CUSTOMER : PURITA WATER SOLUTIONS PVT. LTD.

END USER : BHARTIYA RAIL BIJLEE COMPANY LTD.

PROJECT : NABINAGAR THERMAL POWER PROJECT(4X250MW)

CV

DOCUMENT STATUS:

PRELIMINARY FOR INFORMATION FOR APPROVAL AS BUILT

SWITCHGEAR TEST REPORT


TEST AND CALIBRATION CERTIFICATE

(Duplicate copy)

Model Name: METSEEM6436HCL10NC Serial No: 540410032619


Test Parameters: V, I, F & P Accuracy Class: Class 1.0
Rated Current: 5A Firmware Revision 01.03
Calibration Date: 26/Dec/2020 Communication:

Test Load 63.5V,5.0A 230V,1.0A 277V,0.1A


Parameters - V, I & F Vavg Iavg F Vavg Iavg F Vavg Iavg F
Permissible Error(%) ± 0.8 ± 0.5 ± 0.05 ± 0.5 ± 0.5 ± 0.05 ± 0.5 ± 0.5 ± 0.05
Observed Error (%) @ 50 Hz 0.208 -0.017 -0.014 0.142 -0.018 -0.013 0.144 0.034 -0.012
Observed Error (%) @ 60 Hz 0.149 -0.004 -0.008 0.096 -0.015 -0.013 0.119 0.002 -0.014
Parameters - P UPF 0.5 Lag 0.8 Lead UPF 0.5 Lag 0.8 Lead UPF 0.5 Lag 0.8 Lead
Permissible Error(%) ±1 ±1 ±1 ±1 ±1 ±1 ± 1.5 - -
Observed Error(%) @ 50 Hz-P 0.125 -0.128 0.222 0.127 0.030 0.162 0.164 0.215 0.174

Observed Error(%) @ 60 Hz-P 0.081 -0.124 0.338 0.083 0.008 0.123 0.108 0.215 0.075

Notes:

1. The certificate shall not be reproduced except in full, without prior written approval of the issuing authority.

2. Vavg = 3-phase average voltage (line to neutral) in volt, Iavg = 3-phase average current in ampere

F = Frequency in hertz, P= Active 3-Phase total power in watts.

3. AC Calibration Source: MTSPE 120.3 traceable to international standards.

4. Reference : MTE-PRS 121.3,SN.NO 38594 traceable to International standards.

5. Calibration Setup verified based on ISO 9001:2008 Certified Process.

6.Accuracy :Class 1.0 as per IEC62052-11 and IEC62053-21

7.W Integrated over a period of time is equal to Wh. W accuracy is tested over a period of time(upto 30 samples)

ISO 9000:2008 Certified


ISO 14001:2004 Certified
Schneider Electric India Pvt Ltd
OHSAS 18001:2007 Certified
www.schneider-electric.co.in
Certificate No:
TAE0000202

This is to certify:
That the Motor Starter

with type designation(s)


GV2-ME, GV2-P and GV2-L

Issued to
Schneider Electric Industries SAS
GRENOBLE, France

is found to comply with


DNV GL rules for classification – Ships, offshore units, and high speed and light craft

Application :
Motor- protected circuit breaker including overload release, thermal-magnetic or magnetic
release. Accessories: Under voltage trip, shunt trip, voltage trip, analogue modules, auxiliary
contacts

Product(s) approved by this certificate is/are accepted for installation on all vessels classed
by DNV GL.

Rated voltage (V) 690


Rated current (A) 0.16 - 32
Frequency (Hz) 50 - 60


Issued at Høvik on 2017-06-21


for DNV GL
This Certificate is valid until 2022-06-30. Digitally Signed By: Andreas Kristoffersen

DNV GL local station: Marseille Location: DNV GL Høvik, Norway


Signing Date: 2017-06-23

Approval Engineer: Nicolay Horn Andreas Kristoffersen


Head of Section

This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 1 of 6

© DNV GL 2014. DNV GL and the Horizon Graphic are trademarks of DNV GL AS.
Job Id: 262.1-003417-10
Certificate No: TAE0000202

Name and place of manufacturer

Schneider Electric France Schneider Thailand ltd


6-8 rue de Bailly – B.P. 97872 540 Soi 9, Bangpoo Industry Estate, Sukhumvit
21078 Dijon Cedex, France Road, Muang District
Samutprakarn 102801, Thailand

Product description
Motor starters (circuit breaker/ contactor combination) type:
GV2-ME01, GV2-ME02, GV2-ME03, GV2-ME04, GV2-ME05, GV2-ME06, GV2-ME07,
GV2-ME08, GV2-ME10, GV2-ME14, GV2-ME16, GV2-ME20, GV2-ME21, GV2-ME22 and GV2-ME32.

GV2-P01, GV2-P02, GV2-P03, GV2-P04, GV2-P05, GV2-P06, GV2-P07, GV2-P08, GV2-P10, GV2-P14,
GV2-P16, GV2-P20, GV2-P21, GV2-P22 and GVP32.
GV2-L03, GV2-L04, GV2-L05, GV2-L06, GV2-L07, GV2-L08, GV2-L10, GV2-L14, GV2-L16, GV2-L20,
GV2-L22 and GV2-L32.

Types: GV2-ME01 GV2-ME02 GV2-ME03 GV2-ME04 GV2-ME05 GV2-ME06


Rated operational 690 690 690 690 690 690
voltage Ue(V):
Rated insulation voltage 690 690 690 690 690 690
Ui (V):
Rated current (A): 0.16 0.25 0.4 0.63 1.0 1.6
Rated frequency (Hz): 50/60 50/60 50/60 50/60 50/60 50/60
Overload release setting 0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1.0-1.6
range (A):
Rated ultimate break.
cap. Icu (kA)
415 V 100 100 100 100 100 100
500 V 100 100 100 100 100 100
690 V 100 100 100 100 100 100
Rated service breaking
cap. Ics (kA)
415 V 100 100 100 100 100 100
500 V 100 100 100 100 100 100
690 V 100 100 100 100 100 100
Utilisation category: A A A A A A

Types: GV2-ME07 GV2-ME08 GV2-ME10 GV2-ME14 GV2-ME16 GV2-ME20


Rated operational 690 690 690 690 690 690
voltage Ue(V):
Rated insulation voltage 690 690 690 690 690 690
Ui (V):
Rated current (A): 2.5 4 6.3 10 14 18
Rated frequency (Hz): 50/60 50/60 50/60 50/60 50/60 50/60
Overload release setting 1.6-2.5 2.5-4 4-6.3 6-10 9-14 13-18
range (A):
Rated ultimate break.
cap. Icu (kA)
415 V 100 100 100 100 15 15
500 V 100 100 50 10 6 6
690 V 3 3 3 3 3 3
Rated service breaking

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 2 of 6


Job Id: 262.1-003417-10
Certificate No: TAE0000202

Types: GV2-ME07 GV2-ME08 GV2-ME10 GV2-ME14 GV2-ME16 GV2-ME20


cap. Ics (kA)
415 V 100 100 100 100 7.5 7.5
500 V 100 100 50 10 4.5 4.5
690 V 2.25 2.25 2.25 2.25 2.25 2.25
Utilisation category: A A A A A A

Types: GV2-ME21 GV2-ME22 GV2-ME32 GV2-P01 GV2-P02 GV2-P03


Rated operational 690 690 690 690 690 690
voltage
Ue(V):
Rated insulation voltage 690 690 690 690 690 690
Ui (V):
Rated current (A): 23 25 32 0.16 0.25 0.4
Rated frequency Hz: 50/60 50/60 50/60 50/60 50/60 50/60
Overload release setting 17-23 20-25 24-32 0.1-0.16 0.16-0.25 0.25-0.40
range (A):
Rated ultimate break.
cap. I cu (kA)
415 V 15 15 10 100 100 100
500 V 4 4 4 100 100 100
690 V 3 3 3 100 100 100
Rated service breaking
cap. Ics (kA)
415 V 6 6 5 100 100 100
500 V 3 3 3 100 100 100
690 V 2.25 2.25 2.25 100 100 100
Utilisation category: A A A A A A

