Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Appendix B Communication|ScrEdit Software User Manual

LG Master-K CNET DELTA

A. HMI factory settings

Baud rate: 38400, 8, None, 1. (RS-422)

Controller station number: 0.

Control area/state area: DW0 / DW10.

NOTE

1) HMI default setting is predefined for G6L-CUEC CNET communication module.

B. Definition of controller Read/Write address

Registers

Register Type Format Word No. Bit No. Data Size

I/O relay PWn n: 0 ~ 31 N/A Word


Auxiliary relay MWn n: 0 ~ 191 N/A Word
Keep relay KWn n: 0 ~ 31 N/A Word
Link relay LWn n: 0 ~ 63 N/A Word
Special relay FWn n: 0 ~ 63 N/A Word (Read Only)
Timer elapsed value TWn n: 0 ~ 255 N/A Word
Counter elapsed value CWn n: 0 ~ 255 N/A Word
Data register DWn n: 0 ~ 9999 N/A Word

Contacts

Contact type Format Word No. Bit No.


I/O relay PXnb n: 0 ~ 31 b: 0 ~ F
Auxiliary relay MXnb n: 0 ~ 191 b: 0 ~ F
Keep relay KXnb n: 0 ~ 31 b: 0 ~ F
Link relay LXnb n: 0 ~ 63 b: 0 ~ F
Special relay FXnb n: 0 ~ 63 b: 0 ~ F
Timer contact relay TXb N/A b: 0 ~ 255
Counter contact relay CXb N/A b: 0 ~ 255

B-50 Revision 05/30/2006, EH00


Appendix B Communication|ScrEdit Software User Manual

C. Connections (Connector Pinouts)

RS-422

via G6L-CUEC CNET communication module

DOP Controller
9 pin D-SUB male (RS-422) Cable Connector (RS-422)

RXD+ (2) SDA


RXD- (1) SDB
TXD- (4) RDA
TXD+ (3) RDB
GND (5) SG

RS-232

via LG-120S PLC (Master K)

DOP Controller Controller


9 pin D-SUB male 9 pin D-SUB male 9 pin D-SUB male
(RS-232) (RS-232) (RS-232)

RXD (2) (7) TXD


TXD (3) (4) RXD
GND (5) (5) GND

Top View