SWITCHGEAR COMPLEX

CVE CVE CVE CVE CVE CVE CVE CVE


1. TYPE DESIGNATION : UNIT
72.5/325/50 145/650/50 145/650/50 170/750/50 245/1050/50 300/1050/50 362/1300/50 420/1425/50

2. APPLICABLE STANDARDS : IEC 44-2; IEC 186 (1987) IEC 358 (1990); IEC 44-2 : IEC 44-5; IEC 44-5 CAPACITIVE VOLTAGE TRANSFORMER
3. HIGHEST SYSTEM VOLTAGE : kV 72.5 123 145 170 245 300 362 420 (72.5 TO 420 kV)
4. ONE MIN POWER FREQUENCY VOLTAGE : kV 140 230 275 325 460 510 570 630
5. LIGHTNING IMPULSE : kVp 325 550 650 750 1050 1050 1300 1425
6. SWITCHING IMPULSE : kVp NA 850 950 1050
7. RATED FREQUENCY : Hz 50/60
8. AMBIENT TEMPERATURE : °C -25 TO 50
9. SEISMIC ACCELERATION : g 0.3/0.5
10. RATED VOLTAGE FACTOR : – 1.2 (CONT) / 1.5 (30 SEC)
11. ONE MIN. POWER FREQUENCY
: kV 3
VOLTAGE ON SECONDARY
12. SECONDARY VOLTAGE : V 100, 100/√3, 110, 110/√3 , 120 , 120/ √3.
13. TOTAL CREEPAGE DISTANCE : mm 1810 3075 3625 4250 6125 7500 9050 10500
14. EQUIVALENT CAPACITANCE : pF 8800 6000 6000 6000 4400 4400 4400 4400
15. TOTAL SIMULTANEOUS BURDEN / ACCURACY : – 200VA / CL 0.5
16. TOTAL THERMAL BURDEN : VA 500VA 750VA
17. CANTILEVER LOAD : kg 125 200 250
18. ARCING DISTANCE : mm 820 1215 1215 1415 1930 2180 2630 2830
19. TOTAL HEIGHT (H) : mm 1950 2350 2350 2550 3410 3655 4175 4370
20. MAXIMUM DEPTH (A) : mm 785 785 785 785 785 785 850 850
21. MOUNTING DIMENSIONS (W) : mm 450 450 450 450 450 450 450 450
22. TOTAL WEIGHT : kg 315 360 430 450 575 600 810 825
23. QTY OF OIL : kg 75 90 95 100 115 125 200 210
24. OIL VOLUME COMPENSATION (CC UNIT) : – STAINLESS STEEL BELLOW
25. ALTITUDE : m UPTO 1000

OPTIONALS
TYPE DESIGNATION : UNIT CVE CVE CVE CVE CVE CVE CVE CVE
1. HIGHEST SYSTEM VOLTAGE : kV 72.5 123 145 170 245 300 362 420
2. VOLTAGE FACTOR : – 1.9 FOR 30 SEC —
3. CREEPAGE DISTANCE : mm/kV 25, 31, 35 25
4. TOTAL SIMULTANEOUS BURDEN / ACCURACY : – 200 VA / CL 0.2 100 VA /CL 0.2

These parameters are typical values. For other specifications, please contact us.

Switchgear Complex
A-3, MIDC, Ambad, Nashik - 422 010 India
Tel : (+91) 253 2301661 to 674
Fax : (+91) 253 2381247
E-mail : ranjan.pendharkar@cgl.co.in
URL : www.cglonline.com
Regd. Office : 6th Floor, CG House, S W I T C H G E A R C O M P L E X
Dr. Annie Besant Road, Worli, Mumbai - 400 030, India.
Data subject to change Cat.No. CVT-112 (7/07/5K)
SWITCHGEAR COMPLEX CAPACITIVE VOLTAGE TRANSFORMER SWITCHGEAR COMPLEX

FIG. 1 More than 9500 Crompton Greaves Capacitive Voltage (from the top surface) to maintain a positive oil FIG. 2
Transformers upto 420 kV have been put into service pressure even at lowest ambient temperatures. The
1 A - HV Terminal Zd - Damping Device
in various environments in over 60 countries all over CVT thus has very low PD levels even at low ambient C1 - Pri. Capacitance V - Varistor
2
the world since 1984 where they are operating temperatures. C2 - Sec. Capacitance D - Drain Coil
22 NHF- HF Terminal S - Surge Arestor
21
satisfactorily. L - Compensating Choke ES - Earthing Switch
Electromagnetic Unit Tr - Intermediate Voltage N - Neutral Terminal Of
3 Our CVTs adhere to the requirements of the Transformer Intermediate