Types: GV2-P04 GV2-P05 GV2-P06 GV2-P07 GV2-P08 GV2-P10


Rated operational 690 690 690 690 690 690
voltage Ue(V):
Rated insulation voltage 690 690 690 690 690 690
Ui (V):
Rated current (A): 0.63 1 1,6 2,5 4 6,3
Rated frequency (Hz): 50/60 50/60 50/60 50/60 50/60 50/60
Overload release setting 0.40-0.63 0,63-1 1-1,6 1,6-2,5 2,5-4 4-6,3
range (A):
Rated ultimate break.
cap. Icu (kA)
415 V 100 100 100 100 100 100
500 V 100 100 100 100 100 100
690 V 100 100 100 8 8 6
Rated service breaking
cap. Ics (kA)
415 V 100 100 100 100 100 100
500 V 100 100 100 100 100 100
690 V 100 100 100 8 8 6
Utilisation category: A A A A A A

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 3 of 6


Job Id: 262.1-003417-10
Certificate No: TAE0000202

Types: GV2-P14 GV2-P16 GV2-P20 GV2-P21 GV2-P22 GV2-P32


Rated operational 690 690 690 690 690 690
voltage Ue(V):
Rated insulation voltage 690 690 690 690 690 690
Ui (V):
Rated current (A): 10 14 18 23 25 32
Rated frequency (Hz): 50/60 50/60 50/60 50/60 50/60 50/60
Overload release setting 6-10 9-14 13-18 17-23 20-25 24-32
range (A):
Rated ultimate break.
cap. Icu (kA)
415 V 50 50 50 50 50 50
500 V 50 50 10 10 10 10
690 V 6 6 4 4 4 4
Rated service breaking
cap. Ics (kA)
415 V 100 100 25 25 25 25
500 V 50 31,5 7,5 7,5 7,5 7,5
690 V 6 6 4 4 4 4
Utilisation category: A A A A A A

Types: GV2-L03 GV2-L04 GV2L05 GV2-L06 GV2-L07 GV2-L08


Rated operational 690 690 690 690 690 690
voltage Ue(V):
Rated insulation voltage 690 690 690 690 690 690
Ui (V):
Rated current (A): 0,63 1 1,6 2,5 4 6,3
Rated frequency (Hz): 50/60 50/60 50/60 50/60 50/60 50/60
Overload release setting - - - - - -
range (A):
Rated ultimate break.
cap. Icu (kA)
415 V 100 100 100 100 100 100
500 V 100 100 100 100 100 100
690 V 100 100 100 100 4 4
Rated service breaking
cap. Ics (kA)
415 V 100 100 100 100 100 100
500 V 100 100 100 100 100 100
690 V 100 100 100 100 4 4
Utilisation category: A A A A A A

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 4 of 6


Job Id: 262.1-003417-10
Certificate No: TAE0000202

Types: GV2-L10 GV2-L14 GV2-L16 GV2-L20 GV2-L22 GV2-L32


Rated operational 690 690 690 690 690 690
voltage Ue(V):
Rated insulation voltage 690 690 690 690 690 690
Ui (V):
Rated current (A): 8 10 14 18 25 32
Rated frequency (Hz): 50/60 50/60 50/60 50/60 50/60 50/60
Overload release setting - - - - - -
range (A):
Rated ultimate break.
cap. Icu (kA)
415 V 100 100 100 50 50 35
500 V 100 100 100 10 10 10
690 V 4 4 4 4 4 4
Rated service breaking
cap. Ics (kA)
415 V 100 100 100 25 25 17,5
500 V 100 100 100 7,5 7,5 7,5
690 V 4 4 4 4 4 4
Utilisation category: A A A A A A
Accessories: Under voltage trip, shunt trip, voltage trip, contact modules, auxiliary contacts

Application/Limitation

Motor- protected circuit breaker including overload release, thermal magnetic release.
Applicable for use in an IT net with a voltage up to 690 V.

Type Approval documentation

Technical info:
“TeSys protection components”, parts of manufacturer’s catalogue.
Application For 3C Compulsory Certification Product Description
Catalogue 99422 dated March 1994 and catalogue ART. 27501 dated October 2001

Test reports;
STIE test reports nos. 00901-CB2013CQC-055141-1 ans 2 issued 2015-02-06.
CQC Test Certificate Appendix no. 2007010307236560.
For GV2-P:
ASEFA reports K11-94-06F, K11-94-06G, K11-94-22B, K11-94-25B, K11-94-19B,
K11-94-05C.
ASEFA certification of conformity no. 05-04BT and 06-04BT (GV2-P32).
For GV2-L:
ASEFA reports K11-94-35F, K11-94-35G, K11-94-47B, K11-94-51B, K11-94-43B,
K11-94-05C.
ASEFA certification of conformity no. 085-04BT and 086-04BT (GV2-L32).

Tests carried out

Type tests according to IEC 60947-1, IEC 60947-2 (4th ed. + A1 & A2) including Annex H, IEC60 947-4-
1 (3rd ed. + A2), sequence 1, 2 & 3, and environmental tests.

Marking of product
Telemecanique - Schneider Electric - Type designation.

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 5 of 6


Job Id: 262.1-003417-10
Certificate No: TAE0000202

Periodical assessment
The scope of the periodical assessment is to verify that the conditions stipulated for the Type approval is
complied with and that no alterations are made to the product design or choice of materials.

The main elements of the assessment are:


 Inspection on factory samples, selected at random from the production line (where practicable)
 Results from Routines (RT) checked (if not available tests according to RT to be carried out)
 Review of type approval documentation
 Review of possible change in design, materials and performance
 Ensuring traceability between manufacturer’s product type marking and Type Approval Certificate.

Assessment to be performed at 2 and 3.5 year and at renewal.

END OF CERTIFICATE

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 6 of 6


Certificate No:
TAE000033S
TYPE APPROVAL CERTIFICATE

This is to certify:
That the Contactor

with type designation(s)


Tesys LC1-D _ _ / LC2-D _ _

Issued to
Schneider Electric Industries S.A.S.
Eybens, Isere, France

is found to comply with


IEC 60947
DNV GL rules for classification – Ships, offshore units, and high speed and light craft

Application :
Contactors and reversing / pole-changing contactors with ac control circuit for installation in
enclosures onboard ship and mobile offshore units.

Products approved by this certificate are accepted for installation on all vessels classed by
DNV GL.

Rated voltage (V) 600 / 690


Rated current (A) 9 to 38
Frequency (Hz) 50 - 60

Issued at Høvik on 2018-10-22


for DNV GL
This Certificate is valid until 2022-12-31.
DNV GL local station: Marseille

Approval Engineer: Nicolay Horn Marta Alonso Pontes


Head of Section

This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 1 of 3

© DNV GL 2014. DNV GL and the Horizon Graphic are trademarks of DNV GL AS.
Job Id: 262.1-007395-6
Certificate No: TAE000033S

Name and place of manufacturer


Contactor and auxiliary contactor: Auxiliary contact blocks and accessories:
Schneider Electric Industries SAS Schneider Electric Industries SA
27109 Le Vaudreuil, France Chasseneuil du Poitou, France
PT. Schneider Electric Manufacturing Batam
Batamindo Industrial Park, Lot 4, Muka Kuning
Batam, 29433, Indonesia

Product description
Electric contactors with ac or dc control circuit with electromechanical or electronic coils of type LC1-D _
_ and LC2-D _ _ reversing / pole-changing contactors with 3 poles and 4 poles and auxiliary contact
blocks. Contactor equipped with 1 NO and one NC contact.

