Calculate Size of Diesel Generator Set

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 2

CALCULATE SIZE OF DIESEL GENERATOR SET Jignesh.N.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.

com
System Voltage ( P-P ) 415 Volt Linear Load: General Equipments, Heater
System Voltage ( P-N ) 230 Volt Non-Linear Load: UPS,Invertor,Ballast,VFD
Future Load Expansion 0% % 1
Average Intermittent Use of
0.8 (0.7 To 1.0) 0.8
Equipment
Total Connected Load on Diesel Generator Set Starting Condition Running Condition
Load Full Full Full
Sr. Starting Running Diversity Motor Starting Starting Starting
Equipment Load Type Supply Qty Load Load Load
No Load Kw/Hp P.F P.F Factor Starter Amp Kva Kw
Kva Kw Amp RESULTS
light&small power DB MAIN
Linear 3Ph 1 83 Kw 0.8 0.8 0.5 72 52 42 52 42 72 Starting Kva 1588
BUILDING A

light&small power DB MAIN


Linear 3Ph 1 83 Kw 0.8 0.8 0.5 72 52 42 52 42 72 Starting Kw 1271
BUILDING B

light&small power DB Service


Linear 3Ph 1 66 Kw 0.8 0.8 0.5 57 41 33 41 33 57 Starting Amp 2210
BUILDING

light&small power DB
Linear 3Ph 1 44 Kw 0.8 0.8 0.5 38 28 22 28 22 38 Running Kva 1382
Administration Building

light&small power NEW building DB Linear 3Ph 1 33 Kw 0.8 0.8 0.5 29 21 17 21 17 29 Running Kw 1106

UPS DB basement MAIN BUILDING


Non-Linear 3Ph 1 48 Kw 0.8 0.8 0.5 67 48 38 48 38 42 Running Amp 1525
A

NEW medical UPS DB MAIN


Non-Linear 3Ph 1 80 Kw 0.8 0.8 0.5 111 80 64 80 64 70 Alternator Details
BUILDING B

NETWORK UPS DB MAIN


Non-Linear 3Ph 1 80 Kw 0.8 0.8 0.5 111 80 64 80 64 70 Voltage (P-N) 230
BUILDING B

NEW medical DB MAIN BUILDING


Non-Linear 3Ph 1 166 Kw 0.8 0.8 0.5 231 166 133 166 133 144 Efficiency 80%
B

WATER Treat+Mortuary
fire+building Pump MAIN BUILDING Motor 3Ph 1 110 Kw 0.8 0.8 0.5 Y-D 383 275 220 69 55 96 Engine Overload Capacity 130% (Appro 130% To 150%)
B

SEIMENSE medical DB MAIN


Non-Linear 3Ph 1 240 Kw 0.8 0.8 0.5 334 240 192 240 192 209
BUILDING B

Laundry machines Service


Non-Linear 3Ph 1 108 Kw 0.8 0.8 0.5 150 108 86 108 86 94 Required Generator Rating
BUILDING

kitchen machines Service


BUILDING
Non-Linear 3Ph 1 40 Kw 0.8 0.8 0.5 56 40 32 40 32 35 Generator KVA 1271 (Select D.G near This Value)

HVAC ROOF TOP MAIN BUILDING


A
Linear 3Ph 1 127 Kw 0.8 0.8 0.5 110 79 64 79 64 110 Engine KW 1150

NEW HVAC ROOF TOP MAIN


Linear 3Ph 1 266 Kw 0.8 0.8 0.5 231 166 133 166 133 231
BUILDING A

HVAC DBs&2chiller MAIN


Linear 3Ph 1 100 Kw 0.8 0.8 0.5 87 63 50 63 50 87
BUILDING B

HVAC Service building Service


Linear 3Ph 1 80 Kw 0.8 0.8 0.5 70 50 40 50 40 70 Calculate D.G Set Efficiency & Unit Calculate Approximate
BUILDING
Rate of Power Fuel Consumption
0 0 0 0 0 0
0 0 0 0 0 0 D.G Size ( Kva ) 1000
0 0 0 0 0 0 D.G P.F 1 D.G Size (Kva) 115
0 0 0 0 0 0 D.G Running Hours 20 D.G P.F 0.8
0 0 0 0 0 0 Diesel Consumption (Liter) 1000 D.G Operation Full Load
0 0 0 0 0 0 KWH Reading of Meter 10000
0 0 0 0 0 0 M.F of KWH Meter 1 Required Diesel
0 0 0 0 0 0 Diesel Rate /Liter (Rs) 40 Liter/Hour 23.11
0 0 0 0 0 0 Efficiency of D.G 63%
0 0 0 0 0 0 KWH/Liter (Unit Per Liter) 10
0 0 0 0 0 0 Unit Rate of Power (Rs) 4.0
0 0 0 0 0 0