Professional Documents
Culture Documents
Protocolo FAT Descargadores Suecia
Protocolo FAT Descargadores Suecia
Customer reference
Test witnessed by
We hereby certify that the above objects have passed the routine tests
herein reported successfully.
Ludvika
ABB AB
High Voltage Products / Surge Arresters
Quality Department
The objects specified above are hereby certified as having successfully undergone
the testing herein reported. This is an auto-generated document and is valid without
a signature.
Page 2(4)
Residual voltage at 10kA (8/20 µs) is individually measured on each ZnO-block. The residual
voltage of the complete arrester is taken as the sum of the residual voltages of the ZnO-blocks
in series.
Grading current is measured at Uc (continuous operating voltage) on each arrester unit for
information only. Acceptance criteria are therefore not applicable.
After the reference voltage test having a minimum test time of 30 seconds the test voltage is
decreased to 0.9 times rated voltage of the unit. At this voltage each unit is checked to have a
steady internal corona level less than 5 pC.
Page 3(4)
ACCEPTANCE CRITERIA
Min Max
kV rms kV crest kV crest kV rms Watts
Complete arrester
Page 4(4)
TEST RESULTS
Serial number Reference Residual Internal corona Power losses and grading
voltage at a voltage at current at
resistive at 10kA
current of
2 mA crest