3 poles contactors (LC1) and reversing contactors (LC2):


Ue Ie
Reference Ith Utilization 230V 400V 440V 500V 690V
category
LC1/LC2-D09 (a) 25A Ie (AC-3) 8.5A 8.5A 9A 9.2A 6.7A
Ie (AC-4) 7.1A 7.1A 7.5A 7.7A 5.6A
LC1/LC2-D12(a) 25A Ie (AC-3) 11.3A 11.5A 12A 12.4A 8.9A
Ie (AC-4) 9.42A 9.6A 10A 10.34A 7.42A
LC1/LC2-D18 32A Ie (AC-3) 15A 15.5A 18A 16A 11.7A
Ie (AC-4) 12.5A 12.92A 15A 13.42A 9.75A
LC1/LC2-D183 25A Ie (AC-3) 15A 15.5A 18A 16 A 11.7A
Ie (AC-4) 12.5A 12.92A 15A 13.42A 9.75A
LC1/LC2-D25(b) 40A Ie (AC-3) 20A 22A 25A 23A 17A
Ie (AC-4) 16.7A 18.34A 20.84A 19.2A 14.2A
LC1/LC2-D32 50A Ie (AC-3) 27A 29A 32A 28A 21A
Ie (AC-4) 22.5A 24.2A 20.84A 19.2A 14.2A
LC1/LC2-D323 40A Ie (AC-3) 20A 22A 25A 23A 17A
Ie (AC-4) 16.7A 18.34A 20.84A 19.2A 14.2A
LC1/LC2-D38 50A Ie (AC-3) 31.7A 35A 38A 28A 21A
Ie (AC-4) 26.42A 29.2A 20.84A 19.2A 14.2A
LC1/LC2-D09(a) 25A Ie (AC-4) 7.1A 7.1A 7.5A 7.7A 5.6A
Ie (AC-3) 11.3A 11.5A 12A 12.4A 8.9A
(a) except for D093, D123 : Ith = 20A
(b) except for LC1/LC2-D253 : Ith = 25A

4 poles contactors (LC1) and reversing contactors (LC2):


Ue Ie
Reference Ith Utilization 230V 400V 440V 500V 690V
category
LC1-D098, 20A Ie (AC-3) 8.5A 8.5A 9A 9.2A 6.7A
LC1/LC2-DT20 Ie (AC-4) 7.1A 7.1A 7.5A 7.7A 5.6A
LC1-D128, 25A (c) Ie (AC-3) 11.3A 11.5A 12A 12.4A 8.9A
LC1/LC2-DT25 Ie (AC-4) 9.42A 9.6A 10A 10.34A 7.42A
LC1-D188, 32A Ie (AC-3) 15A 15.5A 18A 16.1A 11.7A
LC1/LC2-DT32 Ie (AC-4) 12.5A 12.92A 15A 13.42A 9.75A
LC1-D258, 40A Ie (AC-3) 20A 22A 25A 23A 17A
LC1/LC2-DT40 Ie (AC-4) 16.7A 18.34A 20.84A 19.2A 14.2A
(c) except for D1283, DT253 : Ith = 20A

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 2 of 3


Job Id: 262.1-007395-6
Certificate No: TAE000033S

Accessories:
Auxiliary contactor CAD-32… and CAD-50…
Aux contacts blocks and Accessories LAD-N, LAD-C, LAD-8N
LAD-T, LAD-S, LAD-R
LAD-6K10, LAD-4, LAD-9
May be followed by: Suffix 3 = Spring terminals
Suffix 6 = Lug connections
Suffix 9 = Faston connections

Application/limitation
With Uimp = 6 kV the max. rated voltage is 600 V when used in a IT (ship) net. It can be used in
applications with directly earthed systems with rated voltage of 400/690 V.

Type Approval documentation


Technical documentation:
«TeSys D, D Green, SK, K, SKGC, GC, GY, GF – Technical Data for Designers» part of cataloge.
Product description : Size 1 contactors 3 polees, 4 poles & Product description Size 2 contactors 3
polees, , 4 poles. Catalogue “Tesys offer Motor starters 0.1 to 75 kW /400 A, Power applications 0.1 à
250 A”, January 2000.

Test reports:
Electrical type tests test after IEC 60947-4-1 & IEC60947-5-1: VDE test reports TFR 242646-1 and 2
dated 2017-12-20, VDE test reports no. 234353 issued 2017-10-10, VDE test report no. 246224 issued
2018-03-20.
Environmental tests: F- Lab test report no. TFR_201703851_002, TFR_201703851_003 and
RI_201703851_004 dated 2017-09-01, Volta test report no. TFR_201604 dated 2017-02-23, Schneider
test reports nos. 545-00 dated April 2001, 546-00 and 548-00 dated June 2001, 547-00 dated October
2001, G0010077A, G0010078A and G0010080A dated October 2000, and GV 10058B dated 2001-05-31.

Tests carried out


Electrical tests after IEC 60947, Environmental tests after DNVGL-CG-0339 Novemberl 2015 (Power
supply variation, power supply failor, dielectric, insulation, inclination, vibration, cold, dry heat and damp
heat).

Marking of product
Telemecanique / Schneider Electric – Type designation

Periodical assessment
The scope of the periodical assessment is to verify that the conditions stipulated for the Type approval is
complied with and that no alterations are made to the product design or choice of materials.

The main elements of the assessment are:


• Inspection on factory samples, selected at random from the production line (where practicable)
• Results from Routines (RT) checked (if not available tests according RT to be carried out)
• Review of type approval documentation
• Review of possible change in design, materials and performance
• Ensuring traceability between manufacturer’s product type marking and Type Approval Certificate.

Assessment to be performed at 1.5 and 3 year and at renewal.


END OF CERTIFICATE

Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 3 of 3


SCHNEIDER ELECTRIC INDIA (P) LIMITED
Address: No 172, Poonamallee Bypass road,Poonamallee, Chennai-
DATE : 15.04.2021
600056. Phone: +044-30962300 Fax: +044-30962400

To whomsoever it may

The below refered products are tested as per the relevant IS/IEC standards and the process meets the schneider electric - chennai ISO 9001:2008
procedure. We confirm the terms and conditions are as per the order acceptance/catalogue.
Disclaimer: Terms and conditions shall be changed without prior notice
Certificate of
Customer Name : Electro Care (India) Private Limited
Or der No : 0300379127 & 300379129

1 A9N2P02C Acti 9 MCB xC60 2P 02A C


2 A9N2P04C Acti 9 MCB xC60 2P 04A C
3 A9N2P16C Acti 9 MCB xC60 2P 16A C
4 A9N2P10C Acti 9 MCB xC60 2P 10 A C
5 A9N2P06C Acti 9 MCBXC60 2P 06AC
6 A9N2P20C Acti 9 MCBXC60 2P 20AC
7 A9N3P16C Acti 9 MCBXC60 3P 16AC
8 A9N1P06C Acti 9 MCBXC60 1P 06AC
9 A9N3P06C Acti 9 MCBXC60 3P 06AC
10 A9N3P40C Acti 9 MCBXC60 3P 40AC

Standard : IS/IEC-60898-1 Product Miniature Circuit Breaker


Sl. No. Test Result
Performed

1 Rating,Type Passed
2 High Voltage Test Passed
3 Test of Instantaneous Tripping Passed
4 Conventional Non Trip Current Test Passed
5 Conventional Trip Current Test Passed
6 Visual Inspection Passed

