Installation
Ruggedized ABB FOX Switch AFS670 / 675
User Manual
User Manual - Installation
Ruggedized ABB FOX Switch
AFS670 / 675
Disclaimer: ABB has taken reasonable care in compiling this document, however ABB accepts no liability
whatsoever for any error or omission in the information contained herein and gives no other
warranty or undertaking as to its accuracy.
ABB can accept no responsibility for damages, resulting from the use of the network
components or the associated operating software. In addition, we refer to the conditions of
use specified in the license contract.
ABB reserves the right to amend this document at any time without prior notice.
Content
Content 1
Safety instructions 3
1 Legend 8
2 Device description 9
2.1 General device description 9
2.2 Description of the device variants 10
2.3 Connections for voltage-carrying lines 13
2.4 AFS devices with PoE 15
2.5 Signal contact 16
2.6 Combination options 16
4 Technical data 35
Safety instructions
Important Information
Notice: Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, or maintain it. The following special messages may appear throughout this
documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies
or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard
exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate
injury.
Note: Contains important information on the product, on how to manage the product, or on the respective
section of the documentation to which your special attention is being drawn.
Certified usage
The device may only be employed for the purposes described in the catalog and technical description, and only
in conjunction with external devices and components recommended or
approved by the manufacturer. The product can only be operated cor-rectly and safely if it is transported,
stored, installed and assembled pro-perly and correctly. Furthermore, it must be operated and serviced
carefully.
Supply voltage
WARNING
ELECTRIC SHOCK
Only connect a supply voltage that corresponds to the type plate of your device.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
For every supply voltage to be connected, make sure the following requirements are met:
The voltage supply conforms to overvoltage category II.
The voltage supply has an easily accessible disconnecting device (e.g. a switch or a plug).
The disconnecting device is clearly identified so that in the case of an emergency, it is clear which
disconnecting device belongs to which line.
The lines to be connected are voltage-free.
The ground screw on the back of the device is connected to the protective conductor.
There is a fuse in the outer conductor (AC) or the positive conductor (DC) of the voltage supply.
Regarding the properties of this fuse: see “Technical data” on page 35.
When using a DC voltage supply: the fuse is suitable for a DC voltage.
If the neutral conductor (AC) or the negative conductor (DC) is not grounded: there is a fuse on each of
the two wires.
Supply with AC voltage: the wire diameter for the input supply line is at least 0.75 mm² (North America:
AWG18).
Supply with DC voltage: the wire diameter for the input supply line is at least 1 mm² (North America:
AWG16).
The cross-section of the protective conductor cable is the same size as or bigger than the cross-section
of the voltage supply cables.
The connection cables used are permitted for the specified temperature range.
Relevant for North America:
For use in Class 2 circuits, the copper wire conforms to class 1, 60/75 °C or 75 °C.
WARNING
ELECTRIC SHOCK
Only start connecting the supply voltage if all the above mentioned requirements are fulfilled.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Make sure that the electrical installation meets local or nationally applicable safety regulations.
Use undamaged parts.
The device does not contain any service components. Internal fuses are only triggered if there is a fault in
the device. If the device is not functioning correctly, or if it is damaged, switch off the voltage supply and
return the device to the plant for inspection.
Only switch on the device when the housing is closed.
First connect the ground screw on the back of the device with the protective conductor before you set up
the other connections. When removing the connections, you remove the protective conductor last.
For voltage supply connections with a protective conductor connection: first connect the protective
conductor before connecting the lines for the supply voltages.
If your device has a second voltage supply connection of this type: here you also first connect the protective
conductor before connecting the lines for the supply voltages.
Shielding ground
The shielding ground of the connectable twisted pairs lines is connected to the front panel as a conductor.
Beware of possible short circuits when connecting a cable section with conductive shielding braiding.
Housing
WARNING
ELECTRIC SHOCK
Never insert any pointed objects (small screwdrivers, wires, etc,.) into the product!
Never insert sharp objects (small screwdrivers, wires, etc.) into the connection terminals for the supply voltage
or the signal contact, and do not touch the terminals!
Only install this device in a switch cabinet or in an operating site with limited access, to which only maintenance
staff have access.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
FIRE HAZARD
Install the device in a fire protected shell if you are mounting it vertically.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Only technicians authorized by the manufacturer are permitted to open the housing.
The ventilation slots must not be covered to promote free air circulation.
The clearance to the ventilation slots of the housing must be at least 10 cm (3.94 in).
Do not touch the housing during operation or shortly after switching off the device. Hot surfaces can cause
injury.
The device must be installed in the horizontal or upright position, either in the switch cabinet or on the wall
(see page 19 „Installing the device“). The device is not intended for operation as a table unit.