4
International quality standards and our quality and The Electromagnetic Unit (EMU) consists of a medium F - HRC Fuse Transformer

environment management systems are certified to voltage transformer, compensating reactor, damping

ARCING DISTANCE
ISO 9001–2000 and ISO 14001 respectively. element and surge protection device. The unit is
housed inside a steel tank which is filled with insulating A
5
DESIGN AND CONSTRUCTION oil leaving a largely dimensioned air cushion at the top
in order to take care of changes in the oil volume due
Figure 1 shows the schematic view as well as the
to fluctuations in the ambient temperature. An oil level
construction of a single stack CVT. Each CVT consists H

ARCING DISTANCE
C1
C1 indivator is mounted on the side wall of the tank.
of a coupling capacitor (CC) which acts as a voltage
divider and an Electro Magnetic Unit (EMU) which The CC unit is mounted on the EMU tank and the
transforms the medium voltage to standard low insulated earth terminal of the CC (marked as ‘NHF’ in
voltage. Depending on the system voltage the CC can Fig.1) is also accessible for connecting to power line H C2

be a single or a multi stack unit. The CC and the EMU carrier communication equipment. A surge arrester
are individually hermetically sealed to ensure accurate across this terminal and earth serves as the surge
NHF
C2
performance and high reliability. protection device. The NHF terminal must always be
L Link D S ES
connected to earth if the CVT is not connected to Tr
6 F 1a

7
Coupling Capacitor carrier equipment. F
1n
2a
20
2n
8 The Coupling Capacitor (CC) acts as a voltage divider The secondary terminal box is provided on the EMU Za v
f
g
19 23 and converts the system voltage to a medium voltage. tank. Secondary leadouts, NHF lead and earth leads N
Link

18 9 The active part of the CC consists of a large number are all terminated inside the secondary terminal box.
24
of oil impregnated paper (or paper and film) capacitor The EMU is caliberated and adjusted at factory for all A A
Name plate
17 elements connected in series. Supercalendered burden and accuracy requirements. No site
10
16 capacitor tissue paper and pure aluminium foils are adjustments or measurements are neccessary. The
15
11 used to make the capacitor elements. The capacitor EMU is given adequate surface treatment for corrosion W W

12 elements are pressed and held in insulating supports protection for life long service.
14
13 to ensure a stable capacitance even for large W W

temperature variations. The electrical connections MAINTENANCE


BOTTOM VIEW BOTTOM VIEW
CAPACITOR VOLTAGE TRANSFORMER between the capacitor elements are designed for a The product is self contained, maintenance free
natural frequency much above 600 Hz in order to avoid and requires no spares over its entire life span. We FIG. 3
1 H.V. Terminal φ30×80 13 EMU Tank

2 Hood for L.T. Pedestal Mount. 14 Oil Sampling Valve


interference with carrier communication. recommend regular and periodic checks as per
3 Porcelain Flange 15 Earthing Pads The processed capacitor stack is assembled inside a pre-specified schedules (specified in the Instruction
4 S.S. Bellow 16 Compensating Choke porcelain insulator with corrosion resistant aluminium Manuals supplied with the CVTs).
5 Porcelain Insulator 17 M.V. Tap Terminal
alloy end fittings. Brown glazed porcelain insulators
6 Oil Filling Plug (For EMU) 18 Oil level Indicator (For EMU)
with shed profile as per IEC 815 are used. The OPTIONALS / ACCESSORIES
7 Lifting Lugs 19 NHF Terminal
insulators are cemented to aluminium alloy flanges for • Terminal Connector (Aluminium/Bimetallic, NEMA
8 Secondary Terminal Box 20 Tank Cover
improved strength. Oil volume changes due to or as per customer specs)
9 Varistor 21 Bellow Level Indicator (for capacitor unit)
temperature variations are compensated by a stainless • Three element Carrier Protection Device Level
10 L.V. Terminal Block 22 Chamber For Indicator

11 Gland Plate 23 Earthing Switch (Optional)


steel bellow installed at the upper end of the CC. The (comprising Drain Coil, surge Arrester & Earth
BELLOW POSITION INDICATOR OIL LEVEL INDICATOR ON EMU
12 Surge Arrestor 24 Drain Coil (Optional) unit is completely filled with degassed insulated oil Switch)
under vacuum. The bellow is pressurised by inert gas • Cable Glands
SWITCHGEAR COMPLEX CAPACITIVE VOLTAGE TRANSFORMER SWITCHGEAR COMPLEX