This is the standard COC hence signature not required


EU DECLARATION OF CONFORMITY
We: Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92506 – France

Hereby declare under our sole responsibility that the products:


Trademark Schneider Electric
Product, Type, Model Electromechanical plug-in relays – RXM miniature relays, RXZE relay sockets and
RXM02/RXM04 protection modules
List of reference and options See Annex
are in conformity with the requirements of the following directives and conformity was checked in accordance with the
following standards.
Directive Harmonized and/or International standards
LV Directive 2014/35/EU Electromechanical elementary relays - Part 1: General requirements
EN 61810-1:2015/AC:2017/AC:2018 and IEC 61810-1:2015/COR1:2017/COR2:2018
Connectors - Safety requirements and test
EN 61984:2009 and IEC 61984:2008
Connecting devices - Electrical copper conductors - Safety requirements for screw-
type and screwless-type clamping units - Part 1: General requirements and particular
requirements for clamping units for conductors from 0,2 mm2 up to 35 mm2
(included)
EN 60999-1:2000 and IEC 60999-1:1999
RoHS Directive 2011/65/EU EN 50581:2012
(Inclusive of Directive (EU) Technical documentation for the assessment of electrical and electronic
2015/863) products with respect to the restriction of hazardous substances

Subject to correct installation, maintenance and use conforming to its intended purpose, to the applicable regulations and
standards, to the supplier's instructions and to accepted rules of the art.
This declaration becomes invalid in the case of any modification to the products not authorized by us.

Issued at Carros, France: 15 March 2020

Alain BERNERD
Vice President
Customer Satisfaction and Quality
Industrial Automation

RELAYS03-02-200315 ORIGINAL DECLARATION, NO TRANSLATION WITHOUT WRITTEN AUTHORISATION Page 1 of 3


EU DECLARATION OF CONFORMITY
Annex - Table of product references: RXM relays
RXM2AB1B7 RXM2LB2BD RXM4AB3FD RXM4LB1P7
RXM2AB1BD RXM2LB2CD RXM4AB3GD RXM4LB2B7
RXM2AB1E7 RXM2LB2ED RXM4AB3JD RXM4LB2BD
RXM2AB1ED RXM2LB2F7 RXM4AB3P7 RXM4LB2CD
RXM2AB1F7 RXM2LB2FD RXM4CB1B7 RXM4LB2ED
RXM2AB1FD RXM2LB2JD RXM4CB1BD RXM4LB2F7
RXM2AB1G7 RXM2LB2P7 RXM4CB1E7 RXM4LB2FD
RXM2AB1GD RXM2NB3B7 RXM4CB1ED RXM4LB2JD
RXM2AB1HD RXM2NB3BD RXM4CB1F7 RXM4LB2P7
RXM2AB1JD RXM2NB3F7 RXM4CB1FD RXM4NB3B7
RXM2AB1MD RXM2NB3FD RXM4CB1JD RXM4NB3BD
RXM2AB1ND RXM2NB3JD RXM4CB1MD RXM4NB3F7
RXM2AB1P7 RXM2NB3MD RXM4CB1P7 RXM4NB3FD
RXM2AB1U7 RXM2NB3P7 RXM4CB2B7 RXM4NB3JD
RXM2AB1UD RXM3AB1B7 RXM4CB2BD RXM4NB3MD
RXM2AB2B7 RXM3AB1BD RXM4CB2E7 RXM4NB3P7
RXM2AB2BD RXM3AB1E7 RXM4CB2ED
RXM2AB2E7 RXM3AB1ED RXM4CB2F7
RXM2AB2ED RXM3AB1F7 RXM4CB2FD
RXM2AB2F7 RXM3AB1FD RXM4CB2JD
RXM2AB2FD RXM3AB1JD RXM4CB2P7
RXM2AB2JD RXM3AB1P7 RXM4GB1B7
RXM2AB2P7 RXM3AB2B7 RXM4GB1BD
RXM2AB3B7 RXM3AB2BD RXM4GB1E7
RXM2AB3BD RXM3AB2E7 RXM4GB1ED
RXM2AB3E7 RXM3AB2ED RXM4GB1F7
RXM2AB3ED RXM3AB2F7 RXM4GB1FD
RXM2AB3F7 RXM3AB2FD RXM4GB1JD
RXM2AB3FD RXM3AB2JD RXM4GB1P7
RXM2AB3JD RXM3AB2P7 RXM4GB2B7
RXM2AB3P7 RXM4AB1B7 RXM4GB2BD
RXM2CB1B7 RXM4AB1BD RXM4GB2E7
RXM2CB1BD RXM4AB1E7 RXM4GB2ED
RXM2CB1E7 RXM4AB1ED RXM4GB2F7
RXM2CB1ED RXM4AB1F7 RXM4GB2FD
RXM2CB1F7 RXM4AB1FD RXM4GB2GD
RXM2CB1FD RXM4AB1JD RXM4GB2JD
RXM2CB1JD RXM4AB1MD RXM4GB2MD
RXM2CB1P7 RXM4AB1P7 RXM4GB2ND
RXM2CB2B7 RXM4AB1U7 RXM4GB2P7
RXM2CB2BD RXM4AB2B7 RXM4GB2U7
RXM2CB2E7 RXM4AB2BD RXM4GB3B7
RXM2CB2ED RXM4AB2E7 RXM4GB3BD
RXM2CB2F7 RXM4AB2ED RXM4GB3E7
RXM2CB2FD RXM4AB2F7 RXM4GB3ED
RXM2CB2JD RXM4AB2FD RXM4GB3F7
RXM2CB2P7 RXM4AB2GD RXM4GB3FD
RXM2LB1B7 RXM4AB2JD RXM4GB3JD
RXM2LB1BD RXM4AB2P7 RXM4GB3P7
RXM2LB1ED RXM4AB3B7 RXM4LB1B7
RXM2LB1F7 RXM4AB3BD RXM4LB1BD
RXM2LB1JD RXM4AB3E7 RXM4LB1ED
RXM2LB1P7 RXM4AB3ED RXM4LB1F7
RXM2LB2B7 RXM4AB3F7 RXM4LB1JD

RELAYS03-02-200315 ORIGINAL DECLARATION, NO TRANSLATION WITHOUT WRITTEN AUTHORISATION Page 2 of 3


EU DECLARATION OF CONFORMITY

Annex - Table of product references: RXZE sockets and RXM02/RXM04 protection modules
RXZE1M2C RXM021BN
RXZE1M4C RXM021FP
RXZE2M114 RXM021RB
RXZE2M114M RXM040W
RXZE2M2N RXM041BN7
RXZE2M4N RXM041FU7
RXZE2S108M
RXZE2S111M
RXZE2S114M
RXZE2S114S
RXZE14P

RELAYS03-02-200315 ORIGINAL DECLARATION, NO TRANSLATION WITHOUT WRITTEN AUTHORISATION Page 3 of 3


EU DECLARATION OF CONFORMITY
We: Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92506 – France

Hereby declare under our sole responsibility that the products:


Trademark Schneider Electric
Product, Type, Model Electromechanical plug-in relays – RXM miniature relays, RXZE relay sockets and
RXM02/RXM04 protection modules
List of reference and options See Annex
are in conformity with the requirements of the following directives and conformity was checked in accordance with the
following standards.
Directive Harmonized and/or International standards
LV Directive 2014/35/EU Electromechanical elementary relays - Part 1: General requirements
EN 61810-1:2015/AC:2017/AC:2018 and IEC 61810-1:2015/COR1:2017/COR2:2018
Connectors - Safety requirements and test
EN 61984:2009 and IEC 61984:2008
Connecting devices - Electrical copper conductors - Safety requirements for screw-
type and screwless-type clamping units - Part 1: General requirements and particular
requirements for clamping units for conductors from 0,2 mm2 up to 35 mm2
(included)
EN 60999-1:2000 and IEC 60999-1:1999
RoHS Directive 2011/65/EU EN 50581:2012
(Inclusive of Directive (EU) Technical documentation for the assessment of electrical and electronic
2015/863) products with respect to the restriction of hazardous substances

Subject to correct installation, maintenance and use conforming to its intended purpose, to the applicable regulations and
standards, to the supplier's instructions and to accepted rules of the art.
This declaration becomes invalid in the case of any modification to the products not authorized by us.