Operating the device in the maximum surrounding air temperature and stacking devices: When installing
the device, make sure there is at least one free rack space (approx. 5 cm) above the device, because heat
is discharged via the housing of the device.
If you are operating the device in a 19" switch cabinet: install sliding/mounting rails for holding the device
(see fig. 16).
Environment
The device may only be operated at the specified surrounding air temperature (temperature of the surrounding
air at a distance of up to 5 cm (1.97 in) from the device) and relative air humidity specified in the technical data.
Install the device in a location where the climatic threshold values specified in the technical data will be
observed.
Use the device only in an environment within the pollution degree specified in the technical data.
Non-observance of these safety instructions can therefore cause material damage and/or injuries.
Only appropriately qualified personnel should work on this device or in its vicinity. These personnel must be
thoroughly familiar with all the warnings and maintenance procedures in accordance with this operating
manual.
The proper and safe operation of this device depends on proper handling during transport, proper storage
and assembly, and conscientious operation and maintenance procedures.
Never start operation with damaged components.
Only use the devices in accordance with this manual. In particular, observe all warnings and safety-related
information.
Any work that may be required on the electrical installation may only be carried out by personnel trained for
this purpose.
Please note that products recommended as accessories may have characteristics that do not fully
correspond to those of the corresponding product. This may limit their possible usage in the overall system.
CE marking
The devices comply with the regulations contained in the following European directive(s):
2004/108/EC
Directive of the European Parliament and the council for standardizing the regulations of member states with
regard to electromagnetic compatibility.
2006/95/EC
Directive of the European Parliament and the council for standardizing the regulations of member states with
regard to electrical equipment to be used within specific voltage ranges.
In accordance with the above-named EU directive(s), the EU conformity declaration will be at the disposal of
the relevant authorities at the following address:
ABB Switzerland Ltd
Bruggerstrasse 72
5400 Baden
Tel.: +41 58 589 37 35
The product can be used in the industrial sector.
Interference immunity: EN 61000-6-2:2005
Emitted interference: EN 55022:2010
Safety: EN 60950-1:2006 + A11:2009 + A1:2010
Warning! This is a class A device. This device can cause interference in living areas, and in this case the
operator may be required to take appropriate measures.
Note: The assembly guidelines provided in these instructions must be strictly adhered to in order to observe
the EMC threshold values.
FCC note:
This device complies with part 15 of FCC rules. Operation is subject to the following two conditions : (1) This
device may not cause harmful interference; (2) this device must accept any interference received, including
interference that may cause undesired operation.
Appropriate testing has established that this device fulfills the requirements of a class A digital device in line
with part 15 of the FCC regulations.
These requirements are designed to provide sufficient protection against interference when the device is being
used in a business environment. The device creates and uses high frequencies and can radiate same, and if
it is not installed and used in accordance with this operating manual, it can cause radio transmission
interference. The use of this device in a living area can also cause interference, and in this case the user is
obliged to cover the costs of removing the interference.
Recycling note
After usage, this product must be disposed of properly as electronic waste, in accordance with the current
disposal regulations of your county, state and country.
The Network Management Software AFS View provides you with additional options for smooth configuration and
monitoring:
Configuration of multiple devices simultaneously
Graphical interface with network layouts
Auto-topology discovery
Event log
Event handling
Client / Server structure
Browser interface
ActiveX control for SCADA integration
SNMP/OPC gateway
Legend
The commendations used in this manual have the following meanings:
Listing
Work step
Subheading
1 Device description
1.1 General device description
The ruggedized AFS switch family for substations provides you with a wide range of switch variants. You set up
your own switch according to your requirements regarding the number of ports, transmission speed, media type,
connector type, temperature range, voltage range and software variant.
The AFS devices are designed for the special requirements of industrial automation. They meet the relevant in-
dustry standards, provide very high operational reliability, even under extreme conditions, and also long-term re-
liability and flexibility. The devices work without a fan. If required, the devices are PoE-capable. For devices
without PoE, the voltage supply can be redundant if required. The Switches are mounted in the switch cabinet by
means of brackets, or vertically on the wall.
The E-MRP redundancy concept enables you to quickly carry out a reconfiguration, and also a simple configura-
tion with only one additional connection. Diagnosis displays and the display of the operating parameters provide
a quick overview.
It can be easily managed via a Web browser, via Telnet, with a management software product (such as AFS View)
or locally on the switch (V.24 interface).
The device allows you to set up switched industrial ETHERNET networks that conform to the IEEE 802.3 and
802.3u standards using copper wires or optical fibers in a line or ring structure. You can connect terminal devices
and other infrastructure components via twisted pair cables, multi-mode F/O and single-mode F/O. The twisted
pair ports support
autocrossing, autonegotiation and autopolarity.
