTCORP

A1001
4. FOR INFORMATION ONLY. VDRL PRIME CODE :
NO SIGNATURE REQUIRED.

NAME : SEQUENCE
REQUISITION NO. VDRLCAT. Rev.
…………………………………… NO.:

DATE :
………………………….…………
RC9RC5-10.01 A1001 0001 0
SIGNATURE :
……………………………………
VIETSOVPETRO
RESEARCH AND ENGINEERING INSTITUTE
FOR OIL AND GAS

PROJECT NAME : RC9-RC5 PLATFORMS

DOCUMENT TITLE : DATASHEET FOR 220VAC UPS

DOCUMENT No. : RC9RC5-001-GENTS-ES2-DS-05

1 Issued for Approval 18/12/2014 P.V.TRUONG T.N.BINH T.H.TOAI B.T.HAN L.V. DZUNG

0 Issued for Approval 21/11/2014 P.V.TRUONG T.N.BINH T.H.TOAI B.T.HAN L.V. DZUNG

CHIEF ENG. PRO.


REV. DESCRIPTION DATE PREPARED CHECKED
DEPART. MANAGER MANAGER

2
RC9-RC5 PLATFORMs Doc. No RC9RC5-001-GENTS-ES2-DS-05

Rev. No 1

DATASHEET FOR 220VAC UPS Page 2 of 8

DATA SHEET FOR 220VAC UPS


1 Tag No. : UP-UPS-01 Client: Vietsovpetro
2 Service: Continuous Plant Location: RC9 Platform,Dragon Oil Field
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : RC9RC5-001-GENTS-ES2-CA-08 Purchase Order No. : TBA
5 No. of Units: 01 unit UPS UP-UPS-01
6 Service Description: 220VAC UNINTERRUPTIBLE POWER SUPPLY UNIT
7 ENVIRONMENTAL CONDITIONS POWER SYSTEM
8 Location: Outdoor marine, tropical & offshore with high corrosive, System Voltage: 380 V  5%
9 humid & salt laden System Frequency: 50 Hz  2%
10 Design Temp: 40 °C Neutral Earthing: Solidly neutral earthed
11 Ambient air temp: Min: 21 °C Max: 39 °C
12 Relative Humidity: 100% max Altitude: 18 m
13 Hazardous area classification: Class 1, Zone 2, IIA, T3
14 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
15 DESIGN DATA (note 3)
16 Applicable Standard IEC Comply
17 Type Static Type Comply
18 Topology Redundant Comply
19 Model VTA Protect 8.31/20
20 Design Ambient Temperature °C 40 Comply
21 Design Humidity % 44 - 100% Comply
22 Isolator Transformer Yes / No Yes Comply
23 Input Isolator Yes / No Yes Comply
24 Maintenance Bypass Yes / No Yes Comply
25 Battery Circuit Breaker Yes / No Yes Comply
26 Static Transfer Switch Yes / No Yes Comply
27 Bypass Transformer Yes / No Yes Comply
28 Load Isolator Yes / No Yes Comply
29 Line Harmonic Filters Yes / No As Required (VTA) Comply
30 RFI Filters Yes / No As Required (VTA) Comply
31 Rectifier Pulse 6 (VTA) Comply
32 Continuous Power Output (at 0.8 PF lag) kVA 12 (VTA) Comply
33 Prospective Fault Level at Source kA (1 sec.) 6 6
34 Max Upstream Feeder Protection Fuse Size / Type VTA 20
35 INPUT / OUTPUT SUPPLY ((note 3))
36 Normal AC Input Voltage VAC 380 380
37 Normal AC Input Number of Phases 3 3
38 Normal AC Input Frequency Hz 50 50
39 Common Bypass AC Input Voltage VAC 380 380
40 Common Bypass AC Input Number of Phases 3 3
41 Common Bypass AC Input Frequency Hz 50 50
42 Input Voltage Tolerance (Transient) ±% 15 15
43 Input Frequency Tolerance (Transient) ±% 5 5
44 Nominal AC Output Voltage VAC 220 220
45 Number of Phases of Output 1 1
46 Nominal AC Output Frequency Hz 50 50
47 Output Voltage Tolerance ±% 5 Comply
48 Output Frequency Tolerance ±% 1 Comply
49 Maximum Rate of Change of Output Frequency Hz / s 1 Comply
50 Minimum output short circuit capability kA VTA Comply
51 Max downstream fuse size for satisfactory clearance A VTA 194A