Issued at Carros, France: 15 March 2020

Alain BERNERD
Vice President
Customer Satisfaction and Quality
Industrial Automation

RELAYS03-02-200315 ORIGINAL DECLARATION, NO TRANSLATION WITHOUT WRITTEN AUTHORISATION Page 1 of 3


EU DECLARATION OF CONFORMITY
Annex - Table of product references: RXM relays
RXM2AB1B7 RXM2LB2BD RXM4AB3FD RXM4LB1P7
RXM2AB1BD RXM2LB2CD RXM4AB3GD RXM4LB2B7
RXM2AB1E7 RXM2LB2ED RXM4AB3JD RXM4LB2BD
RXM2AB1ED RXM2LB2F7 RXM4AB3P7 RXM4LB2CD
RXM2AB1F7 RXM2LB2FD RXM4CB1B7 RXM4LB2ED
RXM2AB1FD RXM2LB2JD RXM4CB1BD RXM4LB2F7
RXM2AB1G7 RXM2LB2P7 RXM4CB1E7 RXM4LB2FD
RXM2AB1GD RXM2NB3B7 RXM4CB1ED RXM4LB2JD
RXM2AB1HD RXM2NB3BD RXM4CB1F7 RXM4LB2P7
RXM2AB1JD RXM2NB3F7 RXM4CB1FD RXM4NB3B7
RXM2AB1MD RXM2NB3FD RXM4CB1JD RXM4NB3BD
RXM2AB1ND RXM2NB3JD RXM4CB1MD RXM4NB3F7
RXM2AB1P7 RXM2NB3MD RXM4CB1P7 RXM4NB3FD
RXM2AB1U7 RXM2NB3P7 RXM4CB2B7 RXM4NB3JD
RXM2AB1UD RXM3AB1B7 RXM4CB2BD RXM4NB3MD
RXM2AB2B7 RXM3AB1BD RXM4CB2E7 RXM4NB3P7
RXM2AB2BD RXM3AB1E7 RXM4CB2ED
RXM2AB2E7 RXM3AB1ED RXM4CB2F7
RXM2AB2ED RXM3AB1F7 RXM4CB2FD
RXM2AB2F7 RXM3AB1FD RXM4CB2JD
RXM2AB2FD RXM3AB1JD RXM4CB2P7
RXM2AB2JD RXM3AB1P7 RXM4GB1B7
RXM2AB2P7 RXM3AB2B7 RXM4GB1BD
RXM2AB3B7 RXM3AB2BD RXM4GB1E7
RXM2AB3BD RXM3AB2E7 RXM4GB1ED
RXM2AB3E7 RXM3AB2ED RXM4GB1F7
RXM2AB3ED RXM3AB2F7 RXM4GB1FD
RXM2AB3F7 RXM3AB2FD RXM4GB1JD
RXM2AB3FD RXM3AB2JD RXM4GB1P7
RXM2AB3JD RXM3AB2P7 RXM4GB2B7
RXM2AB3P7 RXM4AB1B7 RXM4GB2BD
RXM2CB1B7 RXM4AB1BD RXM4GB2E7
RXM2CB1BD RXM4AB1E7 RXM4GB2ED
RXM2CB1E7 RXM4AB1ED RXM4GB2F7
RXM2CB1ED RXM4AB1F7 RXM4GB2FD
RXM2CB1F7 RXM4AB1FD RXM4GB2GD
RXM2CB1FD RXM4AB1JD RXM4GB2JD
RXM2CB1JD RXM4AB1MD RXM4GB2MD
RXM2CB1P7 RXM4AB1P7 RXM4GB2ND
RXM2CB2B7 RXM4AB1U7 RXM4GB2P7
RXM2CB2BD RXM4AB2B7 RXM4GB2U7
RXM2CB2E7 RXM4AB2BD RXM4GB3B7
RXM2CB2ED RXM4AB2E7 RXM4GB3BD
RXM2CB2F7 RXM4AB2ED RXM4GB3E7
RXM2CB2FD RXM4AB2F7 RXM4GB3ED
RXM2CB2JD RXM4AB2FD RXM4GB3F7
RXM2CB2P7 RXM4AB2GD RXM4GB3FD
RXM2LB1B7 RXM4AB2JD RXM4GB3JD
RXM2LB1BD RXM4AB2P7 RXM4GB3P7
RXM2LB1ED RXM4AB3B7 RXM4LB1B7
RXM2LB1F7 RXM4AB3BD RXM4LB1BD
RXM2LB1JD RXM4AB3E7 RXM4LB1ED
RXM2LB1P7 RXM4AB3ED RXM4LB1F7
RXM2LB2B7 RXM4AB3F7 RXM4LB1JD

RELAYS03-02-200315 ORIGINAL DECLARATION, NO TRANSLATION WITHOUT WRITTEN AUTHORISATION Page 2 of 3


EU DECLARATION OF CONFORMITY

Annex - Table of product references: RXZE sockets and RXM02/RXM04 protection modules
RXZE1M2C RXM021BN
RXZE1M4C RXM021FP
RXZE2M114 RXM021RB
RXZE2M114M RXM040W
RXZE2M2N RXM041BN7
RXZE2M4N RXM041FU7
RXZE2S108M
RXZE2S111M
RXZE2S114M
RXZE2S114S
RXZE14P

RELAYS03-02-200315 ORIGINAL DECLARATION, NO TRANSLATION WITHOUT WRITTEN AUTHORISATION Page 3 of 3


CUSTOMER : PURITA WATER SOLUTIONS PVT. LTD.
END USER : BHARTIYA RAIL BIJLEE COMPANY LTD.

PROJECT : NABINAGAR THERMAL POWER PROJECT(4X250MW)

CV

DOCUMENT STATUS:

PRELIMINARY FOR INFORMATION FOR APPROVAL AS BUILT

GASKET TYPE TEST REPORT


Technische
Lieferspezifikationen
Technical specifications for delivery
Artikelbezeichnung: Rechteckprofil
Article designation: Rectangular Gasket

Artikelnummer : 226-1005 2003 2005 2505 Stand: 06/09


Article number Status
Werkstoff - material: CR geschlossenzellig
CR closed

Farbe - colour: schwarz - black

Maße (BxH) – size (WxT): 10 x 5 mm


3
Rohdichte – density: 150 - 200 kg/cm

Einsatztemperatur – -40°C - +115°C kurzzeitig bis +130


operation temperature: -40°C - +115°C short time to +130

Stauchhärte 25% – ASTM D 1056, 35 - 65 (Ø45) kPa


compression deflection 25%:

Shore Härte – 38 – 55 Shore 00


shore hardness:

Wasseraufnahme – ASTM D 1056, < 5 (Ø1,1) %


water absorption:
Zugfestigkeit – DIN 53571, >500 (Ø780) kPa
tensile strength:
Bruchdehnung – DIN 53571, >100 (Ø134) %
liniar shrinkage:
Lineare Schrumpfung – 22h / 70° C, <7 (Ø4) %
linear shrinkage:
Druckverformungsrest – ASTM D 1056 50%/22h/23°C24h, ≤25 (Ø18,7) %
compression set:

Beständigkeit gegen – Ozon gut, Öl/Benzin gut, Lösungsmittel gut, Säuren/Laugen gut,
resistance to: Alterung sehr gut
Ozone good 200ppm/30°C48h without cracking, Oil/Petrol good,
Solvents good, Acids/bases good, Weathering good

Besondere Eigenschaften – bei Kupfer- und Silberkontakt: ätzend Lackdifferenz: keine Fleckenbildung
specifice properties: corrosive effect on copper and silver: corrosive paint staining: non staining

Erfüllt die Normen – Brandverhalten nach MVSS 302: Brennrate <100mm/min


standards: Brandverhalten nach UL 94 HF 1, Brandverhalten nach DIN 4102 B2
MVSS 302: burning rate <100mm/min, UL 94 HF 1 Conform

Diese Angaben wurden sorgfältig ermittelt und dienen der Beratung, ohne Rechtsverbindlichkeit.
This information on synthetic rubber foam is presented to our best knowledge. All test data are average values and should be
considered as guidline, not as a specification.

