UL Subject 2775 Test Summary Electrical Units
UL Subject 2775 Test Summary Electrical Units
Markings Review Review of labels and markings for compliance with Completed successfully
Standard.
Inspection of Review of facility, records keeping, procedures, and Completed successfully
Manufacturing production methods.
facility and process
Gas Chromatograph Monitor gas/effluent chemical output. Completed successfully
Manual Review Review of Design, Installation, Maintenance Manual and Completed successfully
Owner’s Manual for compliance with Standard.
UL 33 Strength of Ten assemblies subjected to a load 5 times the load on the Completed successfully
Heat Response thermal element for 150 hours. Element cannot deform by
Element more than accepted criteria.
Operating Ten assemblies subjected to liquid silicone bath at Completed successfully
Temperature (Bath) temperature. Must function to specification.
Sensitivity - Oven Ten assemblies plunged into heated air flow at 8.33 Completed successfully
feet/sec. All must activate within specified parameters per
UL 33.
90 day High Five samples subjected to temperature exposure (10 Completed successfully
Temperature degree < rated) for 90 days. Cannot function. After
passing units are subjected to Sensitivity Oven test and
must function within specified parameters.
10 day Corrosion Five assemblies subjected to 10 day Salt Spray, Five Completed successfully
assemblies to 10 day Hydrogen Sulfide Atmosphere, and
Five assemblies to Hydrogen Sulfide/CO2 Atmosphere.
After exposure all are subjected to Sensitivity Oven test
and must function within specified parameters.
Fire Test Each unit is placed in the most disadvantageous position Completed successfully on 30T,
in a chamber with 1% un-closeable openings and 60T, 100T. 250T and 500T test
subjected to large scale heptane fire. Two tests are run – chambers are under construction
1 with the pan fire in the corner in front of the opening and will be completed in the next
and 1 with the pan placed in the center. Unit must activate quarter.
and extinguish the fire within 60 seconds.