3
RC9-RC5 PLATFORMs Doc. No RC9RC5-001-GENTS-ES2-DS-05

Rev. No 1

DATASHEET FOR 220VAC UPS Page 3 of 8

DATA SHEET FOR 220VAC UPS


1 Tag No. : UP-UPS-01 Client: Vietsovpetro
2 Service: Continuous Plant Location: RC9 Platform,Dragon Oil Field
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : RC9RC5-001-GENTS-ES2-CA-08 Purchase Order No. : TBA
5 No. of Units: 01 unit UPS UP-UPS-01
6 Service Description: 220VAC UNINTERRUPTIBLE POWER SUPPLY UNIT
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
8 CIRCUIT PROCTECTION (note 3)
9 UPS input circuit breaker rating A VTA ῀ 40A
10 UPS output circuit breaker rating A VTA ῀ 80A
11 Battery circuit breaker rating A VTA ῀ 63A
12
13 CABLES ENTRY
14 Gland plate entry Top BOTTOM
15 Supply Cables to Normal Input
16 Type (note 4) TBA
17 Size and Number of Cores TBA
18 Supply Cables to Bypass Input
19 Type (note 4) TBA
20 Size and Number of Cores TBA
21 Supply Cables at Output
22 Type (note 4) TBA
23 Size and Number of Cores TBA
24
25 RECTIFIER / CHARGER (note 3)
26 General
27 Charging Method Constant Voltage Float Charging
28 Rated Input Current A VTA 17.3A (based on 12kVA)
29 Input Inrush Current A VTA 103.8
30 Maximum Input Earth Leakage Current A VTA 0.1A
31 Maximum Input Current A VTA 43A (based on UPS rating 20kVA)
32 Input Power Factor pu VTA 0.8
33 Nominal Output Voltage VDC VTA 220VDC
34 Output Voltage Tolerance ±% ≤1 1%
35 Maximum Output Voltage Ripple ± % rms ≤2 <2
36 Maximum Allowable Voltage Unbalance % VTA 100%
37 Rectifier Efficiency at Full load, 1/2 load & 3/4 load % VTA All 88%
38 Soft-Start Mode Yes / No Yes Yes
39 Fast Charging Mode Yes / No Yes Yes
40 Total Harmonic Current Distortion at Input % VTA 3%
41 Measurement, Indication,Monitor and Signalling
42 DC voltmeter Yes / No Yes Comply
43 Battery / Battery-charger output / AC mains current Yes / No Yes Comply
44 Main supply indicator lamp Yes / No Yes, Green Color Comply
45 Boost charging indicator lamp Yes / No Yes, Amber Color Comply
46 Float charging indicator lamp Yes / No Yes, Green Color Comply
47 Lamp test Yes / No Yes Comply
48 Main Input voltage loss/undervoltage Yes / No Yes Comply
49 Battery under/over voltage Yes / No Yes Comply
50 Battery isolated Yes / No Yes Comply