Die Daten beziehen sich auf ungespannte, unbelastete Teile. Diese Angaben gestalten nur eine Vorauswahl, bei wichtigen oder
extremen Anwendungsfällen müssen unbedingt praktische Versuche erfolgen.
The data refer to parts neither strained nor stressed. The indications above only allow a pre-selection. In important or extreme
application practical tests have to be performed absolutely.
Technische
Lieferspezifikationen
Technical specifications for
delivery

Artikelbezeichnung: Klebeband
Article designation: Adhesivetape

Artikelnummer : Stand: 06/07


Article number Status

Werkstoff - material: modifiziertes Gewebe


modified acrylate

Träger - carrier: Gittergelege - scrim

Abdeckung - liner: PO-Folie weiss - PO-foil white

Kleberdicke - thickness: 0,09 mm


2
Gewicht - weight: Auftragsmenge 90 g/m

Klebkraft - adhesion: Afera 4001 20 N/25 mm

Temperaturbereich - -40°C - +100°C


temperature range:

Besondere Eigenschaften - Doppelseitiges Klebeband, sehr hohe Anfangsklebekraft,


specifice properties: gute Temperatur-, UV-, Alterungsbeständigkeit
high direct adhesion, good temperatur resistance,
good UV resitance, good weathering

Anwendung - Klebt auf fast allen Materialien, geeignet auch für schwierige
Application: Oberflächen wie Schäumen und PE-Folien
suitable for nonpolar PE-foils and cellular materials

Diese Angaben wurden sorgfälltig ermittelt und dienen der Beratung, ohne Rechtsverbindlichkeit.
This information on synthetic rubber foam is presented to our best knowledge. All test data are average values and should be
considered as guidline, not as a specification.

Die Daten beziehen sich auf ungespannte, unbelastete Teile. Diese Angaben gestalten nur eine Vorauswahl, bei wichtigen oder
extremen Anwendungsfällen müssen unbedingt praktische Versuche erfolgen.
The data refer to parts neither strained nor stressed. The indications above only allow a pre-selection. In important or extreme
application practical tests have to be performed absolutely.
Sicherheitsdatenblatt
gemäß 91/155 EWG - Stand.19.06.2007
Safety Data Sheet
according to 91/155 EEC- Status: 19.06.2007

1. Stoff / Zubereitung – und Firmenbezeichnung


Bezeichnung des Stoffes oder der Zubereitung:
Doppelseitiges Klebeband
Herausgeber des Datenblattes:
DIRAK GmbH
D – 58256 Ennepetal
Königsfelder Str. 1
Telefon: 0 23 33/837-0
1. Information about the product:
Double sided adhesive tape
Publisher of the Data Sheet:
DIRAK GmbH
58256 Ennepetal
Königsfelder Str. 1
Phone: +49 (0) 23 33/837-0

2. Zusammensetzung / Angaben zu Bestandteilen


Chemische Charakterisierung:
Träger: PES Gittergelege
Schutzfolie: Trennschichtfolie PP, weiß
Kleber: Acrylestersäure, polymisierte Dispersion mit Harzen und brennbaren Füllstoffen
Geruch: charakteristisch
2. Composition/information on ingredients
Chemical name:
Substrate material: PES scrim
Protective film: separating layer PP, white
Adhesive: ethyl acrylate, polymerized dispersion with resin and combustible fillers
Odor: characteristic

3. Mögliche Gefahren
Hinweis auf besondere Gefahren: keine
Besondere Gefahrenhinweise für Mensch und Umwelt: nicht relevant
3. Hazards identification
Special risks: none
Special environmental and health risks: not applicable

4. Erste Hilfe Maßnahmen


nicht relevant
4. First aid measures
not applicable

5. Maßnahmen zur Brandbekämpfung


geeignete Löschmittel: Sprühwasser, Trockenlöschmittel, Schaum
5. Fire fight measures
Suitable extinguishing media: water spray, solid extinguishing agent, foam

6. Maßnahmen bei unbeabsichtigter Freisetzung


nicht relevant
6. Accidental release measures
not applicable

7. Handhabung und Lagerung


trocken und nicht über 60°C lagern, entzündlich durch offene Flamme
7. Handling and storage
dry, not above 60 °C, inflammatory via unshielded flame
8. Expositionsbegrenzung und persönliche Schutzausrüstung
Das Produkt unterliegt nicht den Bestimmungen der VbF
Die Möglichkeit einer Selbstentzündung ist weitgehend auszuschließen.
8. Exposure controls/personal protection
The product is not subject to the provisions of the VbF (regulation on inflammable liquids)
Possibility of a spontaneous combustion can be more or less ruled out

9. Physikalische und Chemische Eigenschaften


Sicherheitsrelevante Daten:
Zündtemperatur: 250 – 500°C
Dichte bei 0,8 – 1,0 g/cm³
andere Daten sind nicht vorhanden oder relevant
9. Physical and chemical properties:
Security relevant data:
Ignition temperature: 250 – 500°C
Density at 0,8 – 1,0 g/cm³
No other data available or relevant

10. Stabilität und Reaktivität


Daten sind nicht vorhanden oder nicht relevant
10. Stability and reactivity:
No other data available or relevant

11. Angaben zur Toxikologie


Daten sind nicht vorhanden oder nicht relevant
11. Toxicological information:
No other data available or relevant

12. Angaben zur Ökologie


Kleber, Träger, und Liner sind weitestgehend Lösungsmittel -, Chlorid -, und Schwermetallfrei.
Daher sind bei der Entsorgung keine speziellen Maßnahmen erforderlich.
Das Produkt ist als nicht umweltgefährdent einzustufen.
12. Ecological information
Adhesive, substrate material and liner are to the greatest possible extent solvents
Chloride-free, free of heavy metals
No special measures required on disposal
The products is no classified as being dangerous to the environment

13. Hinweise zur Entsorgung


Kleinere Mengen sind als Hausmüll zu behandeln. Größere Mengen als normaler Industriemüll.
13. Disposal considerations
Small amounts can be treated like household waste.
Bigger amounts can be treated like industrial waste.

14. Angaben zum Transport


kein Gefahrengut im Sinne der Transportvorschriften
14. Transport information
No hazardous material in accordance with transport rules and regulations.