Depending on the software you choose, the devices provide you with a large range of functions:
Redundancy functions
(Rapid Spanning Tree, Redundant Ring Structure, E-MRP, Redundant Coupling, Link Aggregation, for devices
without PoE Redundant Power Supply)
Protection from unauthorized access
Synchronized system time in the network
Network load control
Operation diagnosis
Diagnostics (hardware self-testing)
Reset
Priority
VLAN
Topology Discovery
Web-based Interface
Command Line Interface CLI
SNMP
802.1x port authentication
Real Time Clock
The devices differ with regard to the range of software functions, the number of interfaces, and the media type for
connecting segments.
The AFS670 device variants are ABB FOX Switches without Gigabit ports and, depending on the requirements,
a selectable number (up to 24) of Fast Ethernet ports (10/100 Mbit/s). You can choose the media for the Fast
Ethernet ports 1 to 24 in pairs.
The AFS670-xR devices have an additional fast ethernet port on the front of the device that you can use for
diagnosis purposes.
The AFS670-PE devices support PoE in accordance with IEEE 802.3af.
The PoE ports are the Fast Ethernet ports 1 to 4.
In the AFS670-ER devices, all the cable outlets are at the back, i.e. the ports are on the back of the device.
The AFS670-PR devices support PoE in accordance with IEEE 802.3af.
The PoE ports are the Fast Ethernet ports 1 to 4.
All the cable outlets are at the back, i.e. the ports are on the back of the device.
The AFS675 device variants are ABB FOX Switches with 2 or 4 Gigabit ports (10/100/1000 Mbit/s) and, de-
pending on the requirements, a selectable number (up to 24) of Fast Ethernet ports (10/100 Mbit/s).
You can choose the media for the Fast Ethernet ports 1 to 24 in pairs.
In device variants with 2 Gigabit Ethernet ports, these ports are combo ports (2 x SFP slot: 100/1000 Mbit/s,
alternatively: 2 x twisted pair RJ45 socket: 10/100/1000 Mbit/s).
In device variants with 4 Gigabit Ethernet ports, these can be optionally
- SFP slots (2 x 2 slots),
- twisted pair RJ45 sockets (2 x 2 sockets) or
- 2 x SFP slots plus 2 x twisted pair RJ45 sockets.
The AFS675-ER and AFS675-PR devices have an additional Fast Ethernet port on the front of the device that
you can use for diagnosis purposes.
The AFS675-PE devices support PoE (Power over Ethernet) in accordance with IEEE 802.3af. The PoE
ports are the Fast Ethernet ports 1 to 4.
In the AFS675-ER devices, all the cable outlets are at the back, i.e. the ports are on the back of the device.
The AFS675-PRdevices support PoE (Power over Ethernet) in accordance with IEEE 802.3af. The PoE
ports are the Fast Ethernet ports 1 to 4.
In these devices, all the cable outlets are at the back, i.e. the ports are on the back of the device.
1 1 2 5 6 9 10 13 14 17 18 21 22
USB V.24 LS DA LS DA
3 4 7 8 11 12 15 16 19 20 23 24
AFS675
P RM StandBy
LS DA LS DA
2
R1 R2 FAULT
5 6 9 10 13 14 17 18 21 22 25 26
2 3 4 7 8 11 12 15 16 19 20 23 24
1 3 1 2 5 6 9 10 13 14 17 18 21 22
USB V.24
3 4 7 8 11 12 15 16 19 20 23 24
P RM StandBy
AFS675
LS DA LS DA
2
R1 R2 FAULT
MACH 1000 5 6 9 10 13 14 17 18 21 22 25 26
2 4 3 4 7 8 11 12 15 16 19 20 23 24
Front view of the AFS675 with 4 Gigabit ports (2 x SFP and 2 x RJ45)
1 2 3 4 5
1 3 1 2 5 6 9 10 13 14 17 18 21 22
USB V.24
3 4 7 8 11 12 15 16 19 20 23 24
P RM StandBy AFS675
LS DA LS DA
2
R1 R2 FAULT
MACH 1000 5 6 9 10 13 14 17 18 21 22 25 26
2 4 3 4 7 8 11 12 15 16 19 20 23 24
1 3 1 2 5 6 9 10 13 14 17 18 21 22
USB V.24
3 4 7 8 11 12 15 16 19 20 23 24
P RM StandBy AFS675
LS DA LS DA
2
R1 R2 FAULT
MACH 1000 5 6 9 10 13 14 17 18 21 22 25 26
2 4 3 4 7 8 11 12 15 16 19 20 23 24
And / or: P
10/100/1000 Mbit/s Power over
Twisted pair, RJ45 connections ETHERNET
Fast ETHERNET
FE ports 5 to 24, free choice of connections
E: Module position empty
T: 2 * twisted pair TX, RJ45, 10/100 Mbit/s
D: 2 * Multimode FX DSC 100 Mbit/s
