Professional Documents
Culture Documents
Intelligent Platforms-PAC - EU - TrgP3
Intelligent Platforms-PAC - EU - TrgP3
Intelligent Platforms
GE Intelligent Platforms-
Product Training
Part-3
Customer Training-Gulf
GEIPDXB02-A
This document is based upon information available at the time of its publication.
While efforts have been made to render accuracy to its content, the information
contained herein does not purport to cover all details or variations in hardware or
software, nor to provide for every possible contingency in connection with
installation, operation, and maintenance. Features may be described herein, which
are not present in all hardware and software systems. GE Intelligent Platforms, Inc.
assumes no obligation of notice to holders of this document with respect to changes
subsequently made. GE Intelligent Platforms, Inc. makes no representation or
warranty, expressed, implied, or statutory with respect to, and assumes no
responsibility for the accuracy, completeness, sufficiency, or usefulness of the
information contained herein. Proprietary information of GE Intelligent Platforms, Inc
furnished for Solution provider/customer use only. No other uses are authorized
without written permission of GE Intelligent Platforms, Inc.
Overview
GE Intelligent Platforms- Proficy HMI/SCADA- CIMPLICITY is the world’s number 1 best
selling HMI/SCADA (according to ARC). CIMPLICITY is a good fit for all HMI/SCADA
applications.
So from previous modules we have learnt many technology, features & major
applications of CIMPLICITY.
This module includes back up & restore methods of Proficy HMI/SCADA- CIMPLICITY
From the above cases discussed ,we need to back-up and restore our application
software of Proficy HMI/SCADA- CIMPLICITY. Incase of any abnormal failure of
hardware & software.
Back-up procedure:
Back Up Project
Open the project in the CIMPLICITY Workbench again
Click to “Project” along the top menu bar
Click on “Explore” from the drop down. This should open a Windows Explorer session.
Close the Workbench, but leave the Windows Explorer session open
In the Windows Explorer session click on “Up” button to move up one level in the
directory structure.
You can now copy the folder that contains your project safely to another location.
NOTE:
If you are using the Series 90 Triplex driver it is be suggested to also back up the
gef_cfg.ini file that is located in the Windows installation folder. When you restore the
project you can restore this file as well (as it contains the device names to TCP/IP
address mappings.
Restore Project
If the back-up project is properly done , then Restore of project is easy like copying
our standard file copy function for Microsoft Operating System.
alarm_help
arc
data*
lock
log
master*
screens*
scripts*
The directory names marked with a * above are absolutely required to reconstruct
your project data. if they are missing, it is time to go to a backup or start a new
project.
Once you have completed copying of the project , ensure that the folder do not have
“READ ONLY” check , if it is checked .it is required to uncheck.
3. run osql.exe -Usa (for the system administrator logon). The command line responds
by asking for the system administrator Password:
4. Type the system administrator password and press . The command line responds
with an OSQL environment, command prompt, and line number (e.g 1>)
6. Type Exit to exit the OSQL command environment. Close the command window.
Important Note: Restoring the master database requires that the database server
executable be started in single user mode. The following procedure outlines the steps
to starting the database server in single user mode.
1. Go to Start->Run and type sqlmangr.exe. The database service manager
application starts.
2. Verify that the server name selected matches the local computer name and that
the service name selected is SQL Server and that the service is currently running. If
the service is not running, skip step 3 and go on to step 4.
3. Click the Stop button. The application responds by indicating that the service has
stopped.
4. Verify that the Auto-start check box is checked if you want the service to start
when the OS starts.
5. Close the sqlmangr.exe application.
6. Go to Start->Run and type sqlservr.exe -m. The system responds by starting the
service in a command window with the single user mode on. Leave this command
window open while you go on to restoring the master database.
3. run osql.exe -Usa (for the system administrator logon). The command line responds
by asking for the system administrator Password:
4. Type the system administrator password and press . The command line responds
with an OSQL environment, command prompt, and line number (e.g 1>)
NOTE: If you used the single user mode procedure above, then the command window
running sqlservr.exe will close automatically. At the same time the command window
running the osql.exe will return to a normal windows command prompt.
6. Type Exit to exit the OSQL command environment. Close the command window.
8. Verify that the server name selected matches the local computer name and that
the service name selected is SQL Server and that the service is currently stopped. If
the service is running, skip step 9 and go on to step 10.
9. Click the Run button. The application responds by indicating that the service has
started.
10. Verify that the Auto-start check box is checked if you want the service to start
when the OS starts.
Note: For Historian Back-up & Restore please refer documentation file of “Proficy-
Historian “
Programming Software:
Backing up a project
In the Back Up dialog box that appears, navigate to the folder where you want the
backup saved.