FIG. 1 More than 9500 Crompton Greaves Capacitive Voltage (from the top surface) to maintain a positive oil FIG. 2
Transformers upto 420 kV have been put into service pressure even at lowest ambient temperatures. The
1 A - HV Terminal Zd - Damping Device
in various environments in over 60 countries all over CVT thus has very low PD levels even at low ambient C1 - Pri. Capacitance V - Varistor
2
the world since 1984 where they are operating temperatures. C2 - Sec. Capacitance D - Drain Coil
22 NHF- HF Terminal S - Surge Arestor
21
satisfactorily. L - Compensating Choke ES - Earthing Switch
Electromagnetic Unit Tr - Intermediate Voltage N - Neutral Terminal Of
3 Our CVTs adhere to the requirements of the Transformer Intermediate

4
International quality standards and our quality and The Electromagnetic Unit (EMU) consists of a medium F - HRC Fuse Transformer

environment management systems are certified to voltage transformer, compensating reactor, damping

ARCING DISTANCE
ISO 9001–2000 and ISO 14001 respectively. element and surge protection device. The unit is
housed inside a steel tank which is filled with insulating A
5
DESIGN AND CONSTRUCTION oil leaving a largely dimensioned air cushion at the top
in order to take care of changes in the oil volume due
Figure 1 shows the schematic view as well as the
to fluctuations in the ambient temperature. An oil level
construction of a single stack CVT. Each CVT consists H

ARCING DISTANCE
C1
C1 indivator is mounted on the side wall of the tank.
of a coupling capacitor (CC) which acts as a voltage
divider and an Electro Magnetic Unit (EMU) which The CC unit is mounted on the EMU tank and the
transforms the medium voltage to standard low insulated earth terminal of the CC (marked as ‘NHF’ in
voltage. Depending on the system voltage the CC can Fig.1) is also accessible for connecting to power line H C2

be a single or a multi stack unit. The CC and the EMU carrier communication equipment. A surge arrester
are individually hermetically sealed to ensure accurate across this terminal and earth serves as the surge
NHF
C2
performance and high reliability. protection device. The NHF terminal must always be
L Link D S ES
connected to earth if the CVT is not connected to Tr
6 F 1a

7
Coupling Capacitor carrier equipment. F
1n
2a
20
2n
8 The Coupling Capacitor (CC) acts as a voltage divider The secondary terminal box is provided on the EMU Za v
f
g
19 23 and converts the system voltage to a medium voltage. tank. Secondary leadouts, NHF lead and earth leads N
Link

18 9 The active part of the CC consists of a large number are all terminated inside the secondary terminal box.
24
of oil impregnated paper (or paper and film) capacitor The EMU is caliberated and adjusted at factory for all A A
Name plate
17 elements connected in series. Supercalendered burden and accuracy requirements. No site
10
16 capacitor tissue paper and pure aluminium foils are adjustments or measurements are neccessary. The
15
11 used to make the capacitor elements. The capacitor EMU is given adequate surface treatment for corrosion W W

12 elements are pressed and held in insulating supports protection for life long service.
14
13 to ensure a stable capacitance even for large W W

temperature variations. The electrical connections MAINTENANCE


BOTTOM VIEW BOTTOM VIEW
CAPACITOR VOLTAGE TRANSFORMER between the capacitor elements are designed for a The product is self contained, maintenance free
natural frequency much above 600 Hz in order to avoid and requires no spares over its entire life span. We FIG. 3
1 H.V. Terminal φ30×80 13 EMU Tank

2 Hood for L.T. Pedestal Mount. 14 Oil Sampling Valve


interference with carrier communication. recommend regular and periodic checks as per
3 Porcelain Flange 15 Earthing Pads The processed capacitor stack is assembled inside a pre-specified schedules (specified in the Instruction
4 S.S. Bellow 16 Compensating Choke porcelain insulator with corrosion resistant aluminium Manuals supplied with the CVTs).
5 Porcelain Insulator 17 M.V. Tap Terminal
alloy end fittings. Brown glazed porcelain insulators
6 Oil Filling Plug (For EMU) 18 Oil level Indicator (For EMU)
with shed profile as per IEC 815 are used. The OPTIONALS / ACCESSORIES
7 Lifting Lugs 19 NHF Terminal
insulators are cemented to aluminium alloy flanges for • Terminal Connector (Aluminium/Bimetallic, NEMA
8 Secondary Terminal Box 20 Tank Cover
improved strength. Oil volume changes due to or as per customer specs)
9 Varistor 21 Bellow Level Indicator (for capacitor unit)
temperature variations are compensated by a stainless • Three element Carrier Protection Device Level
10 L.V. Terminal Block 22 Chamber For Indicator