U: 2 * Multimode FX MTRJ 100 Mbit/s
A: 2 * Multimode FX ST 100 Mbit/s
F: 2 * Singlemode FX DSC 100 Mbit/s
B: 2 * Singlemode FX ST 100 Mbit/s
I: 2 * Singlemode Long Haul FX DSC 100 Mbit/s
K: 2 * Singlemode Long Haul FX DSC 200 km 100 Mbit/s
S: 2 * SFP slot 100 Mbit/s
M: 2 * twisted pair TX, M12, 10/100 Mbit/s
V: 2 * Multimode FL ST 10 Mbit/s
AFS675 P RM StandBy 1 3 5 7 9 11 13 15 17 19 21 23
1 2 3 4 5
1 1 2 5 6 9 10 13 14 17 18 21
22
USB V.24 LS DA LS DA
3 4 7 8 11 12 15 16 19 20 23 24
AFS675
P RM StandBy -/N +/L
LS DA LS DA LS DA
2
R1 R2 FAULT
MACH 1000 5 6 9 10 13 14 17 18 21 22 25 26
2 3 4 7 8 11 12 15 16 19 20 23 24
The device variants of the AFS670/675 with ports on the rear panel
have the following characteristics:
The display LEDs are on the front of the device. There are up to 4 LEDs for displaying the status of the
Gigabit Ethernet ports and up to 21 LEDs for displaying the status of the Fast Ethernet ports, as well as 6
LEDs for displaying the device status.
The supply voltage connection and the ports are on the back of the device. The device allows you to connect
a maximum of 20 Fast Ethernet ports as well as an additional Fast Ethernet port on the front of the device
that you can use for diagnosis purposes.
Note: For device variants without PoE: you can connect the supply voltage redundantly for devices with 2 power
supply units. Both inputs are uncoupled.
Note: For device variants without PoE: For device variants with two power units, if there is non-redundant voltage
supply, the device reports the failure of one supply voltage. You can prevent this message by applying the supply
voltage via both inputs, or by changing the configuration in the Management.
A device has one or two internal power supply units. Each power supply unit has a connection for the supply volt-
age and a connection for the signal contact.
The power supply unit types have the following different properties:
Type of connections: terminal or plugged
Type of connectable supply voltages: DC or AC voltage
Level of connectable supply voltages:
Note: To find out which power supply unit type your device has, refer to items 36 and 37 of the product code (see
table 5 on page 17).
The following tables provide an overview of the possible connections for voltage-carrying lines:
1 2
Relay 2 Relay 1
N L N L
1 2 3 4 5 1 2 3 4 5
5
Relay 1
N L
1 2 3 4 5
4 3
USB V.24 LS DA LS DA
3 4 7 8 11 12 15 16 19 20 23 24
AFS675
P RM StandBy -/N +/L
LS DA LS DA LS DA
2
R1 R2 FAULT
MACH 1000 5 6 9 10 13 14 17 18 21 22 25 26
Relay 2
N L
-/N +/L 1 2 3 4 5
-/N +/L
5 2
4 3
The AFS670/675 devices with PoE have 2*2 twisted pair ports TX
10/100 Mbit/s, depending on the device variant, as RJ45 or M12 sockets for connecting network segments or PoE
terminal devices (PD, Powered Device) for all IEEE802.3af classes up to a maximum power output of 15.4 W.
The current is supplied on wire pairs transmitting the signal; the individual ports are not electrically insulated from
each other.
The following conditions are met in accordance with IEEE 802.3af:
Endpoint PSE
Alternative A
Note: You can use the signal contact functions when the voltage supply is connected. If there is redundant voltage
supply, but this is turned off, there is a contact interruption at the corresponding signal contact.
a In device variants with PoE (Power over Ethernet), the first four ports can be twisted pair TX RJ45 10/100 Mbit/s (short designation T) or
twisted pair TX M12 10/100 Mbit/s (short designation M), as desired. The remaining ports can be selected freely from the table. Power supply
unit 2 is a PoE power supply unit (incoming voltage range, item 26: “H” or “Z”). You can choose the connections to power supply unit 1.
1 2
To attach an SFP module, first remove the protective cap over the socket.
Push the SFP module with the lock closed into the socket until it latches audibly in place.
