Insulgard status register map

Function Register
Parameter Description Data Range Size
Code Address
1 00001 Alarm 1 (yellow level), 0/1 1 bit
1 00002 Alarm 2 (red level) 0/1 1 bit
1 00003 Device error (1 - no error) 0/1 1 bit
3 40001 Date 1-31 2 byte
3 40002 Month 1-12 2 byte
3 40003 Year 0-99 2 byte
3 40004 Hours 0-23 2 byte
3 40005 Minutes 0-59 2 byte
3 40006 Relay #1 status 0 or 1 2 byte
3 40007 Relay #2 status 0 or 1 2 byte
3 40008 Relay #3 status 0 or 1 2 byte
3 40009 Max PDI Channel Number 1 to 15 2 byte
40010 % of Max PDI to red level (4-20 mA
0 to 100 2 byte
3 output replication)
3 40011 Power frequency measured 20-70 2 byte (/100 to get real reading)
3 40012 Temperature 2 bytes (/10 to get real reading)
3 40013 Current 2 bytes (/10 to get real reading)
3 40014 Voltage 2 bytes (/10 to get real reading)
40015 2 byte, each channel activity bit
Channel activation status
3 encoded in low byte
40016-
3 40025 Reserved
40026 ch. 1 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40027 ch. 1 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40028 ch. 1 PPS – pulses/sec 2 bytes
40029 ch. 2 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40030 ch. 2 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40031 ch. 2 PPS – pulses/sec 2 bytes
40032 ch. 3 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40033 ch. 3 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40034 ch. 3 PPS – pulses/sec 2 bytes
40035 ch. 4 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40036 ch. 4 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40037 ch. 4 PPS – pulses/sec 2 bytes
40038 ch. 5 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40039 ch. 5 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40040 ch. 5 PPS – pulses/sec 2 bytes
40041 ch. 6 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40042 ch. 6 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40043 ch. 6 PPS – pulses/sec 2 bytes
40044 ch. 7 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40045 ch. 7 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40046 ch. 7 PPS – pulses/sec 2 bytes
40047 ch. 8 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40048 ch. 8 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40049 ch. 8 PPS – pulses/sec 2 bytes
40050 ch. 9 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40051 ch. 9 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40052 ch. 9 PPS – pulses/sec 2 bytes
40053 ch. 10 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40054 ch. 10 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40055 ch. 10 PPS – pulses/sec 2 bytes
40056 ch. 11 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40057 ch. 11 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40058 ch. 11 PPS – pulses/sec 2 bytes
40059 ch. 12 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40060 ch. 12 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40061 ch. 12 PPS – pulses/sec 2 bytes
40062 ch. 13 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40063 ch. 13 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40064 ch. 13 PPS – pulses/sec 2 bytes
40065 ch. 14 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40066 ch. 14 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40067 ch. 14 PPS – pulses/sec 2 bytes
40068 ch. 15 Qmax – maximum pulse 2 byte (use a calibration table to
3 magnitude at 0.2 pulse per period get real number)
40069 ch. 15 PDI – Partial discharge
2 byte (/10 to get a real number)
3 intensity
3 40070 ch. 15 PPS – pulses/sec 2 bytes
Application Note
InsulGard has RS-485 interface and built-in standard MODBUS-RTU protocol.
Therefore, it can be eventually used with any SCADA system supporting both RS-485
network and MODBUS-RTU. Information that can be obtained from InsulGard into
SCADA is described in the attached document.
We do not have any knowledge and experience with IMPAC and PowerNet.
Therefore, we can not advice on this.
You can get all the information on PD using our software that also support RS-485
and MODBUS-RTU, but we do not know how it will interfere with particular SCADA
software, if used over the same wires. This can be resolved only on case by case
basis and is application specific.

ERROR HANDLING AND EXCEPTION RESPONSES


In case of supported exceptions or errors the device sets 1 in the most significant bit
of the returned function code (0x81 and 0x83 accordingly). The data byte following the
function code should contain in this case one of the supported exceptions. No
message length included.

Exception codes supported:


02 – Illegal register
03 – illegal number of registers
Error codes 01, 04, 05, 06, 07, 08 are not supported.