15. Vorschriften
Kennzeichnung: ist nach Gefahrstoff – Verordnung vom 01.10.1986 nicht kennzeichnungspflichtig.
15. Regulatory information
Labeling: Not subject to mandatory labeling, according to German Hazardous Substances Ordinance of
01.10.1986

16. Sonstige Anmerkungen


Dieses Sicherheitsdatenblatt ist eine Abschrift der Daten des Original Sicherheitsdatenblattes.
Die Angaben wurden ohne Änderung übertragen.
16. Other information
This safety data sheet is a transcript of the data of the original safety data sheet.
The data were transmitted without change.
CUSTOMER : PURITA WATER SOLUTIONS PVT. LTD.
END USER : BHARTIYA RAIL BIJLEE COMPANY LTD.

PROJECT : NABINAGAR THERMAL POWER PROJECT(4X250MW)

CV

DOCUMENT STATUS:

PRELIMINARY FOR INFORMATION FOR APPROVAL AS BUILT

PANEL MATERIAL TYPE TEST REPORT


CUSTOMER : PURITA WATER SOLUTIONS PVT. LTD.
END USER : BHARTIYA RAIL BIJLEE COMPANY LTD.

PROJECT : NABINAGAR THERMAL POWER PROJECT(4X250MW)

DOCUMENT STATUS:

PRELIMINARY FOR INFORMATION FOR APPROVAL AS BUILT

PANEL IP TYPE TEST REPORT


ELECTRICAL RESEARCH AND DEVELOPMENT ASSOCIATION
(Accredited by the National Accreditation BoardforTesting and Calibration Laboratories,Govt.of India)
ERDA Road, Makarpura Industrial Estate, Vadodara-390 010, India.
EPABX : +91 (0265) 2642942,2642964,2642377,3043128 / 29 / 30 / 31 / 33
U U
Fax : +91 (0265) 2638382
Certificate No. :T-0071
E-mail : erdaQerda.org
Web : http://www.erda.org

SHEET 06 OF 06

TEST REPORT NO.: RP-1617-049661


DATE: 25/01/2017

U
PHOTOGRAPH NO.: 1 6 1 7 - 0 1 8 0 1 3 / 0 0 1 7 9 6 7 3 / C

LT PANEL
CUSTOMER : PURITA WATER SOLUTIONS PVT. LTD.
END USER : BHARTIYA RAIL BIJLEE COMPANY LTD.

PROJECT : NABINAGAR THERMAL POWER PROJECT(4X250MW)

DOCUMENT STATUS:

PRELIMINARY FOR INFORMATION FOR APPROVAL AS BUILT

PANEL PANEL COATING TYPE TEST REPORT


CUSTOMER : PURITA WATER SOLUTIONS PVT. LTD.
END USER : BHARTIYA RAIL BIJLEE COMPANY LTD.

PROJECT : NABINAGAR THERMAL POWER PROJECT(4X250MW)

DOCUMENT STATUS:

PRELIMINARY FOR INFORMATION FOR APPROVAL AS BUILT

SHORT CIRCUIT TYPE TEST REPORT


CUSTOMER : PURITA WATER SOLUTIONS PVT. LTD.
END USER : BHARTIYA RAIL BIJLEE COMPANY LTD.

PROJECT : NABINAGAR THERMAL POWER PROJECT(4X250MW)

CV

DOCUMENT STATUS:

PRELIMINARY FOR INFORMATION FOR APPROVAL AS BUILT

BUSBAR TEST REPORT


Spec. H-2(Z) Issue 2011 Page 1/5

Hongshang
Hongshang Heat Shrinkable Materials Co., Ltd Issue 2011

No.9 Qilin Rd, Nankeng Cun, Bantian, Longgang, Shenzhen Date 2011-9-13

China, 518129 Spec. H-2(Z)

TECHNICAL REPORT ON

H-2(Z) Environment Friendly Flexible


Flame Retardant Heat Shrinkable Tubing

Hongshang Heat Shrinkable Materials Co., Ltd


Spec. H-2(Z) Issue 2011 Page 2/5

1 SCOPE
This specification covers the requirements for one type of flexible electrical
insulating, extruded tubing whose diameter will reduce to a predetermined size
upon the application of heat in excess of 70°C .This tubing meets the
requirements of UL 224 with a continuous operating temperature range of -55°C
to 125°C. H-2(Z) is free of any substances including polybrominated biphenyls
(PBB) and polybrominated biphenyl oxides (PBBO) and meet the requirement of
Latest RoHS ..

2 Applicable Documents
This specification takes precedence over documents referenced herein. Unless
otherwise specified, the latest issue of referenced documents applies. The
following documents form a part of this specification to the extent specified herein.
UL 224 Extruded Insulating Tubing
CSA CANADIAN STANDARDS ASSOCIATION
C22.2 No.198.1 Extruded Insulating Tubing
ASTM D 2671 Standard Test Method for Heat Shrinkable Tubing for
Electrical Use
IEC 60093-1980 Methods of Test for Volume Resistance and Surface
Resistance of Solid Electrical Insulating Materials
3 REQUIREMENTS

3.1 Materials
H-2(Z) flexible heat shrinkable tubing is made from radiation crosslinked
polyolefin. Specifically designed formulation makes the tubing to have outstanding
physical, chemical and electrical properties, and also meet the requirement of
RoHS and other environment concerned standards.

3.2 Color
The Standard colors for the tubing shall be black, red, blue, yellow, green and
white

3.3 Properties
The tubing shall meet all requirements of Table 1

3.4 Test Procedures


Unless otherwise specified, tests shall be performed on specimens which have
been fully recovered by conditioning for 3 minutes in a 200 ± 2 °C oven. All
ovens should be the mechanical convection type

3.4.1 Dimensions and Longitudinal Change


Three 150-mm specimens of tubing, as supplied, shall be measured for length
± 1 mm and inside diameter in accordance with ASTM D 2671, conditioned for
Spec. H-2(Z) Issue 2011 Page 3/5

3 minutes in a 200 ± 2°C oven, cooled to 23 ± 3°C and then re-measured.


Longitudinal change (LC) shall be calculated as follows:

LC = ( L1 – L0)/L0 x 100

LC = longitudinal change
L0 = length before shrinkage
L1 = length after shrinkage

3.4.2 Eccentricity
Perform the test in accordance with UL 224.
Eccentricity % = ( 1 – W1/W2) x 100

W1 = minimum wall thickness


W2 = maximum wall thickness

3.4.3 Tensile Strength and Ultimate Elongation


Three specimens of tubing shall be tested for tensile strength and ultimate
elongation in accordance with ASTM D 2671. The rate of jaw separation shall
be 50.8mm per minute.

3.4.4 Volume resistance


Perform the test in accordance with IEC 93

3.4.5 Dielectric strength


Perform the test in accordance with IEC 243

3.4.6 Water absorption


Perform the test in accordance with ISO 62 at the condition of 24 hrs. /23 ℃.

3.4.7 Heat shock


Perform the test in accordance with UL 224. The specimen may be placed
horizontally in the oven at 250 ℃ for 4 hours. While in the oven and after removal
from the oven, the specimen shall be examined for evidence of cracking.

3.4.8 Thermal aging


Perform the test in accordance with UL 224. Aging condition shall be 158℃ for
168 hrs.

3.4.9 Flammability teat


Perform the test in accordance with UL 224 VW-1 or ASTM D 2671 procedure C.

3.4.10 Cold bend test


Perform the test in accordance with UL 224. at the condition of -30℃/1 hrs
Spec. H-2(Z) Issue 2011 Page 4/5

3.4.11 Fluid resistance


Not applicable.

3.4.12 Copper corrosion test


Perform the test in accordance with UL 224. The surface of copper tube shall be
no sign of corrosion except for thermal oxidation.