2.1.3 Connecting the power unit connections for supply voltage and signal contact
Connecting the voltage supply terminals (power supply units “L” and “H”)
WARNING
ELECTRIC SHOCK
Only connect a supply voltage that corresponds to the type plate of your device.
Never insert sharp objects (small screwdrivers, wires, etc.) into the connection terminals for the supply voltage,
and do not touch the terminals!
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 2
Relay
-/N +/L
1 2 3 4 5
- +
1 2
Relay
-/N +/L
1 2 3 4 5
G
1 2
Relay
-/N +/L
1 2 3 4 5
- +
For every supply voltage to be connected, perform the following steps:
Ensure the required conditions for connecting the supply voltage (see page 3 „Supply voltage“).
WARNING
ELECTRIC SHOCK
Only start connecting the supply voltage if all the above mentioned requirements are fulfilled.
(see page 3 „Supply voltage“)
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Note: To insert the cable, you open the terminal lock by positioning the screwdriver as illustrated below and
pressing on the lever.
-/N +/L
1 2 3 1
Figure 10: Connecting the supply voltage via the 3-pin spring-loaded terminal
1 - Field connection terminal for supply voltage
2 - Terminal lock
Connect the lines for the supply voltage to the terminals +/L and -/N.
Note: Use copper wire with cross-section AWG20 to AWG12 (0.5 mm2 to 3.0 mm2) and stripping length 12
mm.
Connecting the plugged voltage supply (power supply units “Y” and “Z”)
WARNING
ELECTRIC SHOCK
Only connect a supply voltage that corresponds to the type plate of your device.
Never insert sharp objects (small screwdrivers, wires, etc.) into the connection terminals for the supply voltage,
and do not touch the terminals!
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Note: The terminal blocks for devices with power unit type “Z” (type “Y”) are coded to prevent them from being
accidently connected to devices with power unit type “Y” (type “Z”).
1 2
-/N +/L
4
1 2
1 2
Relay
Figure 12: Power supply unit “Y”, DC voltage (see page 35 „General technical data“)
Connection for
1 - supply voltage
2 - signal contact
1 2 1 2
Relay Relay
-/N +/L -/N +/L
Figure 13: Power supply unit “Z” (see page 35 „General technical data“):
AC voltage (pictured on right) or DC voltage (pictured on left)
Connecting
1 - Supply voltage
2 - Signal contact
WARNING
ELECTRIC SHOCK
Only start connecting the supply voltage if all the above mentioned requirements are fulfilled.
(see page 3 „Supply voltage“)
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
ELECTRIC SHOCK
Never insert sharp objects (small screwdrivers, wires, etc.) into the connection terminals for the signal lines, and
do not touch the terminals!
Failure to follow these instructions can result in death, serious injury, or equipment damage.
For every signal contact to be connected, make sure the following requirements are met:
The lines to be connected are voltage-free.
The connected voltage is limited by a current limitation or a fuse.
Observe the electrical threshold values for signal contact (see on page 35 „General technical data“).
For every signal contact to be connected, perform the following steps:
For terminal connections: connect the signal contact lines to the connection terminals.
Note: To insert the cable, you open the terminal lock by positioning the screwdriver as illustrated below and
pressing on the lever.
Note: Use copper wire with cross-section AWG 20 to AWG 12 (0.5 mm2 to 3.0 mm2) and stripping length
12 mm.
Relay
Figure 14: Connecting the switching voltage via the 2-pin spring-loaded terminal
1 - Field connection terminal for switching voltage
2 - Terminal lock
For plugged connections: connect the signal contact lines with the terminal block connections. Mount the
terminal block on the device using screws.
WARNING
ELECTRIC SHOCK
Only install this device in a switch cabinet or in an operating site with limited access, to which only maintenance
staff have access.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
CAUTION
OVERHEATING OF THE DEVICE
When installing the device, ensure that the ventilation slots are not covered.
Non-adherence to these instructions can lead to minor physical injury or material damage.
Note: The shielding ground of the connectable industrial twisted pair lines is connected to the front panel as a
conductor.
Note: Install the device in the 19" switch cabinet using sliding or mounting rails.
This provides a more stable position of your device in environments subject to vibration.
For more information on sliding/mounting rails and how to install them, please contact your switch cabinet
manufacturer.
USB V.24 LS DA LS DA LS DA LS DA
3 4 7 8 11 12 15 16 19 20 23 24
P RM StandBy
AFS675
LS DA LS DA
2
R1 R2 FAULT
5 6 9 10 13 14 17 18 21 22 25 26
Note: Fasten the device with two additional brackets at the back of the switch cabinet when operating it in
environments with strong vibrations (see on page 39 „Accessories“, not included in the delivery).