The project is zipped (compressed into a single archive file), copied to the folder you
chose, and given a .ZIP extension.
Notes on backups
If you're not using a Proficy Change Management Server, you can add backed-up
projects to your computer with the File menu's Restore command.
If you are using Proficy Change Management, you can add backed-up projects to
your computer or a Server. For more information, see Adding a project.
To save and back up an open project (and continue to work with it):
Do one of the following:
In the Manager tab of the Navigator, right-click the open Machine Edition
project you want to save and back up and choose Save and Back up.
- or -
From the File menu, choose Save and Back up Project.
These menu options are unavailable if no project is open. You can back up a closed
project.
In the Back Up dialog box that appears, navigate to the folder where you want the
backup saved.
By default, backups are stored in the "C:\Program Files\GE Fanuc\Proficy Machine
Edition\Backup" directory.
Enter a name or use the default name and click OK.
The project is saved. See Notes on saving a project. Then it is zipped (compressed into
a single archive file), copied to the folder you chose, and given a .ZIP extension.
If you want to add an existing project stored elsewhere on the network or on your
computer, look for Machine Edition Files (*.SwxCF) in the Files of type box.
If you want to add a project that has been backed up, look for Zip Files (*.ZIP) in the
Files of type box.
When you've selected the project you want to add, click OK.
The project is copied (and unzipped, if necessary) to the Machine Edition area on your
computer. The original project is left untouched. Any changes you make to the project
will be performed on the new copy.
To delete a project:
Note: If you're using Proficy Change Management, see Deleting a Project from a
Server and Deleting a Local Copy of a Project.
In the Manager tab of the Navigator, right-click the Machine Edition project you
want to delete from the local computer.
-Select Destroy Project. The Destroy dialog box appears.
-You can delete a project only if the project is closed.
-Select Yes from the dialog box that appears. The project is deleted.
-Warning: This permanently removes the project from your system.
CPU LED’s
The seven CPU LEDs, visible through the module door, indicate the presence of power
and show the operating mode and diagnostic status of the CPU. They also indicate
the presence of faults, forces, and communications on the CPU’s two ports.
Power ON when the CPU is receiving 5V power from the power supply. Does not
indicate the status of the 3.3 V power output.
OK ON indicates the CPU has passed its power diagnostics and is functioning
properly. OFF indicates a CPU problem.
RUN Green when the CPU is in Run mode. Amber when the CPU is in Stop/IO Scan
mode. If this LED is OFF but OK is ON, the CPU is in Stop/No IO Scan
mode. ( may change w.r.t family of CPU , however “RUN “ should always
Steady & Green )
FAULT ON if the CPU is in Stop/Faulted mode because a fatal fault has occurred.
To turn off the Fault LED, clear both the I/O Fault Table and the PLC
Fault Table.
Similarly some of RACK based modules do have LED indicators.Please refer the
relevant product manual for Diagnostics LEDs
General:
General Diagnostics tools for Control System will be like protocol analysers, ping test
tool , protocol simulators, port monitor softwares. Now a days widely open many
such software tool exists can be used to diagnosis the network, or communication
ports.
GE Intelligent Platform have such tools general tool to test the Serial port or Ethernet
communication for its products namely:
UDP Station Manager (see below to download) - used to remotely connect (over
Ethernet) to the Station Manger built into the Ethernet interface.
Resolution:
Machine Edition users (Version 6.00 and later):
UDP Station Manager is not included on a Machine Edition install.
Serial comm test tool is accessible by going into the Utilities tab in the Navigator (2nd
tab from left), then double click on Serial Communication Utility to launch the tool.
Before using Station Manager utility the recommended procedure is to look at status
lights on the Ethernet module/CPU.
Ethernet modules have LED indicators. ( may change the description in other family )
Normal operation communications:
SER OFF
STAT ON (SOLID)
If OK light is off or turns off, do not proceed further. The hardware may be defective,
check the PLC fault table.
Hitting the restart pushbutton if the module has locked up can reset communications.
Also check to see if the module is responding by pinging the IP address from the
command prompt.
i.e. >ping 3.26.15.169
Serial Version: Need to use serial cable IC693CBL316A to RJ11 connection on the
module/CPU or a serial 9-pin Null modem cable for PAC Systems. Connect with
HyperTerminal using default settings.
(Data Rate = 9600, Parity = NONE, Flow Control = NONE, Stop Bits = 1);
TALLY command.
This is an example of a Station Manager connection to a PAC system CPU. You may
not get all this information displayed depending on your CPU/module type.