4
RC9-RC5 PLATFORMs Doc. No RC9RC5-001-GENTS-ES2-DS-05

Rev. No 1

DATASHEET FOR 220VAC UPS Page 4 of 8

DATA SHEET FOR 220VAC UPS


1 Tag No. : UP-UPS-01 Client: Vietsovpetro
2 Service: Continuous Plant Location: RC9 Platform,Dragon Oil Field
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : RC9RC5-001-GENTS-ES2-CA-08 Purchase Order No. : TBA
5 No. of Units: 01 unit UPS UP-UPS-01
6 Service Description: 220VAC UNINTERRUPTIBLE POWER SUPPLY UNIT
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
8 Charger current limiter operating Yes / No Yes Comply
9 Battery Charger failure Yes / No Yes Comply
10 Low charger output voltage Yes / No Yes Comply
11 DC earth fault Yes / No Yes Comply
12 Cooling fan failure Yes / No Yes Comply
13
14
15 INVERTER (note 3)
16 General
17 Inverter Rating kVA 12 20%
18 Inverter Output Overload Capacity in 1 Minute % 150 150
19 Inverter Output Voltage Setting Range % VTA +/-3%
20 Inverter DC Input Voltage Range for Rated Output ±% VTA 20%
21 Inverter Output Frequency Setting Range % VTA 50Hz/60Hz
22 Inverter Efficiency at Full load, 1/2 load & 3/4 load % VTA >86%
23 Total Harmonic Distortion of Output AC voltage
24 (At Rated Output to Linear Load 1.0 PF) % VTA 1%
25 Maximum Load PF Variation at Rated Output pu VTA 1.0 lead to 1.0 lag
26 Inverter Power Efficiency 100%/80%/50% rated output % VTA 86/87/86%
27 Measurement, Indication, Monitor and Signalling
28 Inverter Output Voltage Yes/No Yes Comply Via LCD Display
29 Inverter Output Current Yes/No Yes Comply Via LCD Display
30 Inverter Output frequency Yes/No Yes Comply Via LCD Display
31 Inverter Synchronized (between 2 Inverters output) Yes/No Yes Comply Via LCD Display
32 Source Synchronized (between Inverter and Static Switch/By-pass) Yes/No Yes Comply Via LCD Display
33 Inverter On-line Yes/No Yes Comply Via LCD Display
34 AC output over/under voltage Yes/No Yes Comply Via LCD Display
35 Overload Yes/No Yes Comply Via LCD Display
36 AC output over/under frequency Yes/No Yes Comply Via LCD Display
37 Inverter failure Yes/No Yes Comply Via LCD Display
38 Cabinet Temperature high Yes/No Yes Comply Via LCD Display
39 AC earth fault Yes/No Yes Comply Via LCD Display
40 Ventilation equipment failure Yes/No Yes Comply Via LCD Display
41
42
43 SYSTEM PERFORMANCE
44 Step AC Load Change (% of Inverter Rating) 0 - 100 100 - 0 50-100 100 - 50
45 AC Output Voltage Change (% of Nominal) % VTA 2 2 2 2
46 Response Time of AC Output Voltage
47 To 95% of Nominal s VTA 0.001 0.001 0.001 0.001
48 To Steady Condition s VTA 0.001 0.001 0.001 0.001
49
50

5
RC9-RC5 PLATFORMs Doc. No RC9RC5-001-GENTS-ES2-DS-05

Rev. No 1

DATASHEET FOR 220VAC UPS Page 5 of 8

DATA SHEET FOR 220VAC UPS


1 Tag No. : UP-UPS-01 Client: Vietsovpetro
2 Service: Continuous Plant Location: RC9 Platform,Dragon Oil Field
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : RC9RC5-001-GENTS-ES2-CA-08 Purchase Order No. : TBA
5 No. of Units: 01 unit UPS UP-UPS-01
6 Service Description: 220VAC UNINTERRUPTIBLE POWER SUPPLY UNIT
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
8 RELIABILITY DATA (Note 3)
9 Overall Mean Time Before Failure (MTBF) days VTA Approx 200,000 hours
10 Overall Mean Time To Repair (MTTR) days VTA
11
12 UPS ENCLOSURE (note 3)
13 Construction Material Sheet Steel Sheet Steel
14 Location Air-conditioned/ fan ventilated UPS room Noted
15 Dimensions (Length x Width x Height) mm VTA Please refer to GA Drawing
16 Weight (Excluding Batteries) kg VTA Please refer to GA Drawing
17 Degree of Protection IP21 (minimum) IP21
18 Maximum Sound Pressure Level at 1m dBA 70 70
19 Heat Loss at Worst Case Operating Conditions W VTA 1056W
20 Enclosure Access Front Front
21 Finish Colour - External RAL 7032 (Note-5) RAL 7032
22 Finish Colour - Internal RAL 7032 (Note-5) RAL 7032 Light Grey Powder Coat
23 Paint Specification BKT-001-TS-AZ7-SP-01 RAL 7032 Light Grey Powder Coat
24 Ventilation Natural Ventilation & Fan Natural Ventilation & Fan
25 Mounting Free standing/ Floor Mounted Free standing/ Floor Mounted
26 Minimum Space Clearance to Wall Behind mm VTA 0
27 Minimum Side Clearance mm VTA 0
28
29 TRANSFORMER
30 Duty / Location Isolation Bypass
31 Voltage Ratio V 380/380 380/220
32 Winding Connection VTA VTA YY0 Open delta
33 Rated Power VA VTA VTA 30kVA 20kVA
34 Rated Impedance Voltage % VTA VTA 4-6% 4-6%
35 Full Load Losses kW VTA VTA
36
37 CONTROL & INTERFACE
38 Communications Interface Modbus RS-485, Ethernet Comply
39 Common Alarm Voltage Free Contact Yes / No Yes Comply
40 Remote Access Capability Yes / No Yes Comply