WARNING
FIRE HAZARD
Install the device in a fire protected shell if you are mounting it vertically.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Use the pre-mounted brackets included in the delivery as shown in the following figure (see fig. 16).
Attach two additional brackets to the device (see on page 39 „Accessories“, not included in the delivery) as
shown in the following figure (see fig. 16).
Fasten the device by screwing the brackets to the wall.
Warning
When installing the device, make sure the ventilation slots remain unobstructed, as otherwise the
device can overheat and be damaged.
Note: The shielding ground of the connectable industrial twisted pair lines is connected to the front panel as a
conductor.
Dimensions
53,2
482,6
31,75
218,25
313,5
31,75
444 44,2
465,9
482,6
465,9
31,8
44
352,5
342
Note: To optimize the data flow, connect the main data traffic to ports 1 and 4.
n.c. 8
n.c. 7
TD- 6
n.c. 5
n.c. 4
TD+ 3
RD- 2
RD+ 1
Figure 18: Pin assignment of a TP/TX interface in MDI-X mode, RJ45 socket
Note: In substation applications, the RJ45 ports are used to connect to additional communication devices such
as routers or telecommunication multiplexers that are installed in close proximity to the device (i.e. less than 3
meters away). It is not recommended to use these ports for connection to field devices across longer distances
which could cause a significant increase in the ground potential (Ground Potential Rise GPR, i.e. more than
2500 V).
BI_DC- 8
BI_DC+ 7
BI_DA- 6
BI_DD- 5
BI_DD+ 4
BI_DA+ 3
BI_DB- 2
BI_DB+ 1
Figure 19: Pin assignment of the 1000 Mbit/s twisted pair interface
Note: In general, you should adhere to the following recommendations for data cable connections using copper
in environments with high electrical interference levels:
Keep the length of the data cables as short as possible - ideally max. 3m long. You should not use any
copper data cables for the data transmission between buildings.
Power supply and data cables should not run parallel over longer distances, and ideally they should be
installed in separate cable channels. If the inductive coupling has to be reduced, the power supply and data
cables should cross at a 90° angle.
You may also choose to use shielded cables (SF/UTP).
n.c. 8
n.c. 7
TD- 6
n.c. 5
n.c. 4
TD+ 3
RD- 2
RD+ 1
Figure 20: Pin assignment of a TP/TX interface in MDI-X mode, RJ45 socket
Table 9: Pin assignment of the TP/TX interface for PoE (M12 socket)
(6) (6)
(6) (6)
(6) (6)
(6) (6)
Note: Make sure that the LH ports are only connected with LH ports, SM ports are only connected with SM
ports, and MM ports only with MM ports.
Note: Make sure that the LH ports are only connected with LH ports, SX ports are only connected with SX ports,
and LX ports only with LX ports.
Note: With the AFS675 with two Gbit/s F/O ports, these ports are combo ports (SFP/RJ45). You can use either
the SFP slot or the RJ45 socket to connect data lines. If both are used, the assigned SFP slot switches off the
related RJ45 port.
USB V.24 LS DA LS DA
3 4
AFS675
P RM StandBy
2
R1 R2 FAULT
5 6
1 2
Figure 22: Display elements of AFS670/675, device variants with ports on the front
1 - Device status display elements
2 - Port status display elements
P RM StandBy 1 3 5 7 9 11 13 15 17 19 21 23
1 2 3
Figure 23: Display elements of AFS670/675, device variants with ports on the back
1 - Device status display elements
2 - Port status display elements for up to 4 Gigabit Ethernet ports and up to 20 Fast Ethernet ports
3 - Diagnosis port with display element
Device state
These LEDs provide information about conditions which affect the operation of the whole device.
P - Power (green/yellow LED)
Glowing green Device variants with 2 power supply units: Both supply voltages are on
Device variants with 1 power supply unit: Supply voltage is on
Glowing yellow Device variants with 2 power supply units: There is only one supply voltage (P1 or P2) on
Not glowing Supply voltage is too low
RM - Ring Manager (green/yellow LED)
Glowing green RM function active, redundant port disabled
Glowing yellow RM function active, redundant port enabled
Not glowing RM function not active
Flashing green Incorrect configuration of the E-MRP (e.g. the ring is not connected to the ring port).
If the manual adjustment is active on the “FAULT” signal contact, then the detected error display is independent
of the setting of the signal contact.
Port state
The green and yellow LEDs at the individual port display port-related information. During the boot phase, these
LEDs are used to display the status of the boot procedure.
LS - data, link status (one green/yellow LED or one green and one yellow LED)
Not glowing No valid connection.
Glowing green Valid connection.
Flashing green (1 time a period) Port is switched to stand-by.