11 Gland Plate 23 Earthing Switch (Optional)


steel bellow installed at the upper end of the CC. The (comprising Drain Coil, surge Arrester & Earth
BELLOW POSITION INDICATOR OIL LEVEL INDICATOR ON EMU
12 Surge Arrestor 24 Drain Coil (Optional) unit is completely filled with degassed insulated oil Switch)
under vacuum. The bellow is pressurised by inert gas • Cable Glands
SWITCHGEAR COMPLEX

CVE CVE CVE CVE CVE CVE CVE CVE


1. TYPE DESIGNATION : UNIT
72.5/325/50 145/650/50 145/650/50 170/750/50 245/1050/50 300/1050/50 362/1300/50 420/1425/50

2. APPLICABLE STANDARDS : IEC 44-2; IEC 186 (1987) IEC 358 (1990); IEC 44-2 : IEC 44-5; IEC 44-5 CAPACITIVE VOLTAGE TRANSFORMER
3. HIGHEST SYSTEM VOLTAGE : kV 72.5 123 145 170 245 300 362 420 (72.5 TO 420 kV)
4. ONE MIN POWER FREQUENCY VOLTAGE : kV 140 230 275 325 460 510 570 630
5. LIGHTNING IMPULSE : kVp 325 550 650 750 1050 1050 1300 1425
6. SWITCHING IMPULSE : kVp NA 850 950 1050
7. RATED FREQUENCY : Hz 50/60
8. AMBIENT TEMPERATURE : °C -25 TO 50
9. SEISMIC ACCELERATION : g 0.3/0.5
10. RATED VOLTAGE FACTOR : – 1.2 (CONT) / 1.5 (30 SEC)
11. ONE MIN. POWER FREQUENCY
: kV 3
VOLTAGE ON SECONDARY
12. SECONDARY VOLTAGE : V 100, 100/√3, 110, 110/√3 , 120 , 120/ √3.
13. TOTAL CREEPAGE DISTANCE : mm 1810 3075 3625 4250 6125 7500 9050 10500
14. EQUIVALENT CAPACITANCE : pF 8800 6000 6000 6000 4400 4400 4400 4400
15. TOTAL SIMULTANEOUS BURDEN / ACCURACY : – 200VA / CL 0.5
16. TOTAL THERMAL BURDEN : VA 500VA 750VA
17. CANTILEVER LOAD : kg 125 200 250
18. ARCING DISTANCE : mm 820 1215 1215 1415 1930 2180 2630 2830
19. TOTAL HEIGHT (H) : mm 1950 2350 2350 2550 3410 3655 4175 4370
20. MAXIMUM DEPTH (A) : mm 785 785 785 785 785 785 850 850
21. MOUNTING DIMENSIONS (W) : mm 450 450 450 450 450 450 450 450
22. TOTAL WEIGHT : kg 315 360 430 450 575 600 810 825
23. QTY OF OIL : kg 75 90 95 100 115 125 200 210
24. OIL VOLUME COMPENSATION (CC UNIT) : – STAINLESS STEEL BELLOW
25. ALTITUDE : m UPTO 1000

OPTIONALS
TYPE DESIGNATION : UNIT CVE CVE CVE CVE CVE CVE CVE CVE
1. HIGHEST SYSTEM VOLTAGE : kV 72.5 123 145 170 245 300 362 420
2. VOLTAGE FACTOR : – 1.9 FOR 30 SEC —
3. CREEPAGE DISTANCE : mm/kV 25, 31, 35 25
4. TOTAL SIMULTANEOUS BURDEN / ACCURACY : – 200 VA / CL 0.2 100 VA /CL 0.2

These parameters are typical values. For other specifications, please contact us.

Switchgear Complex
A-3, MIDC, Ambad, Nashik - 422 010 India
Tel : (+91) 253 2301661 to 674
Fax : (+91) 253 2381247
E-mail : ranjan.pendharkar@cgl.co.in
URL : www.cglonline.com
Regd. Office : 6th Floor, CG House, S W I T C H G E A R C O M P L E X
Dr. Annie Besant Road, Worli, Mumbai - 400 030, India.
Data subject to change Cat.No. CVT-112 (7/07/5K)