The document discusses the design of low speed turbo alternators. It provides equations to calculate the diameter (D) and length (L) of the alternator based on factors like peripheral speed (V), number of poles (P), specific loading (Bav), and kVA rating (Q). It also discusses estimating the length of the air gap (lg) using ratios like lg/τ and calculating the mmf required for the air gap. Flow charts are provided showing the steps to determine the main dimensions and overall design of the turbo alternator.
The document discusses the design of low speed turbo alternators. It provides equations to calculate the diameter (D) and length (L) of the alternator based on factors like peripheral speed (V), number of poles (P), specific loading (Bav), and kVA rating (Q). It also discusses estimating the length of the air gap (lg) using ratios like lg/τ and calculating the mmf required for the air gap. Flow charts are provided showing the steps to determine the main dimensions and overall design of the turbo alternator.
The document discusses the design of low speed turbo alternators. It provides equations to calculate the diameter (D) and length (L) of the alternator based on factors like peripheral speed (V), number of poles (P), specific loading (Bav), and kVA rating (Q). It also discusses estimating the length of the air gap (lg) using ratios like lg/τ and calculating the mmf required for the air gap. Flow charts are provided showing the steps to determine the main dimensions and overall design of the turbo alternator.
1. 1. DESIGN OF TURBO ALTERNATORS DESIGN OF AC MACHINE PREET
PATEL(151310109032) 2. 2. CONTENT • Design of low speed and vertically operatedturbo alternator • Length of air-gap • Flow chart for overall design of alternator • Flow chart for overall design of alternator 2
3. 3. DESIGN OF TURBO ALTERNATOR
𝑉 = 𝜋𝐷𝑛 𝑠 𝐷 = 𝑉 𝜋𝑛 𝑠 In low speed turbo-alternator the diameter is limited by the maximum
peripheral speed, The output equation of ac machine can be modified by using the above relation. The kVA rating or Output kVA, Q = C0 𝐷2 𝐿𝑛 𝑠 where, C0 = 11 𝑎𝑐 𝐵𝑎𝑣 𝐾 𝑤 ∗ 10 − 3 Substitute , and the expression for C0 in the equation for Q Q = 11 𝑎𝑐 𝐵𝑎𝑣 𝐾 𝑤 𝑉 𝜋𝑛 𝑠 2 𝐿 ∗ 10 − 3 Q = 1.11 𝑎𝑐 𝐵 𝑎𝑣 𝐾 𝑤 𝐿 𝑉 𝑛 𝑠 2 ∗ 10 − 3 𝐷 = 𝑉 𝜋𝑛 𝑠 3 4. 4. The length of armature , L can be estimated from above equation. The value of specific loading for conventionally cooled alternators are, 𝐵 𝑎𝑣 = 0.54 𝑡𝑜 0.65 𝑊𝑏/𝑚2 𝑎𝑐 = 50000 𝑡𝑜 75000 𝑎𝑚𝑝. 𝑐𝑜𝑛𝑑 𝑚 The specific loading for conventionally cooled alternator are, 𝑃 𝑎𝑣 = 0.54 𝑡𝑜 0.65 𝑊𝑏/𝑚2 𝑎𝑐 = 180000 𝑡𝑜 200000 𝑎𝑚𝑝. 𝑐𝑜𝑛𝑑 𝑚 4 5. 5. LENGTH OF AIR-GAP The length of air gap can be estimated from the ratio lg/τ = 0.02 to 0.025. It can be also estimated from value of SCR. mmf for airgap = 800000 𝐾 𝑔 𝐵 𝑔 𝑙 𝑔 mmf for airgap = 80% of no load field mmf 𝐴𝑇 𝑓0 Here, ATf0=SCR x 𝐴𝑇 𝑎; where 𝐴𝑇 𝑎 = 𝑎𝑐(𝜏/2); Note:- 𝑆𝐶𝑅 = 0.5 𝑡𝑜 0.7 for turbo alternators and 𝐵 𝑔= 𝐵 𝑎𝑣/𝐾 𝑓 5 6. 6. On equating the two equation of mmf and mmf for airgap, 800000 𝐾 𝑔 𝐵 𝑔 𝑙 𝑔 = 0.8 𝐴𝑇 𝑓0 800000 𝐾 𝑔 𝐵 𝑔 𝑙 𝑔 = 0.8 x 𝑆𝐶𝑅 x 𝐴𝑇 𝑎 800000 𝐾 𝑔 𝐵 𝑔 𝑙 𝑔 = 0.8 x 𝑆𝐶𝑅 x 𝑎𝑐 x (𝜏/2) 𝑙 𝑔 = 0.8 x 𝑆𝐶𝑅 x 𝑎𝑐 (𝜏/2) 800000𝐾 𝑔 𝐵 𝑔 = 0.5 x 𝑆𝐶𝑅 x𝑎𝑐 x 𝜏 𝐾 𝑔 𝐵 𝑔x 106 6 7. 7. = 0.5 x𝑆𝐶𝑅 x𝑎𝑐 x 𝜏 x 10 − 6 𝐾 𝑔 𝐵 𝑎𝑣/𝐾 𝑓 The armature slot, winding, turns per phase and conductor design of turbo-alternator are same as that of salient pole alternator. 7 8. 8. FLOW CHART FOR MAIN DIMENSION OF ALTERNATOR start P=(120*f)/n 𝐶 𝑂 =11* 𝐾 𝑤* 𝐵𝑎𝑣*ac*10−3 𝐷2 L= Q/(𝐶 𝑂 *(n/60)) D=𝑉𝑎𝑚/(П ∗ 𝑛) L=(𝐷2 L)/𝐷2 τ= П*D/P Select the suitable value of D and L end 𝐵𝑎𝑣,KVA , n, f ,m, pf, ac, ƞ, 𝐾 𝑤 8 9. 9. FLOW CHART FOR OVERALL DESIGN OF ALTERNATOR 9 10. 10. THANK YOU