Flashing green (3 times a period) Port is switched off.
Flashing yellow Data reception.
Further information on the basic settings of the device can be found in the "Basic Configuration" user manual on
the CD ROM.
Default settings
IP address: The device looks for the IP address using DHCP
Password for management:
Login: user; password: user (read only)
Login: admin; password: admin (read and write)
Parameters that can be set via the management are set to pre-defined values in accordance with the MIB
V.24 data rate: 9,600 Baud
Ring redundancy: disabled
USB interface
The USB socket has an interface for the local connection of an Configuration Recovery Adapter(part number
CRA see on page 39 „Accessories“). It is used for saving/loading the configuration and for loading the software.
The socket housing is electrically connected to the front panel of the device. The V24 interface is not electrically
isolated from the supply voltage.
RJ11 DB9
Pin 5
Pin 6 Pin 8
Pin 1
Pin 1
CTS 1
n.c. 2 2
TX 3 3
GND 4
RX 5 5
RTS 6
Note: You will find the order number for the terminal cable, which is ordered separately, in the Technical Data
chapter (see page 39 „Accessories“).
You will find a detailed description of the configuration in the “Basic Configuration User Manual”.
2.4 Maintenance
When designing this device, ABB was largely able to forego using wear parts. The parts subject to wear are
dimensioned to last longer than the lifetime of the product when it is operated normally. Operate this device
according to the specifications (see „Technical data“).
Relays are subject to natural wear. This wear depends on the frequency of the switching operations.
Depending on the frequency of the switching operations, check the volume resistance of the closed relay
contacts and the switching function.
ABB are continually working on improving and developing their software. You should regularly check whether
there is a new version of the software that provides you with additional benefits. You will find software
information with your local ABB contact.
Depending on the degree of pollution in the operating environment, check at regular intervals that the
ventilation slots in the device are not obstructed.
USB V.24 LS DA LS DA LS DA LS DA
3 4 7 8 11 12 15 16 19 20 23 24
P RM StandBy
AFS675
LS DA LS DA
2
R1 R2 FAULT
5 6 9 10 13 14 17 18 21 22 25 26
3 Technical data
General technical data
Dimensions AFS67x (ports on front, power supply option 448 x 310 x 44 mm
WxDxH “L” or “H”, spring clamps)
AFS67x (ports on front, power supply option 448 x 345 x 44 mm
“Y” or “Z”, connectors)
AFS67x (ports on rear) 448 x 345 x 44 mm
Weight AFS670-EE fully equipped max. 4.6 kg
(incl. redundant power unit AFS670-EE fully equipped max. 4.7 kg
or PoE power unit) AFS670-ER fully equipped max. 5.4 kg
(incl. redundant power unit)
AFS675-ER fully equipped max. 5.5 kg
(incl. redundant power unit)
AFS670-PR fully equipped max. 5.5 kg
AFS675-PR fully equipped max. 5.6 kg
AFS670-PE fully equipped max. 4.7 kg
AFS675-PE fully equipped max. 4.8 kg
Weight AFS670-EE basic device approx. 3.9 kg
AFS670-EE basic device approx. 4.0 kg
AFS670-ER basic device approx. 4.7 kg
AFS675-ER basic device approx. 4.8 kg
AFS670-PR basic device approx. 5.1 kg
AFS675-PR basic device approx. 5.2 kg
AFS670-PE basic device approx. 4.3 kg
AFS675-PE basic device approx. 4.4 kg
Optional PoE power unit approx. 0.39 kg
Optional second power unit additional approx. 0.3 kg
Per 6 ports (3 modules) additional approx. 0.1 kg
Per M12 module additional approx. 0.09 kg
Power supply Nominal voltage range AC 100 V - 240 V, 50 Hz - 60 Hz
Power unit type “H” and “Z” Voltage range AC, incl. max. tolerance 90 - 265 V, 47 - 63 Hz
Nominal voltage range DC 110 V - 250 V
Voltage range DC, incl. max. tolerance 77 - 300 V
Connection type “H” 3-pin spring-loaded terminal for copper wire with cross-section
AWG 20-12 (0.5 to 3.0 mm2) and stripping length 12 mm
Connection type “Z” 3-pin terminal block
Power failure bridging > 20 ms at 230 V AC
Power unit type “L” and “Y” Nominal voltage DC 24 - 48 V
Voltage range DC incl. maximum tolerances 18 V - 60 V
Connection type “L” 3-pin spring-loaded terminal for copper wire with cross-section
AWG 20-12 (0.5 to 3.0 mm2) and stripping length 12 mm
