SCHEDULE OF WALL FINISHES :

MARK WALL DESCRIPTION


C B A C B A 150 mm THK. CHB EXTERIOR WALL WITH PLAIN CEMENT PLASTER
0.40mm THK. PRE-PAINTED AND PREFORMED G.I. END
EWF - 1 PAINTED FINISH
FLASHING SHEET WITH TOTAL COATED THICKNESS 0.40 mm THK. (BASE METAL THICKNESS) WITH TOTAL (SUBMIT COLOR SCHEMES FOR APPROVAL)
OF 0.43 - 0.45 mm THK. 4200 1225 THICKNESS OF 0.43 - 0.45 mm THK. (WITH PAINT)
1100 400 1100 CORRUGATED G.I. SHEET ROOFING 1100 1100 150 mm THK. CHB EXTERIOR WALL RAILING WITH PLAIN CEMENT
EWF - 1a PLASTER PAINTED FINISH

300

300
300
300
950 950
950 950 (SUBMIT COLOR SCHEMES FOR APPROVAL)
APEX LINE OF TRUSS APEX LINE OF TRUSS
100 mm THK. R.C. PARAPET WITH PLAIN CEMENT PLASTER PAINTED
EWF - 2 FINISH (SUBMIT COLOR SCHEMES FOR APPROVAL)
100 mm X 50 mm THK. PRE-CAST MOULDINGS WITH
PAINTED FINISH (ALL-AROUND)
R
100 mm THK./ 150 mm THK. CHB INTERIOR WALL WITH PLAIN CEMENT
3150

EWF-2 EWF-2 EWF-2 IWF - 1 PLASTER PAINTED FINISH


S E E T R U S S (SUBMIT COLOR SCHEMES FOR APPROVAL)
TOP LINE OF ROOF BEAM/ S E E T R U S S D E T A I L
D E T A I L

550 800

600 800
DECK ROOF

500
DECK ROOF FLOOR LEVEL TOP LINE OF ROOF BEAM 200 X 200 mm VITRIFIED GLAZED TILE WALL FINISH

1400

1400

1400
IWF - 2 R

431
(SIZE & OR COLOR FOR APPROVAL BY THE END-USER)

450
CEILING LINE (CORRIDOR) CEILING LINE (CLASSROOM) CEILING LINE (CORRIDOR) - TYPICAL ON ALL TOILET WALLS
TOILET CEILING LINE
W-3 4.5 mm THK. FIBER CEMENT BOARD WITH PAINTED IWF-1
IWF-2 LANDING EWF-1
3150

FINISH ON METAL FURRING CEILING NAILERS 19 mm SQUARE BARS (PAINTED FINISH) FULLY

2700
W-1

2700
2600

1000 500
D-2 D-4

900 600
1800 19 mm SQUARE BARS (PAINTED FINISH) FULLY D-1
(GRILLE SUPPORT FRAME)

1575
1500
(GRILLE SUPPORT FRAME)
SHE 400 CLASS ROOM LEGEND:

900
THIRD FLOOR LINE (CORRIDOR) CORRIDOR THIRD FLOOR LINE (CORRIDOR) CORRIDOR

TOILET CEILING LINE


IWF-2 W-3
EWF-1a
REINFORCED CONCRETE MEDIA AGUA WITH PAINTED
EWF-1a
R REVISION OF DRAWING DETAILS (1/23/2018)
1000 4.5 mm THK. FIBER CEMENT BOARD WITH
LANDING
R
1000 FINISH
3150

W-1 PAINTED FINISH ON METAL FURRING CEILING - REVISION OF CORRIDOR RAILING AT SECOND AND
2600

D-2 REINFORCED CONCRETE CANOPY WITH PAINTED NAILERS THIRD FLOOR ADAPTING THE PROPOSED DEPED DESIGN.
R
D-1
1575

FINISH
1500

PLAIN CEMENT FLOOR FINISH WITH INTEGRAL - REVISION OF STAIR RAILING FROM GROUND TO THIRD FLOOR,
SHE CLASS ROOM

900
800

SECOND FLOOR LINE (CORRIDOR) SECOND FLOOR LINE (CORRIDOR)


R MEMBRANE WATER PROOFING ADAPTING THE PROPOSED DEPED DESIGN
CORRIDOR CORRIDOR

700

700
- ADDITIONAL CANOPY (REINFORCED CONCRETE) ALONG MAIN
IWF-1 ENTRANCE, AS RECOMMENDED ON THE PROPOSED DEPED
TOILET CEILING LINE
EWF-1 IWF-1 REINFORCED CONCRETE CANOPY WITH PAINTED DESIGN
W-3
LANDING FINISH
3150

W-1 - ADDITIONAL MEDIA AGUA (REINFORCED CONCRETE SUN


2600

EWF-1 D-2 BREAKER) ABOVE WINDOW (W-1) AT REAR.


D-1
1575
1500

SHE CLASS ROOM - REVISION OF PARAPET WALL (R.C. GUTTER) FROM 100 mm THK.