Emergency Shutdown Trip should be the normally


41 Yes / No Yes Comply
open source 24 VDC contact from ESS system

42 Status of battery to DCS Required Comply


43 Status of Inverter to DCS Required Comply
44 Status of main power to DCS Required Comply
45 Status of common bypass to DCS Required Comply
46 Common alarm of UPS to DCS Required Comply
47
48
49
50

6
RC9-RC5 PLATFORMs Doc. No RC9RC5-001-GENTS-ES2-DS-05

Rev. No 1

DATASHEET FOR 220VAC UPS Page 6 of 8

DATA SHEET FOR 220VAC UPS


1 Tag No. : UP-UPS-01 Client: Vietsovpetro
2 Service: Continuous Plant Location: RC9 Platform,Dragon Oil Field
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : RC9RC5-001-GENTS-ES2-CA-08 Purchase Order No. : TBA
5 No. of Units: 01 unit UPS UP-UPS-01
6 Service Description: 220VAC UNINTERRUPTIBLE POWER SUPPLY UNIT
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
8 BATTERY (note 3)
9 Battery Type Valve Regulated Sealed Lead Acid Fiamm Italy
10 Battery Manufacturer VTA 6V
11 Nominal Battery Voltage V VTA 2.23/2.3/2.3
12 Voltage per cell floating/ equalizing/ boost VDC VTA
13 Battery location Air-conditioned/ fan ventilated UPS room
14 Battery Backup Time Min 60
15 Capacity Ah / Cx (VTA) 160AH / C1
16 Charge time ( from 0 to 80%) Hour 10 10
17 Nominal Cell Voltage (Float) VDC VTA 2
18 Number of Cells per Battery 126 (VTA) 108
19 Cell End of Discharge Voltage VDC ≥ 1.7 (VTA) 1.7
20 Battery Ageing Allowance % 25 (VTA) 25
21 Cell Internal Resistance W at X °C VTA 1.4mohm @ 20degC
22 Battery Earth Negative Pole
23 Weight of Single Battery Unit kg VTA 23
24 Battery Life (In Design Environmental Conditions) Years VTA >10 Years
25 Battery bank location Rack Refer to attached
26 Rack dimension mm VTA Approx 1100 kg
27 Total battery weight including supports kg VTA
28 Heat Dissipation at Floating/Recharging/Initial charge mode kW VTA 0.1 to 0.2 KW
29 Battery hydrogen emission floating/recharging/initial charge kW VTA
30
31
32 BATTERY CIRCUIT BREAKER (note 3)
33 Type VTA Thermal Magnetic
34 Rated Continuous Current A VTA ῀ 100A
35 Rated Voltage VDC VTA 220 VDC
36 Shunt Trip Yes / No Yes Yes
37 Earth Fault Yes / No Yes Yes
38 Interrupting Duty VTA Instantaneous
39 Rated Duty Uninterrupted Uninterrupted
40 Utilisation Category VTA A
41 Enclosure Yes / No Yes Inside bypass panel
42 Dimension mm VTA
43
44
45
46
47
48
49
50