Connection type “Y” 3-pin terminal block
Power failure bridging > 10 ms at 20.4 V DC
Output voltage for device 48 V DC ± 5%
variants with PoE
Properties of the back-up Power units “L” and “Y” Nominal rating 6.3 A
fuse to be installed for the Characteristic: slow blow
voltage supply Power units “H” and “Z” Nominal rating 2.5 A
Characteristic: slow blow
Signal contact Nominal value for AC Imax = 2 A at Umax = 230 V
Nominal value for DC Imax = 2 A at Umax = 30 V
Imax = 0.2 A at Umax = 125 V
Imax = 0.1 A at Umax = 250 V
Connection type for power units “L” and “H” 2-pin spring-loaded terminal for copper wire with cross-section
AWG 20-12 (0.5 mm2 to 3.0 mm2) and stripping length 12 mm
Connection type for power units “Y” and “Z” 2-pin terminal block
Environment Storage temperature Standard: -40 °C to +70 °C
(ambient air) Extended: -40 °C to +85 °C
Humidity 5% to 95% (non-condensing)
Air pressure Up to 2000 m (795 hPa), higher altitudes on request
Operating temperature Standard (ambient air) 0 °C to +60 °C
Extended (ambient air) -40 °C to +85 °C abcde
Pollution degree 2
Protection classes Laser protection Class 1 according to EN 60825-1 (2001)
Protection class IP 30
a. If you are using SFP modules without the “EEC” extension, then an operating temperature range from 0 °C to +60 °C applies for your
device. (see page 39 „Accessories“)
b. For devices with an extended temperature range equipped with more than 14 F/O ports, the maximum operating temperature is reduced
by 1K for each additional F/O port. Example: AFS670/675 device with extended temperature range and 20 F/O ports: Operating temper-
ature = -40 °C to +79 °C.
c. AFS670/675 device equipped with “K” Fast Ethernet modules (Singlemode Long Haul FX DSC 200 km ): 0 °C to +60 °C
d. -40 °C to + 70 °C for devices with PoE, devices with FL ports and devices with 4 Gigabit Ethernet ports
e. Relevant for North America: maximum operating temperature (ambient air temperature): +70 °C
Network range
TP port
Length of a twisted pair segment max. 100 m / 300 ft (cat5e cable with 1000BASE-T)
Table 14: Fiber port 1000BASE-FX (SFP fiber optic Gigabit ETHERNET Transceiver)
a. including 3 dB system reserve when compliance with the fiber data is observed
b. The bandwidth length product cannot be used to calculate the expansion.
c. With F/O adapter compliant with IEEE 802.3-2002 clause 38 (single-mode fiber offset-launch mode conditioning patch cord)
d. including 2.5 dB system reserve when compliance with the fiber data is observed
Table 15: Fiber port 100BASE-FX (SFP fiber optic Fast ETHERNET Transceiver)
a. including 3 dB system reserve when compliance with the fiber data is observed
AFS675-... basic device (incl. 2 Gigabit Ethernet module combo 10.5 W 35.9 Btu (IT)/h
ports, without Fast Ethernet modules)
AFS675-xyGP (x=E or P, y=E & R) 11.5 W 39.2 Btu (IT)/h
AFS675-xyGT (x=E or P, y=E & R) 14.5 W 49.5 Btu (IT)/h
AFS675-xyGS (x=E or P, y=E & R) 13.0 W 44.4 Btu (IT)/h
Fast Ethernet modules
additionally for each Fast Ethernet FX module 2.0 W 6.9 Btu (IT)/h
additionally for each Fast Ethernet TX module 0.4 W 1.4 Btu (IT)/h
additionally for each PoE module 38.0 W 130.0 Btu (IT)/h
Examples
AFS670-EEETTTTTTTTTTTTPHE 12.3 W 42.0 Btu (IT)/h
Scope of delivery
Accessories
Note: Please note that products recommended as accessories may have characteristics that do not fully cor-
respond to those of the corresponding product. This may limit their possible usage in the overall system.
Name
EN 61000-6-2 Generic norm – immunity in industrial environments
EN 55022 IT equipment – radio interference characteristics
IEC/EN 60950-1 Safety for the installation of IT equipment
EN 61131-2 Programmable logic controllers
EN 50121-4 Railway applications - EMC - emitted interference and interference immunity for signal and telecommunication
systems
EN 50155 Railway applications - electronic systems in railway vehicles
FCC 47 CFR Part 15 Code of Federal Regulations
cUL 508:1998 Safety for Industrial Control Equipment
EN 61850-3 Communications networks and systems in stations
IEEE 1613 Standard Environment and Testing Requirements for Communication Networking Devices in Electric Power Sub-
stations
www.abb.com/utilitycommunication