Table 1 Requirements

Property Unit Required Value Test Value


Shrinking properties
Longitudinal Changes % ±5% 0 to -3 %
Eccentricity % Max. 30% 10 to 25 %
Physical properties
Tensile strength MPa Min. 10.3 MPa Min. 11MPa
Elongation % Min. 200% Min 400 %
After aging at 158℃
/168 hrs
Tensile strength Mpa Remain 70% Min. 12 Mpa
Ultimate Elongation % Min. 100% Min. 250%
Heat shock No cracking, flowing, No cracking, flowing,
250℃ / 4 hrs dropping dropping
Cold bend test No cracking No cracking
-30℃ / 1 hrs
Electrical properties
Dielectric strength kV/mm Min. 19.7 32
14
Volume resistance Ω.cm Min. 10 1014
Chemical properties
Water absorption % Max. 0.5 0.2
Copper corrosion No corrosion No corrosion
Flammability VW-1 Pass Pass
Spec. H-2(Z) Issue 2011 Page 5/5

3.5 Shrinking curve

Checked by: Zeng Wan Date: 2011-9-14

Approved by: Zhong Xiaoguang Date: 2011-9-15


RIGIL TECHNO INDIA PVT.LTD

Hongshang Rigil Techno India Pvt. Ltd.


H-2(Z) :Environment Friendly Flame Retardant Flexible Thin Wall Polyolefin
Heat Shrinkable Tubing

Applications
Widely used for electrical insulation and protects in-line components, disconnect
terminals, and splices with its high strength and excellent resilience. Bundles wires
for very flexible light-duty harnesses. Identifies or color-codes, wires, cables,
terminals, and components.

Features/Benefits
• Free from Environment harmful substance such as PBBS, PBBES, PBBOS and
toxic heavy metal compounds in its components.
• Low shrunk temperature reduces installation time and the risk of damage to
temperature- sensitive components.
• Very flexible, does not easily wrinkle when bent.
• Higher temperature rating, better thermal stability and higher resistance to
physical abuse than non-cross linked materials.

Shrink Ratio: 2:1

Minimum Shrink Temperature: 70O C


Minimum Full Recovery Temperature: 100O C

Approvals: CRU US 125O C VW -1 600V File No. E204071

Material: RoHS Compliant, Meets Standards of Sony- SS-00259

Standard Color: Black, white, blue, yellow, green, red, and grey.
Other colors available on request

Technical Specifications

Properties Method of test Value


Operating Temperature UL 224 -55O C to 125O C
Tensile Strength ASTM D 2671 14 Mpa
Ultimate Elongation ASTM D 2671 400%
Longitudinal Shrinkage UL 224 +5 %
Eccentricity ASTM D 2671 < 20%
Heat Aging 158O C 168 hrs 14Mpa
Tensile Strength 350%
Ultimate Elongation
Flammability VW-1 Pass
Dielectric Strength IEC 243 20 kV/mm
Volume Resistance IEC 93 1014 ohm cm
Copper Stability ASTM D 2671 Pass

RTIL/PRODUCTSPECS/2005 1
RIGIL TECHNO INDIA PVT.LTD

H-2 (Z) Product dimensions (metric)

Normal As supplied mm After Recovered mm Standard


Size Inside Wall Inside Wall Length
Diameter Thickness Diameter Thickness m/Spool
Normal Max. Min.
Ф 1.0 1.5 ± 0.2 0.18 0.50 0.33 200
Ф 1.5 2.0 ± 0.2 0.18 0.75 0.36 200
Ф 2.0 2.7 ± 0.2 0.20 1.00 0.44 200
Ф 2.5 3.1 ± 0.2 0.25 1.25 0.44 200
Ф 3.0 3.7 ± 0.3 0.25 1.50 0.44 200
Ф 3.5 4.0 ± 0.3 0.25 1.75 0.44 200
Ф 4.0 4.7 ± 0.3 0.25 2.00 0.44 200
Ф 5.0 5.6 ± 0.3 0.25 2.50 0.56 100
Ф 6.0 6.8 ± 0.3 0.25 3.00 0.56 100
Ф 7.0 7.7 ± 0.3 0.25 3.50 0.56 100
Ф 8.0 8.8 ± 0.3 0.30 4.00 0.56 100
Ф 9.0 9.8 ± 0.3 0.30 4.50 0.56 50
Ф 10.0 10.7 ± 0.4 0.30 5.00 0.56 50
Ф 11.0 11.7 ± 0.4 0.30 5.50 0.56 50
Ф 12.0 12.7 ± 0.4 0.30 6.00 0.56 50
Ф 13.0 13.7 ± 0.4 0.35 6.50 0.65 50
Ф 14.0 14.7 ± 0.4 0.35 7.00 0.69 50
Ф 15.0 15.7 ± 0.5 0.35 7.50 0.69 50
Ф 16.0 16.7 ± 0.5 0.35 8.00 0.69 50
Ф 18.0 19.0 ± 0.5 0.40 9.00 0.80 50
Ф 20.0 21.4 ± 0.5 0.40 10.00 0.80 50
Ф 22.0 23.4 ± 0.6 0.45 11.00 0.80 50
Ф 25.0 26.5 ± 0.8 0.45 12.50 0.90 50
Ф 28.0 29.5 ± 0.8 0.45 14.00 0.90 50
Ф 30.0 31.5 ± 0.8 0.45 15.00 0.90 50
Ф 35.0 36.5 ± 0.8 0.50 17.50 0.90 50
Ф 40.0 42.0 ± 0.8 0.50 20.00 1.00 50
Ф 50.0 52.0 ± 0.8 0.50 25.00 1.00 50
Ф 60.0 62.0 ± 1.0 0.50 30.00 1.00 30
Ф 70.0 72.0 ± 1.0 0.50 35.00 1.20 30
Ф 80.0 82.0 ± 1.0 0.55 40.00 1.20 30
Ф 100 102.0 ± 1.0 0.55 50.00 1.30 30
Ф 120 121.0 ± 1.0 0.55 60.00 1.30 15
Ф 150 151.0 ± 1.0 0.55 75.00 1.30 15

RTIL/PRODUCTSPECS/2005 2
RIGIL TECHNO INDIA PVT.LTD

H-2 (Z) Product dimensions (inch)


Normal Size As supplied mm After Recovered mm Standard
Length
mm inch Inside Wall Inside Wall m/Spool
Diameter Thickness Diameter Thickness
Normal Max. Min.
Ф 1.2 3/64 1.6 ± 0.2 0.18 0.60 0.33 200
Ф 1.6 1/16 2.0 ± 0.2 0.18 0.80 0.36 200
Ф 2.4 3/32 3.0 ± 0.2 0.25 1.20 0.44 200
Ф 3.2 1/8 3.7 ± 0.3 0.25 1.60 0.44 200
Ф 4.8 3/16 5.2 ± 0.3 0.25 2.40 0.50 100
Ф 6.4 1/4 6.8 ± 0.3 0.30 3.20 0.50 100
Ф 9.5 3/8 10.7 ± 0.4 0.30 4.70 0.56 50
Ф 12.7 1/2 13.7± 0.4 0.30 6.40 0.69 50
Ф 19.1 3/4 20.4 ± 0.4 0.40 9.50 0.89 50
Ф25.4 1 26.5 ± 0.4 0.45 12.70 0.89 50
Ф38.1 1 1/2 41.0 ± 0.8 0.50 19.10 1.10 25
Ф50.8 2 52.0 ± 1.0 0.50 25.40 1.15 25
Ф76.2 3 82.0 ± 1.0 0.55 38.10 1.20 15
Ф102 4 104 ± 1.0 0.55 50.80 1.20 15

Size selection
Always order the largest that will shrink snugly over the component to be covered.
Special order sizes are available on request.

Standard Packaging
On Spools

Marking
Marked with UL/CSA/-F-legends

Ordering Description
Specify Product name, Size, Color.

RTIL/PRODUCTSPECS/2005 3