900

600
GROUND FLOOR LINE (CORRIDOR) STORAGE RM. GROUND FLOOR LINE (CORRIDOR)
400

CORRIDOR RAMP CORRIDOR CHB TO 100 mm THK. REINFORCED CONCRETE.


300

300
- REVISION OF TOILET'S WALL & FLOOR FINISHES
NATURAL GRADE LINE NATURAL GRADE LINE - (IWF-2) FROM 200 X 200 mm VIT. GLAZED WALL TILES FINISH
IWF-2 TO 300 X 300 mm VIT. GLAZED TILES WALL FINISH
- (FL-3) FROM 200 X 200 mm VITRIFIED UNGLAZED TILES FLOOR
3150 3700 1200 (1 @ 900 mm, 1@ 700 mm HIGH FROM RAMP/ LANDING 2625 FINISH TO 300 X 300 mm VITRIFIED UNGLAZED TILES FLOOR
FINISH
7000 2500 1600 FLOOR LEVEL) 7000 2700 300
STEEL VERTICAL PIPE RAILING - ( SEE DETAIL)

2 CROSS SECTION 3 CROSS SECTION NOTE:


SCALE 1: 100 M. SCALE 1: 100 M.
A-6 A-6
- FOR SCHOOL BUILDING SITE LOCATED NEAR SEA BOARDS OR COASTAL
AREAS PRONE TO CORROSION ON G.I. ROOFING, CORRUGATED ASPHALT
ROOFING SHEETS (3.0 mm THK. - BITUMINOUS - CELLULOSE FIBRES CAN BE
USED AS ALTERNATE ROOFING MATERIALS).
- FOR COLUMNS AND BEAMS SIZES REFER TO STRUCTURAL SHOP DRAWINGS.

1 2 3 4 5 6 7 8 9 10 11 12 13
55000
5000 9000 9000 9000 9000 9000 5000
400 400

APEX LINE OF TRUSS


0.40mm THK. PRE-PAINTED AND PREFORMED G.I. END
0.40 mm THK. (BASE METAL THICKNESS) WITH TOTAL FLASHING G.I. SHEET WITH TOTAL COATED THICKNESS
THICKNESS OF 0.43 - 0.45 mm THK. (WITH PAINT) OF 0.43 - 0.45 mm THK.
CORRUGATED G.I. SHEET ROOFING
3150

EWF-2
TOP LINE OF ROOF BEAM/ S E E T R U S S D E T A I L
600 800

600 800
DECK ROOF FLOOR LEVEL DECK ROOF DECK ROOF

1400
TOILET CEILING LINE
W-3 W-3
3150

IWF-2
2600

2600
D-3a

1800
BD-1 BD-1 D-2 BD-1
1500

1500
SHE D-2 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 HE
THIRD FLOOR LINE (CORRIDOR)

550
TOILET CEILING LINE
W-3 W-3
3150

IWF-1
2600

2600
1800
BD-1 BD-1 D-3a D-2 BD-1
1500

1500
EWF-1 D-2
SHE W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 HE
SECOND FLOOR LINE (CORRIDOR)

550
TOILET CEILING LINE
W-3 W-3
3150

IWF-2
2600

D-3 D-3

1800
BD-1 BD-1 D-2 BD-1

1500
300

D-2
SHE CLASS ROOM HE
1000

1000
GROUND FLOOR LINE (CORRIDOR) W-1 CLASS ROOM W-1 W-1 W-1 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1 W-1 CLASS ROOM W-1
700

700
300

NATURAL GRADE
LINE

300 X 300 mm VITRIFIED GLAZED TILE COUNTER TOP FINISH 300 X 300 mm VITRIFIED GLAZED TILE
1000 5000 9000 9000 9000 9000 9000 5000 1000 COUNTER TOP FINISH (HAND WASH COUNTER)
(HAND WASH COUNTER)
- SIZE & OR COLOR FOR APPROVAL BY THE END-USER 400 400 - SIZE & OR COLOR FOR APPROVAL BY THE END-USER
EWF-1 IWF-1 IWF-1 IWF-1 EWF-1

1 LONGITUDINAL SECTION
SCALE 1: 100 M.
A-6

REPUBLIC OF THE PHILIPPINES ARCHITECTURAL CONCEPT:


PROJECT AND LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO. SHEET NO.
ARCHITECTURAL SECTION
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CROSS SECTION
CADD: SIGNED SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
MODIFIED STANDARD DPWH - DEPED LONGITUDINAL SECTION
BUREAU OF DESIGN THREE (3) STOREY, FIFTEEN (15)
SCHEDULE OF WALL FINISHES FRANCIS G. SERRANO
ARCHITECT III
APPROVED WITH SIGNATURE BOD
A-6
BUILDINGS DIVISION JOSEPHINE P. ISTURIS LEA N. DELFINADO GILBERTO S. REYES LEONOR M. BRIONES
CHECKED: SIGNED B 21 89
BONIFACIO DRIVE PORT AREA, MANILA
CLASSROOM SCHOOL BUILDING MARYLENE C. SISON CHIEF, BUILDINGS DIVISION OFFICER-IN-CHARGE