>Node
REM> IC698 Embedded Ethernet Interface
REM> Copyright (c) 2003. All rights reserved.
REM> Version 1.00 (21A1) TCP/IP
REM> Version 1.00 (21A1) Loader
REM> IP Address = 3.26.15.169 Subnet Mask = 255.255.252.0
REM> Gateway = 3.35.6.4
REM> MAC Address = <<08001900F458>>
REM> SNTP Not Configured
REM>
REM> Station Manager Port:
REM> Data Rate = 9600, Parity = NONE, Flow Control = NONE
REM>
REM> Source of Soft Switches: PLC Configuration
REM> Source of IP Address: Configuration
REM>
REM> Mar 1, 2000 4:17:00.6
REM> Date/time initialized from PLC CPU
REM>
>LOG
REM> <<< Exception Log >>>
REM> IC698 Embedded Ethernet Interface version 1.00 (21A1)
REM> Log displayed 01-MAR-2000 02:28:28.3
REM> Log initialized using valid RAM information
REM> Log last cleared 31-DEC-1999 23:56:56.8
REM> Date Time Event Count Entry 2 through Entry 6
REM> 24-FEB-2000 18:51:27.1 28H 0H 001dH 004bH 0000H 0004H 0187H
REM> 24-FEB-2000 20:40:10.2 28H 0H 001dH 004bH 0000H 0004H 0187H
REM> 24-FEB-2000 22:09:24.2 28H d21eH 001dH 004bH 0000H 0004H 0187H
REM> 24-FEB-2000 22:09:24.8 20H 1H 0001H 8080H 0000H 0001H 0290H
REM> 24-FEB-2000 22:10:51.3 28H 1edH 001dH 004bH 0000H 0004H 0187H
REM>
To view Event code descriptions see Appendix B GFK-1186G
Important note:
If log file is full, the status light on the module will go out. Clearing the log will remove log entries and turn on the
status light on.
May want to troubleshoot why the stat went out before resetting log.
>Clear Log
The CLEAR command has the form:
>Tally
Tally is used to check the number of active connections. See appendix C for Tally descriptions.
TCPIP Ethernet Communications Station Manager Manual- GFK-1186G
There is one other command. Stat which is commonly used to check the status of communications. This can be
handy in troubleshooting communications setup Example - Stat g to see if EGD packets are being consumed or
produced.
- Stat b to check memory usage to see if the Ethernet port is overloaded.
>Stat
REM> Usage: stat <task(s)>
REM> Where <task(s)> includes any of the following
REM>
REM> s - Flash File System t - FTP Server
REM> e - WEB Server l - Network Interface
REM> j - ICMP/IGMP u - UDP
REM> w - TCP i - IP
REM> *** All parameters converted to lower case unless within quotes
REM>
Controller :
In the Project tab of the Navigator, double-click the online target Controller
whose Fault Tables you want to view or modify.
- or -
In the Project tab of the Navigator, right-click the online target Controller whose Fault
Tables you want to view or modify, and choose Diagnostics.
- or -
In the Status bar, double-click the online target icon whose Fault Tables you want to
view or modify.
To switch between the Controller Fault Table and the I/O Fault Table:
In the left pane of the current Fault Table, select the appropriate button (Controller or
I/O).
In the Fault Table, click the fault entry you want details on.
Note: You can expand multiple entries.
To set the Fault Extra Data's Format, select the appropriate button in the left pane
(Byte, Word, or ASCII).
IMPORTANT NOTE!!!!
Don’t Clear fault table unless you have saved & stored incase of any abnormality.
Fault table once cleared cannot be retrieved. However Access Level to the
programmer for controller can avoid accident use any un-authorised user
For detailed description of fault you need to refer respective product controller family
system manual.
PACSAnalyzer:
In case of Programmer is not able to connect in some cases to retrieve the fault .GE
Intelligent Platforms have the toll called ”PACSAnalyzer” . ( can be used anytime )
SCADA/HMI:
We can resolve problems by examining the various log files in order to identify
• Errors.
• Error sources.
• Other relevant logging information.
Note: you can Set the Maximum Records Allowed in the Cor_Status.log
A Status Log file can contain up to 1,000 messages. If you are looking for a particular
set of messages, you can filter the file to display only the messages that are currently
of interest to you. Click View on the status log viewer menu bar.
Select Filter Entries.
To view all the details of a particular message, you can do one of the following:
• Double-click on the message.
• Select the message then press Ctrl+D.
• Select the message, and then select Detail from the View menu.
You can contact always GE Intelligent Platforms support team for any fault
description & details incase if you need.