7
RC9-RC5 PLATFORMs Doc. No RC9RC5-001-GENTS-ES2-DS-05

Rev. No 1

DATASHEET FOR 220VAC UPS Page 7 of 8

DATA SHEET FOR 220VAC UPS


1 Tag No. : UP-UPS-01 Client: Vietsovpetro
2 Service: Continuous Plant Location: RC9 Platform,Dragon Oil Field
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : RC9RC5-001-GENTS-ES2-CA-08 Purchase Order No. : TBA
5 No. of Units: 01 unit UPS UP-UPS-01
6 Service Description: 220VAC UNINTERRUPTIBLE POWER SUPPLY UNIT
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
8 STATIC TRANSFER SWITCH (note 3)
9 Rated Voltage V 220 (VTA) 220
10 Continuous Current Capability A VTA 70A
11 Rated Power kVA 12 20kVA
12 Short-Circuit Making Capability kA VTA 6
13 Short-Circuit Breaking Capability kA VTA 6
14 Rated Short Circuit Withstand Current A VTA 384A
15 Leakage Current A VTA
16 Maximum Transfer Time ms VTA < 1 ms
17 Classification (As per IEC 60947-6-1) PC / CB VTA DC31-A
18 Utilization Category VTA A
19 Measurement, Indication & Signalling
20 AC volmeter Static Switch output Yes/No Yes Comply LCD Display
21 Static Switch on-line Yes/No Yes Comply LCD Display
22 Static Switch on by-pass Yes/No Yes Comply LCD Display
23 Static Switch supply voltage out of limits Yes/No Yes Comply LCD Display
24 Static Switch supply frequency out of limits Yes/No Yes
25 ISOLATION / MAINTENANCE BYPASS SWITCHES (note 3)
26 Type Switch Disconnect 230V
27 Rated Voltage V 220 (VTA) 70A
28 Rated Continuous Current A VTA 20kVA
29 Rated Power kVA 12 20kVA
30 Operation Manual Manual
31 Rated Duty Uninterrupted Uninterrupted
32 Utilisation Category VTA A
33 Measurement, Indication & Signalling
34 AC volmeter Maintenance bypass output Yes/No Yes Comply
35 Maintenance bypass on-line Yes/No Yes Comply
36 Maintenance bypass on by-pass Yes/No Yes Comply
37 Maintenance bypass supply voltage out of limits Yes/No Yes Comply
38 Maintenance bypass supply frequency out of limits Yes/No Yes Comply
39 LOAD PROFILE
40 Load Current(A)
41 In
42
43
44
45
46
47
48 0
49 Time (hours)
50 0.25 0.5 0.75 1.0

8
RC9-RC5 PLATFORMs Doc. No RC9RC5-001-GENTS-ES2-DS-05

Rev. No 1

DATASHEET FOR 220VAC UPS Page 8 of 8

DATA SHEET FOR 220VAC UPS


1 Tag No. : UP-UPS-01 Client: Vietsovpetro
2 Service: Continuous Plant Location: RC9 Platform,Dragon Oil Field
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : RC9RC5-001-GENTS-ES2-CA-08 Purchase Order No. : TBA
5 No. of Units: 01 unit UPS UP-UPS-01
6 Service Description: 220VAC UNINTERRUPTIBLE POWER SUPPLY UNIT
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
8 NOTES:
9 1. The methodology used to derive the reliability data (MTBF and MTTR) shall be attached with tender.
10 2. Refer to AC UPS Battery sizing calculations Document "BKT-001-TS-ES2-CA-03".
11 3. Data Sheet to be read in conjunction with BKT-001-TS-ES2-SP-11 Specification for AC UPS Systems.
12 4. Refer to Specification for Cable Document "BKT-001-TS-ES2-SP-01".
13 5. Painting shall be as specified in Technical Specification for Painting, Document Number BKT-001-TS-AZ7-SP-01.
14 6. VTA = Vendor To be Advise.
15 7. TBA = To Be Advised.
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

You might also like